Plan Review Details - Permit 18010230
Plan Review Stops For Permit 18010230
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-07 Cont ID  
Sent By aclange Date 2018-03-07 Time 09:15 Rev Time 0.00
Received By aclange Date 2018-03-07 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-11 Cont ID  
Sent By aclange Date 2018-01-11 Time 09:17 Rev Time 0.00
Received By aclange Date 2018-01-11 Time 07:40 Sent To  
Notes
2018-01-11 09:17:39****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. SEPARATE PERMITS REQUIRED FOR PARKING LOT AND
 STRIPING. PROVIDE PLANS FOR THIS AND INCLUDE ADA
 COMPLIANCE AS WELL AS RAMP DETAILS IF APPLICABLE.
 LANDSCAPING AND IRRIGATION AND EXTERIOR SIGNAGE WILL BE
 UNDER A SEPARATE PERMIT.
  
 2. PERMIT VALUE IS SHOWN AS APPROXIMATE. INCLUDE THE
 VALUE OF THE PERMIT FOR THE WORK THAT WILL BE COMPLETED
 UNDER THIS PERMIT. THE OTHER PERMITS CAN CARRY THEIR
 OWN VALUE FOR THE WORK TO BE COMPLETED.
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
  
 3. PERMIT APPLICATIONS RECEIVED AFTER 12/31/2017 WILL
 BE UNDER THE 2017 FLORIDA BUILDING CODE 6TH EDITION.
 UPDATE THE CODE CRITERIA ON THE COVER PAGE AS WELL AS
 PAGE A 0.1.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 14:38 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By jpearson Date 2018-01-24 Time 13:34 Rev Time 0.00
Received By jpearson Date 2018-01-24 Time 13:34 Sent To  
Notes
2018-01-24 13:27:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODE ABOVE)
 2. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC
 422.52
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 215.5, 408.4
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). NEC 215.5
 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 6. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE BATHROOMS.
 FBC EC C405.2
 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By pleduc Date 2018-03-08 Time   Rev Time 0.00
Received By pleduc Date 2018-03-07 Time 16:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-12 Cont ID  
Sent By pleduc Date 2018-01-12 Time   Rev Time 0.00
Received By pleduc Date 2018-01-11 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-17 Cont ID  
Sent By lcrespo Date 2018-03-17 Time 12:31 Rev Time 0.00
Received By lcrespo Date 2018-03-01 Time 07:43 Sent To  
Notes
2018-03-06 07:43:22B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-26 Cont ID  
Sent By gjohnson Date 2018-01-26 Time 17:27 Rev Time 0.00
Received By gjohnson Date 2018-01-09 Time 13:15 Sent To  
Notes
2018-01-10 13:15:47B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-01-11 Cont ID  
Sent By aclange Date 2018-01-11 Time 09:18 Rev Time 0.00
Received By aclange Date 2018-01-11 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-17 Cont ID  
Sent By lcrespo Date 2018-03-17 Time 12:30 Rev Time 0.00
Received By lcrespo Date 2018-03-17 Time 12:30 Sent To  
Notes
2018-03-17 12:31:0903/17/18 APPROVED BY PLUMBING AND SENT TO PROCESSING,
 LAC

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-01-26 Cont ID  
Sent By gjohnson Date 2018-01-26 Time 15:19 Rev Time 0.00
Received By gjohnson Date 2018-01-26 Time 10:20 Sent To  
Notes
***NONE***