Plan Review Details - Permit 18010205
Plan Review Stops For Permit 18010205
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By pleduc Date 2018-03-06 Time   Rev Time 0.00
Received By pleduc Date 2018-03-05 Time 12:38 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-11 Cont ID  
Sent By pleduc Date 2018-01-11 Time   Rev Time 0.00
Received By pleduc Date 2018-01-10 Time 11:43 Sent To M
Notes
2018-01-10 17:01:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO BUILDING AND KITCHEN LAY-OUT PLAN
 INDICATING WHERE THIS UNIT IS PROPOSED.
  
 PLEASE PROVIDE EXACT LOCATION INCLUDING DIMENSIONS.
  
  
 2) THERE IS NO INDICATION WHERE THE REMOTE
 ACTIVATION/PULL STATION IS LOCATED.
  
 10.5 MANUAL ACTIVATION.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN.
 AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M
 (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S)
 WITHIN A PATH OF EGRESS OR AT AN ALTERNATIVE LOCATION
 ACCEPTABLE TO THE AHJ.
  
 PLEASE PROVIDE EXACT LOCATION INCLUDING DIMENSIONS.
  
  
  
  
 3) THERE IS NO INDICATION OF FUEL OF ELECTRICAL
 SHUTOFF.
  
 10.4 FUEL AND ELECTRIC POWER SHUTOFF.
 10.4.1 UPON ACTIVATION OF ANY FIRE-EXTINGUISHING SYSTEM
 FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND
 ELECTRICAL POWER THAT PRODUCE HEAT TO ALL EQUIPMENT
 REQUIRING PROTECTION BY THAT SYSTEM SHALL AUTOMATICALLY
 SHUT OFF.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 4) THERE IS NO INDICATION OF FIRE ALARM CONNECTION FOR
 ACTIVATION OR TIE-INTO THE FIRE ALARM SYSTEM BY A
 CERTIFIED CONTRACTOR.
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM, AN AUDIBLE ALARM OR VISUAL
 INDICATOR SHALL BE PROVIDED TO SHOW THAT THE SYSTEM HAS
 ACTIVATED.
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCYWHERE THE EXTINGUISHING SYSTEM IS LOCATED,
 THE ACTIVATION OF THE AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM SHALL ACTIVATE THE FIRE ALARM SIGNALING SYSTEM.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-08 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-01 Time 12:32 Sent To  
Notes
2018-03-02 12:32:56RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-01-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-08 Time 13:34 Sent To  
Notes
2018-01-09 13:35:05ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By ccole Date 2018-03-08 Time 17:11 Rev Time 0.00
Received By ccole Date 2018-03-08 Time 17:11 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-23 Cont ID  
Sent By ccole Date 2018-01-23 Time 12:34 Rev Time 0.00
Received By ccole Date 2018-01-23 Time 12:18 Sent To I
Notes
2018-01-23 13:08:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010205
 1/23/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMIT VALUE IS BASED ON LABOR, MATERIALS,
 EQUIPMENT, DESIGN FEES, PROFIT AMD OVERHEAD- SECTION
 109.3 WPB AMENDMENTS TO THE FBC. THE APPLICATION AND
 CONTRACT INDICATES THE $1,011.15 VALUE LISTED ON THE
 PERMIT APPLICATION IS FOR LABOR ONLY. PLEASE ADJUST THE
 VALUE IN ACCORDINGLY.
  
 2) PROVIDE A FLOOR PLAN DRAWING THAT SHOW THE LOCATION
 OF THE VENTLESS HOOD.
  
 3) CLARIFY HOW MAKEUP AIR IS BEING PROVIDED FOR THE
 3000 CFM EXHAUST HOOD. SHOW THE SOURCE OF THE MAKEUP
 AIR ON THE PLAN AND PROVIDE AIR BALANCE CALCULATIONS.
  
 4) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE AND
 SHOW COMPLIANCE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 5) PLEASE NOTE THAT THE RESTAURANT PLANS UNDER PRIMARY
 PERMIT #17010872 INDICATES A VENTED HOOD WITH AN
 EXHAUST RATE OF 1500 CFMS. PLEASE ALERT THE GENERAL
 CONTRACTOR THAT REVISION TO THE MAIN PLAN WILL BE
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  