Plan Review Details - Permit 18010446
Plan Review Stops For Permit 18010446
Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-05-12 Cont ID  
Sent By tklarge Date 2018-05-12 Time 09:33 Rev Time 0.00
Received By tklarge Date 2018-05-12 Time 07:23 Sent To I
Notes
2018-05-12 08:30:131) THE GAS DRAWING REFERS TO THE 2014 FBC. THE CODE IN
 EFFECT FOR THIS GAS PERMIT IS THE 2017 FBC BECAUSE
 THESE APPLIANCES WERE SHOWN ON THE ORIGINAL PLANS AS
 ELECTRIC.REVISE THE NOTE ON THE PLAN.
 2) THE COPIES OF THE GAS SIZING TABLES ARE FROM THE
 2014 FBC. THE CODE IN EFFECT FOR THIS PERMIT IS THE
 2017 FBC. SUBMIT TWO COPIES OF EACH APPLICABLE SIZING
 TABLE BEING USED IN THE DESIGN OF THIS GAS SYSTEM. WPB
 AMEND. TO FBC SEC. 107.1.
 3) SUBMIT TWO COPIES OF PAGE 30 FROM THE NAVIEN
 INSTALLATION MANUAL THAT SHOWS THE REQUIRED LOCATION
 AND CLEARANCES OF THE TANKLESS WATER HEATER. WPB AMEND.
 TO FBC SEC. 107.1.
 4) SHOW THE LOCATION OF THE GAS METERS, THE TANKLESS
 WATER HEATERS AND THE INLET AND OUTLET VENTS ON SHT.
 S-1. THE LOCATION OF THE TANKLESS WATER HEATERS AND
 VENTS SHALL COMPLY WITH THE INSTALLATION MANUAL.
 5) THE SUBMITTED RESPONSE NARRATIVE STATES THAT A
 TANKLESS WATER HEATER WILL BE INSTALLED ON THE EXTERIOR
 OF THE BUILDING YET SHT. S-1 SHOWS A TANK TYPE WATER
 HEATER IN THE GARAGE AS CROSSED-OUT WITH AN "X" BUT
 WITH A HANDWRITTEN NOTE STATING "WATER HEATER IN
 GARAGE." IS THE TANK TYPE HEATER IN THE GARAGE BEING
 DELETED OR REMAINIING? THE RESPONSE NARRATIVE STATES "
 WILL WHITE OUT ON SET OF PLANS" BUT NOTHING HAS BEEN
 DONE. CLARIFY.
 6) THE SURROUNDING AREAS ON THE SECOND FLOOR CANNOT BE
 USED FOR SUPPLYING COMBUSTION AIR FOR THE DRYER UNLESS
 LOUVERS ARE INSTALLED IN THESE ROOMS BECAUSE THERE ARE
 DOORS ON THESE ROOMS.THE COMMUNICATING SPACE(S) MUST BE
 OPEN IN ORDER TO BE USED TO COMPLY WITH SEC.G2407.5.
 SUBMIT INFORMATION AS TO HOW COMBUSTION AIR WILL BE
 SUPPLIED FOR THE DRYER. COMPLY WITH 2017 FBCR
 SEC.G2439.5.
 7) INDICATE ON THE PLAN IF THE LAUNDRY ROOM LOUVERED
 BI-FOLD DOORS ARE METAL OR WOOD AND NOTE THE TOTAL
 SQUARE INCH AREA OF EACH OF THE LOUVERS ON EACH DOOR.
 THE NET FREE AREA FOR METAL LOUVERS SHALL BE ASSUMED TO
 BE 75% AND 25% FOR WOOD LOUVERS PER 2017 FBCR
 SEC.G2407.10.
 8) SHOW THE LOCATION OF THE UNDERGROUND PE GAS LINE GAS
 ON SHT. S-1.
 9) THE GAS PIPING RISER NOTES THAT THE GAS SYSTEM IS
 FOR A 12 INCH WATER COLUMN PRESSURE YET YOU HAVE
 SUBMITTED A GAS SIZING TABLE FOR PE PIPE AT A 2 PSI
 PRESSURE. CLARIFY AND SUBMIT A COPIES OF THE CORRECT
 SIZING TABLES FOR REVIEW. 2017 FBCR SEC. G2413.
 10) IF THIS IS A 12 INCH WATER COLUMN SYSTEM, WHY ARE
 REGULATORS BEING INSTALLED? ALSO, THESE ARE SERVICE
 REGULATORS AND ARE USUALLY INSTALLED BY THE GAS
 SUPPLIER TO REDUCE AND LIMIT THE SERVICE LINE PRESSURE
 TO DELIVERY PRESSURE. CLARIFY THE USE OF THESE
 REGULATORS.WPB AMEND TO FBC SEC. 107.2.1, 2017 FBCR
 SEC.G2403 (DEFINITIONS).
 11) THE SUBMITTED GAS SIZING TABLES FOR THE SCH. 40
 METALLIC PIPE AND CSST ARE FOR A PRESSURE DROP OF 0.5
 IN. W.C. BUT THE GAS PIPING RISER REFERENCES TABLES
 402.4 (4) AND 402.4 (17) WHICH IS FOR A PRESSURE DROP
 OF 6.0 IN. W.C. CLARIFY.
 12) THE SUBMITTED GAS SIZING TABLE FOR THE PE PIPE IS
 FOR A 2 PSI SYSTEM BUT THE SIZING TABLE REFERENCED ON
 THE PLAN IS 402.4 (21) WHICH IS FOR A SYSTEM LESS THAN
 2 PSI WITH A PRESSURE DROP OF 0.5 IN. W.C. CLARIFY.
 13) SHOW THE PIPE SIZE OF THE SCH. 40 METALLIC PIPE TO
 THE TANKLESS WATER HEATER AND ALSO TO THE RANGE ON BOTH
 GAS PIPING RISERS. IF THIS IS LESS THAN A 2 PSI SYSTEM,
 THE PIPE SIZE TO THE TANKLESS WATER HEATER SHALL BE A
 MINIMUM OF 1 INCH AND THE PIPE SIZE TO THE RANGE SHALL
 BE A MINIMUM OF 3/4 INCH.
 14) THE SIZE OF THE SCH. 40 METALLIC PIPE ON THE POINT
 OF DELIVERY FROM THE METER ( OUTLET OF THE METER) SHALL
 BE A MINIMUM OF 1 INCH PER TABLE G2413.4 (1) OF 2017
 FBCR. THE MAXIMUM BTU LOAD OF A 1 INCH PIPE AT 40 FEET
 FOR A LESS THAN 2 PSI SSYSTEM WITH A 0.5 IN. W.C.
 PRESSURE DROP IS 320,000 BTU'S AND THE SYSTEM IS
 SHOWING A TOTAL LOAD OF 331,000 BTU'S. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-20 Cont ID  
Sent By lcrespo Date 2018-03-20 Time 16:37 Rev Time 0.00
Received By lcrespo Date 2018-03-20 Time 16:37 Sent To  
Notes
2018-03-20 16:38:0603/20/2018 GAS 2ND REVIEW**DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. 2ND REQUEST, SUBMIT CALCULATIONS FOR COMBUSTION AIR
 PER THE 2014 FBC-FUEL GAS CODE SEC.304.1, 614.5
 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 2. 2ND REQUEST, SUBMIT TWO COPIES OF A HOUSE PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE WATER
 HEATER IS SHOWN AS A TANK ON PLAN BUT NOT DRAWN OUTSIDE
 AND NO DISTANCE GIVEN FROM WINDOW OR DOOR. ON THE
 ISOMETRIC, YOU HAVE IT OUTSIDE. THE PLAN CAN BE HAND
 DRAWN IN. IF THE HEATER IS GOING TO BE IN THE GARAGE
 HOW ARE YOU GOING TO VENT IT OUTSIDE, PLEASE CLARIFY?
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. 2ND REQUEST SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. PLEASE PROVIDE DOCUMENTATION FROM THE
 MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. 2017 FGC SEC.410.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By thunt Date 2018-01-18 Time 05:28 Rev Time 0.00
Received By thunt Date 2018-01-18 Time 05:28 Sent To  
Notes
2018-01-18 05:31:0801/18/2018 GAS 1ST REVIEW**DENIED**
  
 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1, 614.5 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 2.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3.SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 ***YOU ISOMETRIC DRAWING IS SHOWING ALL AS 12?W.C AND
 WOULD BE UNDER SIZED. YOU INCLUDED A 2 PSI P.E SIZING
 TABLE IN THIS PERMIT PACKET. IS IT YOUR INTENT TO MAKE
 THIS A 2LB SYSTEM? FBC 107.2.1 IF SO THE FOLLOWING WILL
 APPLY:
  
  
 1.SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. A
 LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS 2017
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. I
  
 2.SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 3.SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2017 FGC SEC.410.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-12 Cont ID  
Sent By tklarge Date 2018-05-12 Time 09:33 Rev Time 0.00
Received By tklarge Date 2018-05-09 Time 13:01 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-20 Cont ID  
Sent By lcrespo Date 2018-03-20 Time 16:38 Rev Time 0.00
Received By lcrespo Date 2018-03-16 Time 12:41 Sent To  
Notes
2018-03-19 12:41:38RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-18 Cont ID  
Sent By thunt Date 2018-01-18 Time 05:31 Rev Time 0.00
Received By thunt Date 2018-01-12 Time 09:47 Sent To I
Notes
2018-01-16 09:47:35PLUMB <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved