Plan Review Details - Permit 18010380
Plan Review Stops For Permit 18010380
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-05 Cont ID  
Sent By rmcdouga Date 2018-03-05 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2018-03-05 Time 13:58 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By rmcdouga Date 2018-01-31 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2018-01-31 Time 18:18 Sent To I
Notes
2018-01-31 18:56:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017).
  
 2) THE MASTER BATHROOM ON THE SECOND FLOOR WAS
 INCREASED IN SIZE AND NOW CONTAINS A WINDOW THAT IS
 ADJACENT TO THE SHOWER. FBC-R 308.4.5 REQUIRES THE
 WINDOW TO HAVE SAFETY GLAZING OR TO BE LARGE MISSILE
 IMPACT RATED.
  
 3) ONE OF THE WINDOWS IN THE REMODELED BEDROOM 2 ON THE
 SECOND FLOOR IS NOW LOCATED IN THE ENLARGED MASTER
 BATHROOM. THIS BEDROOM IS REQUIRED TO MAINTAIN THE SAME
 LEVEL OF EGRESS THAT IT HAD BEFORE THE REMODELING. THE
 CLEAR OPENING AREA IN THE REMAINING WINDOW MUST BE
 EQUAL TO WHAT EXISTING BEFORE THE CHANGES. FBC EXISTING
 BUILDING 702.5
  
 4) THE PLANS INDICATE THAT A NEW GAS RANGE IS BEING
 INSTALLED. SHOW COMPLIANCE WITH FBC-R315 FOR REQUIRED
 CARBON MONOXIDE ALARMS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-27 Cont ID  
Sent By jpearson Date 2018-02-27 Time 15:19 Rev Time 0.00
Received By jpearson Date 2018-02-27 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By jpearson Date 2018-01-24 Time 15:58 Rev Time 0.00
Received By jpearson Date 2018-01-24 Time 15:58 Sent To  
Notes
2018-01-24 15:57:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODE ABOVE)
 2. ELECTRICAL NOTE S DOES NOT COVER ALL AREAS REQUIRED
 TO HAVE AFCI PROTECTION. PER CODE: "BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED." PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. RISER DIAGRAM DOES NOT MATCH WHAT PLAN SHOWS. RISER
 HAS A METER TO A PANEL, WHILE THE PLAN SHOWS A METER TO
 AN OUTSIDE DISCONNECT FEEDING AN INTERIOR PANEL.
 PROVIDE CORRECTION. FBC 107.2.1; NEC 215.5
 4. PROVIDE GFCI PROTECTED RECEPTACLE ON 2ND FLOOR
 BALCONY. NEC 210.52(E); FBC RE E3901.7
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. MASTER BATH DOES
 NOT SHOW THIS. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 7. PROVIDE GFCI PROTECTION FOR OUTLETS ON THE KITCHEN
 ISLAND. NEC 210.8, 210.52(C)(2); FBC RE E3901.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-01-26 Cont ID  
Sent By thunt Date 2018-01-26 Time 15:06 Rev Time 0.00
Received By thunt Date 2018-01-26 Time 15:06 Sent To  
Notes
2018-01-26 15:07:25A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. WPB
 AMEND. TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-05 Cont ID  
Sent By rmcdouga Date 2018-03-05 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2018-02-12 Time 15:14 Sent To  
Notes
2018-02-13 15:14:41R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-31 Cont ID  
Sent By rmcdouga Date 2018-01-31 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2018-01-11 Time 14:24 Sent To  
Notes
2018-01-12 14:25:06R09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-01-26 Cont ID  
Sent By cmontell Date 2018-01-26 Time 14:41 Rev Time 0.00
Received By cmontell Date 2018-01-26 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-01-26 Cont ID  
Sent By thunt Date 2018-01-26 Time 15:07 Rev Time 0.00
Received By thunt Date 2018-01-26 Time 15:07 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved