| Plan Review Stops For Permit 18010354 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-05-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-30 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-30 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-21 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-21 |
Time |
07:15 |
Sent To |
E |
|
| Notes |
| 2018-05-21 07:18:28 | ONE SET OF THE APPROVED GENERATOR PAD PLANS IS MISSING | | | FROM THE SUBMITTAL DOCUMENTS. TWO SETS OF PLANS ARE | | | REQUIRED. FBC 107.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-08 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-08 |
Time |
10:14 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-24 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-24 |
Time |
07:36 |
Sent To |
E |
|
| Notes |
| 2018-01-24 08:29:46 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MODEL NUMBER LISTED ON THE PAD ENGINEERING FOR | | | THE 20 KW BRIGGS & STRATTON GENERATOR DOES NOT MATCH | | | THE ONES LISTED ON THE GENERATOR SPECIFICATIONS THAT | | | WERE SUBMITTED. THE BASE OF THE GENERATOR IS LARGER | | | THAN THE PAD. FBC-R301.1 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-22 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-22 |
Time |
08:43 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-01-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-01-24 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-24 |
Time |
12:53 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
P |
Date |
2018-05-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-30 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-30 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2018-05-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-19 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-19 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2018-05-19 09:25:20 | 1) THERE IS STILL ONE COPY OF THE PROPANE TANK | | | INSTALLATION DETAIL SHEET THAT BEARS A COPY OF THE | | | ENGINEER'S SEAL AND SIGNATURE. YOU HAVE SUBMITTED | | | COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED | | | ENGINEER ( KEVIN L.ATCHLEY) FOR THE PROPANE TANK | | | HOLDOWN DETAILS.FOR THE 5TH TIME, DOCUMENTS BEARING AN | | | ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND | | | CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE | | | 61G15-23.001. IF YOU ARE GOING TO SUBMIT THESE DETAILS, | | | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | 2) THERE IS ONLY ONE COPY OF THE AMERICAST GENERATOR | | | CONCRETE PAD DRAWING THAT HAS AN ORIGINAL ENGINEER'S | | | SEAL AND SIGNATURE. SUBMIT ANOTHER COPY THAT BEARS AN | | | ORIGINAL SEAL AND SIGNATURE OF THE DESIGN PROFESSIONAL | | | OF RECORD PER FL. ADMIN. CODE 61G15-23.001. | | | 3) THERE IS ONLY ONE COPY OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE GENERATOR. SUBMIT TWO COPIES OF | | | THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. | | | WPB AMEND. TO FBC SEC. 107.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-04 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-04 |
Time |
09:52 |
Sent To |
I |
|
| Notes |
| 2018-05-04 10:25:24 | 1) YOU HAVE SUBMITTED COPIES OF A SIGNED AND SEALED | | | DOCUMENT BY A LICENSED ENGINEER ( KEVIN L.ATCHLEY) FOR | | | THE PROPANE TANK HOLDOWN DETAILS. DOCUMENTS BEARING AN | | | ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND | | | CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE | | | 61G15-23.001. IF YOU ARE GOING TO SUBMIT THESE DETAILS, | | | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | 2) THERE IS ONLY ONE COPY OF THE AMERICAST GENERATOR | | | CONCRETE PAD DRAWING, THE ELECTRICAL DRAWING AND THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. SUBMIT | | | TWO COPIES OF THE SIGNED AND SEALED GENERATOR PAD | | | DRAWING AND OF THE ELECTRICAL PLANS AND THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. WPB | | | AMEND. TO FBC SEC. 107.1. | | | 3) INDICATE THE TYPE OF PIPE AND THE PIPE SIZE | | | DOWNSTREAM OF THE SECOND STAGE REGULATOR. INDICATE THE | | | PSI OF THE SYSTEM DOWNSTREAM OF THE SECOND REGULATOR. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-03-21 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-03-21 |
Time |
13:10 |
Sent To |
I |
|
| Notes |
| 2018-03-21 14:14:55 | 1) YOU HAVE SUBMITTED COPIES OF A SIGNED AND SEALED | | | DOCUMENT BY A LICENSED ENGINEER (CARMO ENGINEERING | | | ASSOCIATES) FOR THE PROPANE TANK HOLDOWN DETAILS. | | | DOCUMENTS BEARING AN ENGINEER'S SEAL AND SIGNATURE MUST | | | BE ORIGINAL AND CANNOT BE COPIES PER THE FL. ADMIN. | | | CODE RULE 61G15-23.001.THE PRINTING ON THESE DOCUMENTS | | | IS ILLEGIBLE. IF YOU ARE GOING TO SUBMIT THESE DETAILS, | | | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD AND ARE LEGIBLE. | | | | | | 2) SOME OF THE MANIFACTURER'S SPECIFICATION SHEETS FOR | | | THE PRESSURE REGULATORS ARE ILLEGIBLE. SUBMIT TWO | | | COPIES OF CLEAR AND LEGIBLE REGULATOR SPECIFICATIONS | | | FOR REVIEW WPB AMEND. TO FBC SEC. 107.2.1. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1. | | | | | | 3) YOU HAVE SUBMITTED A SIZING TABLE FOR THE SCHEDULE | | | 40 METALLIC PIPE FROM THE 2014 FBC-FUEL GAS CODE. THE | | | CODE IN EFFECT FOR THIS PERMIT IS THE 2017 FBC-FUEL GAS | | | CODE. SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE | | | 2017 FBC-FUEL GAS CODE. | | | | | | 4) THE SIZING TABLE FROM NFPA 58 FOR THE 10 PSI IS | | | ALMOST ILLEGIBLE. SUBIT TWO LEGIBLE COPIES OF THE | | | SIZING TABLE. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | 5) THE GAS DRAWING SHOWING THE 500 GAL. UNDERGROUND | | | TANK HAS A NOTE THAT REFERS TO SEC.411.1 OF THE | | | FBC-FUEL GAS CODE. THIS CODE SECTION REFERS TO | | | APPLIANCE CONNECTIONS AND MANUFACTURED HOMES. CLARIFY. | | | | | | NOTE: SINCE THESE PLANS HAVE BEEN REJECTED FOR SOME OF | | | THE SAME COMMENTS 3 TIMES, THE NEXT RESUBMITTAL IS | | | SUBJECT TO A RESUBMITTAL FEE OF 4 TIMES THE PLAN REVIEW | | | FEE PER FL. STATUTE 553.80 (2) (B). | | | | | | I SUGGEST YOU CONTACT THIS PLAN REVIEWER TO ARRANGE A | | | MEETING TO GO OVER THE REVIEW COMMENTS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-03-06 |
Time |
06:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-03-06 |
Time |
05:10 |
Sent To |
|
|
| Notes |
| 2018-03-06 05:48:34 | 1) THE ENGINEER WHOSE COPY OF HIS SIGNATURE AND SEAL | | | FOR THE DOCUMENTS FROM TIE DOWN ENGINEERING HAS A | | | LICENSE THAT HAS BEEN NULL AND VOID SINCE 2/28/15. ALSO | | | SIGNATURE IS REQUIRED TO BE WET AND SEAL CANNOT BE | | | COPIED. COPIES ARE NOT PERMITTED PER FL.ADMIN CODE | | | 61G15-23.001 | | | | | | 2) IN ADDITION TO COMMENT #1, YOU HAVE ALSO SUBMITTED | | | COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED | | | ENGINEER (CARMO ENGINEERING ASSOCIATES) FOR THE PROPANE | | | TANK HOLDOWN DETAILS. AGAIN, DOCUMENTS BEARING AN | | | ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND | | | CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE | | | 61G15-23.001.THE PRINTING ON THESE DOCUMENTS IS | | | ILLEGIBLE. IF YOU ARE GOING TO SUBMIT THESE DETAILS, | | | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD AND ARE LEGIBLE. | | | | | | 3) THERE ARE TWO DIFFERENT SHEETS THAT HAVE BEEN | | | SUBMITTED FOR THE CATHODIC PROTECTION. ONE IS | | | ILLEGIBLE. REMOVE THE SPECIFICATION SHEET FOR THE | | | CATHODIC PROTECTION THAT WILL NOT BE USED. FBC107.2.1. | | | A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA | | | 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED | | | PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS ON THE TYPE | | | OF CATHODIC PROTECTION, SIZE ( LBS) & NUMBER OF | | | MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. | | | | | | 4) SOME OF THE MANIFACTURER'S SPECIFICATION SHEETS FOR | | | THE PRESSURE REGULATORS ARE ILLEGIBLE. SUBMIT TWO | | | COPIES OF CLEAR AND LEGIBLE REGULATOR SPECIFICATIONS | | | FOR REVIEW WPB AMEND. TO FBC SEC. 107.2.1. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1. | | | | | | 5) YOU HAVE SUBMITTED A SIZING TABLE FOR THE SCHEDULE | | | 40 METALLIC PIPE FROM THE 2014 FBC-FUEL GAS CODE. THE | | | CODE IN EFFECT FOR THIS PERMIT IS THE 2017 FBC-FUEL GAS | | | CODE. SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE | | | 2017 FBC-FUEL GAS CODE. | | | | | | 6) THE SIZING TABLE FROM NFPA 58 FOR THE 10 PSI IS | | | ALMOST ILLEGIBLE. SUBIT TWO LEGIBLE COPIES OF THE | | | SIZING TABLE. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | 7) THERE ARE NOW 3 DIFFERENT TANK TIE-DOWN DETAILS | | | SUBMITTED WITH THIS REVIEW. I HAVE NO IDEA WHICH DETAIL | | | IS GOING TO BE USED. REMOVE ALL DOCUMENTS FROM THIS | | | PACKAGE THAT ARE NOT APPLICABLE AND SUBMIT TWO COPIES | | | OF TANK TIE-DOWN DETAILS. IF THE TIE-DOWN DETAILS TO BE | | | SUBMITTED BEAR AN ENGINEER'S SEAL AND SIGNATURE, THEY | | | MUST BE ORIGINAL AND NOT COPIES. FL. ADMIN. CODE RULE | | | 61G15-23.001. | | | | | | 8) THE GAS DRAWING SHOWING THE 500 GAL. UNDERGROUND | | | TANK HAS A NOTE THAT REFERS TO SEC.411.1 OF THE | | | FBC-FUEL GAS CODE. THIS CODE SECTION REFERS TO | | | APPLIANCE CONNECTIONS AND MANUFACTURED HOMES. CLARIFY. | | | | | | I SUGGEST YOU CONTACT THIS PLAN REVIEWER TO ARRANGE A | | | MEETING TO GO OVER THE REVIEW COMMENTS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-01-19 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-19 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-19 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2018-01-19 15:34:28 | 01/19/2018 GAS 1ST REVIEW**DENIED** | | | | | | 1) ENGINEER FOR TIE DOWN ENGINEERING LICENSE | | | REVOKE/EXPIRED. ALSO SIGNATURE IS REQUIRED TO BE WET. | | | COPIES ARE NOT PERMITTED PER FL.ADMIN CODE 61G15-23.001 | | | | | | 2) CATHADIC PROTECTIONSPEC SHEET NOT LEGIBLE. | | | FBC107.2.1.A CATHODIC PROTECTION SYSTEM SHALL BE | | | REQUIRED PER NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND | | | SHALL BE MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT | | | DETAILS ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) | | | & NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE | | | CABLE. | | | | | | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1 | | | | | | 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4 | | | (28) FOR THE PROPER PIPE SIZE AND BTU LOAD | | | | | | 5) SUBMIT SIZING CHART FOR THE .5 SCH 40 METAL | | | PIPING.SUBMIT TWO COPIES OF THE APPLICABLE SIZING | | | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON | | | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) | | | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN | | | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 | | | FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES | | | 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. | | | G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-22 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-17 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2018-05-18 13:52:26 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-04 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-04-30 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2018-05-01 14:28:49 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-03-21 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-03-19 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2018-03-20 09:47:46 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-08 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-01 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2018-03-02 10:40:10 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-01-24 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-11 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2018-01-12 14:29:01 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-01-17 |
|
|
Cont ID |
|
| Sent By |
AW |
Date |
2018-01-17 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-01-16 |
Time |
15:38 |
Sent To |
B |
|
| Notes |
|
|