| 2018-01-09 15:43:45 | 01/09/2018 GAS 1ST REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | ALSO WE ARE CURRENTLY USING THE 2017 6TH ED OF THE |
| | FLORIDA FUEL AND GAS. |
| | |
| | 1) YOU DID NOT INCLUDE ANY MANUFACTURE SPECS OR |
| | INSTALLATION MANUAL FOR THE GENERATOR. CURRENTLY WE DO |
| | NOT SHOW ANY PERMIT OR APPLICATION FOR A PERMIT TO |
| | INSTALL A GENERATOR. SUBMIT MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2014 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1 OR YOU WILL NEED TO WAIT FOR THE MAIN |
| | GENERATOR PERMIT BEFORE YOUR SUB CAN BE ISSUED. |
| | |
| | 2) CITY RECORDS SHOW YOUR ISOMETRIC AND BTU LOAD OF |
| | EXISTING NOT TO BE ACCURATE. BASED OFF CITY RECORDS THE |
| | ADDING OF ANY MORE BTU ON THE EXISTING 1" METALLIC PIPE |
| | OUTLET OF THE EXISTING 2LB METER WILL BE UNDERSIZED |
| | .THE EXISTING BTU LOAD OF THE EXISTING GAS SYSTEM MUST |
| | BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. . FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| | 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |