Plan Review Details - Permit 18010447
Plan Review Stops For Permit 18010447
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By cthroop Date 2018-02-01 Time 07:48 Rev Time 0.00
Received By cthroop Date 2018-02-01 Time 07:48 Sent To  
Notes
2018-02-01 07:54:41BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. 4 TIMES FEE APPLIED DUE TO INSTALLATION OF WINDOWS
 WITHOUT PERMIT.
 2. PROVIDE FRAMING PLAN FOR EACH OPENING.
 3. PROVIDE DESIGN WIND LOADS FOR EACH OPENING.
 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS.
 5. IF NEW WINDOWS AREW NOT IMPACT RATED PROVIDE
 SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES.
 6. DESIGNER TO SIGN PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By destabro Date 2018-01-30 Time 09:39 Rev Time 0.00
Received By destabro Date 2018-01-22 Time 14:56 Sent To B
Notes
2018-01-30 09:40:591/30/2018- REQUESTED SITE PHOTOS OF PROPOSED STUCCO
 REPAIR WORK ON 1/24/18. APPLICANT COMPLIED, BUT NO
 PERMIT EXISTS FOR THE REPLACEMENT WINDOWS SINCE THE
 OPENINGS HAVE BEEN REDUCED. THE INSTALLED HORIZONTAL
 SLIDER WINDOWS DO NOT MEET THE DESIGN GUIDELINES FOR
 THE HISTORIC DISTRICT. DLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-01 Cont ID  
Sent By cthroop Date 2018-02-01 Time 07:54 Rev Time 0.00
Received By cthroop Date 2018-01-12 Time 14:46 Sent To I
Notes
2018-01-16 14:46:41ROUTED TO HISTORIC VIA ZONING INBOX