Plan Review Details - Permit 18010354
Plan Review Stops For Permit 18010354
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-05-30 Cont ID  
Sent By shill Date 2018-05-30 Time 10:01 Rev Time 0.00
Received By shill Date 2018-05-30 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-21 Cont ID  
Sent By rmcdouga Date 2018-05-21 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2018-05-21 Time 07:15 Sent To E
Notes
2018-05-21 07:18:28ONE SET OF THE APPROVED GENERATOR PAD PLANS IS MISSING
 FROM THE SUBMITTAL DOCUMENTS. TWO SETS OF PLANS ARE
 REQUIRED. FBC 107.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2018-03-08 Time 10:14 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By rmcdouga Date 2018-01-24 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2018-01-24 Time 07:36 Sent To E
Notes
2018-01-24 08:29:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBER LISTED ON THE PAD ENGINEERING FOR
 THE 20 KW BRIGGS & STRATTON GENERATOR DOES NOT MATCH
 THE ONES LISTED ON THE GENERATOR SPECIFICATIONS THAT
 WERE SUBMITTED. THE BASE OF THE GENERATOR IS LARGER
 THAN THE PAD. FBC-R301.1
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By jleahy Date 2018-05-22 Time 08:43 Rev Time 0.00
Received By jleahy Date 2018-05-22 Time 08:43 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-01-24 Cont ID  
Sent By jleahy Date 2018-01-24 Time 12:53 Rev Time 0.00
Received By jleahy Date 2018-01-24 Time 12:53 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2018-05-30 Cont ID  
Sent By gjohnson Date 2018-05-30 Time 09:57 Rev Time 0.00
Received By gjohnson Date 2018-05-30 Time 09:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2018-05-19 Cont ID  
Sent By tklarge Date 2018-05-19 Time 09:38 Rev Time 0.00
Received By tklarge Date 2018-05-19 Time 09:08 Sent To  
Notes
2018-05-19 09:25:201) THERE IS STILL ONE COPY OF THE PROPANE TANK
 INSTALLATION DETAIL SHEET THAT BEARS A COPY OF THE
 ENGINEER'S SEAL AND SIGNATURE. YOU HAVE SUBMITTED
 COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED
 ENGINEER ( KEVIN L.ATCHLEY) FOR THE PROPANE TANK
 HOLDOWN DETAILS.FOR THE 5TH TIME, DOCUMENTS BEARING AN
 ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND
 CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE
 61G15-23.001. IF YOU ARE GOING TO SUBMIT THESE DETAILS,
 ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD.
 2) THERE IS ONLY ONE COPY OF THE AMERICAST GENERATOR
 CONCRETE PAD DRAWING THAT HAS AN ORIGINAL ENGINEER'S
 SEAL AND SIGNATURE. SUBMIT ANOTHER COPY THAT BEARS AN
 ORIGINAL SEAL AND SIGNATURE OF THE DESIGN PROFESSIONAL
 OF RECORD PER FL. ADMIN. CODE 61G15-23.001.
 3) THERE IS ONLY ONE COPY OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GENERATOR. SUBMIT TWO COPIES OF
 THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR.
 WPB AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2018-05-04 Cont ID  
Sent By tklarge Date 2018-05-04 Time 14:35 Rev Time 0.00
Received By tklarge Date 2018-05-04 Time 09:52 Sent To I
Notes
2018-05-04 10:25:241) YOU HAVE SUBMITTED COPIES OF A SIGNED AND SEALED
 DOCUMENT BY A LICENSED ENGINEER ( KEVIN L.ATCHLEY) FOR
 THE PROPANE TANK HOLDOWN DETAILS. DOCUMENTS BEARING AN
 ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND
 CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE
 61G15-23.001. IF YOU ARE GOING TO SUBMIT THESE DETAILS,
 ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD.
 2) THERE IS ONLY ONE COPY OF THE AMERICAST GENERATOR
 CONCRETE PAD DRAWING, THE ELECTRICAL DRAWING AND THE
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. SUBMIT
 TWO COPIES OF THE SIGNED AND SEALED GENERATOR PAD
 DRAWING AND OF THE ELECTRICAL PLANS AND THE
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. WPB
 AMEND. TO FBC SEC. 107.1.
 3) INDICATE THE TYPE OF PIPE AND THE PIPE SIZE
 DOWNSTREAM OF THE SECOND STAGE REGULATOR. INDICATE THE
 PSI OF THE SYSTEM DOWNSTREAM OF THE SECOND REGULATOR.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-03-21 Cont ID  
Sent By tklarge Date 2018-03-21 Time 14:14 Rev Time 0.00
Received By tklarge Date 2018-03-21 Time 13:10 Sent To I
Notes
2018-03-21 14:14:551) YOU HAVE SUBMITTED COPIES OF A SIGNED AND SEALED
 DOCUMENT BY A LICENSED ENGINEER (CARMO ENGINEERING
 ASSOCIATES) FOR THE PROPANE TANK HOLDOWN DETAILS.
 DOCUMENTS BEARING AN ENGINEER'S SEAL AND SIGNATURE MUST
 BE ORIGINAL AND CANNOT BE COPIES PER THE FL. ADMIN.
 CODE RULE 61G15-23.001.THE PRINTING ON THESE DOCUMENTS
 IS ILLEGIBLE. IF YOU ARE GOING TO SUBMIT THESE DETAILS,
 ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD AND ARE LEGIBLE.
  
 2) SOME OF THE MANIFACTURER'S SPECIFICATION SHEETS FOR
 THE PRESSURE REGULATORS ARE ILLEGIBLE. SUBMIT TWO
 COPIES OF CLEAR AND LEGIBLE REGULATOR SPECIFICATIONS
 FOR REVIEW WPB AMEND. TO FBC SEC. 107.2.1. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1.
  
 3) YOU HAVE SUBMITTED A SIZING TABLE FOR THE SCHEDULE
 40 METALLIC PIPE FROM THE 2014 FBC-FUEL GAS CODE. THE
 CODE IN EFFECT FOR THIS PERMIT IS THE 2017 FBC-FUEL GAS
 CODE. SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE
 2017 FBC-FUEL GAS CODE.
  
 4) THE SIZING TABLE FROM NFPA 58 FOR THE 10 PSI IS
 ALMOST ILLEGIBLE. SUBIT TWO LEGIBLE COPIES OF THE
 SIZING TABLE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 5) THE GAS DRAWING SHOWING THE 500 GAL. UNDERGROUND
 TANK HAS A NOTE THAT REFERS TO SEC.411.1 OF THE
 FBC-FUEL GAS CODE. THIS CODE SECTION REFERS TO
 APPLIANCE CONNECTIONS AND MANUFACTURED HOMES. CLARIFY.
  
 NOTE: SINCE THESE PLANS HAVE BEEN REJECTED FOR SOME OF
 THE SAME COMMENTS 3 TIMES, THE NEXT RESUBMITTAL IS
 SUBJECT TO A RESUBMITTAL FEE OF 4 TIMES THE PLAN REVIEW
 FEE PER FL. STATUTE 553.80 (2) (B).
  
 I SUGGEST YOU CONTACT THIS PLAN REVIEWER TO ARRANGE A
 MEETING TO GO OVER THE REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-06 Cont ID  
Sent By tklarge Date 2018-03-06 Time 06:24 Rev Time 0.00
Received By tklarge Date 2018-03-06 Time 05:10 Sent To  
Notes
2018-03-06 05:48:341) THE ENGINEER WHOSE COPY OF HIS SIGNATURE AND SEAL
 FOR THE DOCUMENTS FROM TIE DOWN ENGINEERING HAS A
 LICENSE THAT HAS BEEN NULL AND VOID SINCE 2/28/15. ALSO
 SIGNATURE IS REQUIRED TO BE WET AND SEAL CANNOT BE
 COPIED. COPIES ARE NOT PERMITTED PER FL.ADMIN CODE
 61G15-23.001
  
 2) IN ADDITION TO COMMENT #1, YOU HAVE ALSO SUBMITTED
 COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED
 ENGINEER (CARMO ENGINEERING ASSOCIATES) FOR THE PROPANE
 TANK HOLDOWN DETAILS. AGAIN, DOCUMENTS BEARING AN
 ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND
 CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE
 61G15-23.001.THE PRINTING ON THESE DOCUMENTS IS
 ILLEGIBLE. IF YOU ARE GOING TO SUBMIT THESE DETAILS,
 ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD AND ARE LEGIBLE.
  
 3) THERE ARE TWO DIFFERENT SHEETS THAT HAVE BEEN
 SUBMITTED FOR THE CATHODIC PROTECTION. ONE IS
 ILLEGIBLE. REMOVE THE SPECIFICATION SHEET FOR THE
 CATHODIC PROTECTION THAT WILL NOT BE USED. FBC107.2.1.
 A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA
 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED
 PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS ON THE TYPE
 OF CATHODIC PROTECTION, SIZE ( LBS) & NUMBER OF
 MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 4) SOME OF THE MANIFACTURER'S SPECIFICATION SHEETS FOR
 THE PRESSURE REGULATORS ARE ILLEGIBLE. SUBMIT TWO
 COPIES OF CLEAR AND LEGIBLE REGULATOR SPECIFICATIONS
 FOR REVIEW WPB AMEND. TO FBC SEC. 107.2.1. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1.
  
 5) YOU HAVE SUBMITTED A SIZING TABLE FOR THE SCHEDULE
 40 METALLIC PIPE FROM THE 2014 FBC-FUEL GAS CODE. THE
 CODE IN EFFECT FOR THIS PERMIT IS THE 2017 FBC-FUEL GAS
 CODE. SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE
 2017 FBC-FUEL GAS CODE.
  
 6) THE SIZING TABLE FROM NFPA 58 FOR THE 10 PSI IS
 ALMOST ILLEGIBLE. SUBIT TWO LEGIBLE COPIES OF THE
 SIZING TABLE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) THERE ARE NOW 3 DIFFERENT TANK TIE-DOWN DETAILS
 SUBMITTED WITH THIS REVIEW. I HAVE NO IDEA WHICH DETAIL
 IS GOING TO BE USED. REMOVE ALL DOCUMENTS FROM THIS
 PACKAGE THAT ARE NOT APPLICABLE AND SUBMIT TWO COPIES
 OF TANK TIE-DOWN DETAILS. IF THE TIE-DOWN DETAILS TO BE
 SUBMITTED BEAR AN ENGINEER'S SEAL AND SIGNATURE, THEY
 MUST BE ORIGINAL AND NOT COPIES. FL. ADMIN. CODE RULE
 61G15-23.001.
  
 8) THE GAS DRAWING SHOWING THE 500 GAL. UNDERGROUND
 TANK HAS A NOTE THAT REFERS TO SEC.411.1 OF THE
 FBC-FUEL GAS CODE. THIS CODE SECTION REFERS TO
 APPLIANCE CONNECTIONS AND MANUFACTURED HOMES. CLARIFY.
  
 I SUGGEST YOU CONTACT THIS PLAN REVIEWER TO ARRANGE A
 MEETING TO GO OVER THE REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-19 Cont ID  
Sent By thunt Date 2018-01-19 Time 15:17 Rev Time 0.00
Received By thunt Date 2018-01-19 Time 15:17 Sent To  
Notes
2018-01-19 15:34:2801/19/2018 GAS 1ST REVIEW**DENIED**
  
 1) ENGINEER FOR TIE DOWN ENGINEERING LICENSE
 REVOKE/EXPIRED. ALSO SIGNATURE IS REQUIRED TO BE WET.
 COPIES ARE NOT PERMITTED PER FL.ADMIN CODE 61G15-23.001
  
 2) CATHADIC PROTECTIONSPEC SHEET NOT LEGIBLE.
 FBC107.2.1.A CATHODIC PROTECTION SYSTEM SHALL BE
 REQUIRED PER NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND
 SHALL BE MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT
 DETAILS ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS)
 & NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE
 CABLE.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1
  
 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD
  
 5) SUBMIT SIZING CHART FOR THE .5 SCH 40 METAL
 PIPING.SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-05-22 Cont ID  
Sent By jleahy Date 2018-05-22 Time 08:44 Rev Time 0.00
Received By jleahy Date 2018-05-17 Time 13:52 Sent To  
Notes
2018-05-18 13:52:26RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-04 Cont ID  
Sent By tklarge Date 2018-05-04 Time 14:36 Rev Time 0.00
Received By tklarge Date 2018-04-30 Time 14:28 Sent To  
Notes
2018-05-01 14:28:49RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-21 Cont ID  
Sent By tklarge Date 2018-03-21 Time 14:17 Rev Time 0.00
Received By tklarge Date 2018-03-19 Time 09:47 Sent To  
Notes
2018-03-20 09:47:46RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2018-03-01 Time 10:39 Sent To  
Notes
2018-03-02 10:40:10RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-24 Cont ID  
Sent By jleahy Date 2018-01-24 Time 12:53 Rev Time 0.00
Received By jleahy Date 2018-01-11 Time 14:28 Sent To  
Notes
2018-01-12 14:29:01ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-17 Cont ID  
Sent By AW Date 2018-01-17 Time 09:22 Rev Time 0.00
Received By awooten Date 2018-01-16 Time 15:38 Sent To B
Notes
***NONE***