| 2018-02-13 09:27:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH |
| | EDITION (2014) AND NEC 2010. THE FBC SIXTH EDITION |
| | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW |
| | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED |
| | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION |
| | (2017) AND NEC 2014. SEE THE COVER SHEET AND PAGES 3.0, |
| | 7.0 AND 9.0. |
| | |
| | 2) FBC R302.6 REQUIRES NOT LESS THAN 5/8" TYPE X GYPSUM |
| | BOARD OR EQUIVALENT TO SEPARATE THE GARAGE FROM |
| | HABITABLE ROOMS ABOVE. THE WALL SECTION 1 ON PAGE 7.0 |
| | DOES NOT SPECIFY 5/8 ' TYPE X DRYWALL ON THE CEILING. |
| | |
| | 3) REVISE THE EXTERIOR GLAZING NOTES ON SHEET 7.0 TO |
| | REFERENCE THE 2017 FBC-R. |
| | |
| | 4) SPECIFY THE SIZE OF THE ATTIC ACCESS OPENING ON THE |
| | PLANS. FBC-R 807.1 |
| | |
| | 5) SUBMIT TWO SETS OF A FLORIDA ENERGY CODE COMPLIANCE |
| | FORM AS REQUIRED BY FBC ENERGY CONSERVATION SECTION |
| | R101.5.1. THE PREPARER'S NAME AND OWNER/AGENT'S |
| | SIGNATURE IS REQUIRED ON THE FORM. |
| | |
| | 6) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING OF THE CORNER AND |
| | PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION #7 OF |
| | NOA NO. 14-1030.02 FOR THE GAF MODIFIED ROOFING SYSTEM. |
| | |
| | 7) NOA NO. 12-0716.04 THAT WAS SUBMITTED FOR THE 12' |
| | WIDE SECTIONAL GARAGE DOOR IS EXPIRED. THE NEGATIVE |
| | DESIGN PRESSURE FROM THE PRODUCT APPROVAL IS -52.0 PSF |
| | WHICH DOES NOT MEET THE REQUIREMENTS OF THE THE DOOR |
| | SCHEDULE AND ELEVATIONS WHICH SPECIFY -53.2 PSF. SUBMIT |
| | TWO SETS OF CURRENT PRODUCT APPROVALS WITH THE DESIGNER |
| | OF RECORD'S REVIEW. FBC 107.3.4.1 |
| | |
| | 8) THE PRODUCT APPROVALS FOR THE "CAST CRETE" LINTELS |
| | NOA NO. 17-0227.15, HAS BEEN SUPERSEDED BY 17-0821.19. |
| | SUBMIT TWO SETS OF CURRENT PRODUCT APPROVALS WITH THE |
| | DESIGNER OF RECORD'S REVIEW. FBC 107.3.4.1 |
| | |
| | 9) SUBMIT TWO SETS OF THE 2017 CODE VERSION OF THE |
| | PRODUCT APPROVALS FOR THE JELD-WEN DOOR, FL 11136 WITH |
| | THE DESIGNER OF RECORD'S REVIEW. THE ONES THAT WERE |
| | SUBMITTED ARE FOR THE 2014 FBC. FBC 107.3.4.1 |
| | |
| | 10) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE |
| | PERMIT VALUATION HAS BEEN INCREASED FROM $40,000.00 TO |
| | $ 165,028.00 BASED ON CURRENT ICC VALUATION DATA. |
| | |
| | 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |