| Plan Review Stops For Permit 18010190 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-04-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-04-26 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-26 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2018-04-26 11:07:51 | FROM: DARIO HERRERO | | | TO: [email protected], MARTY APPLEBAUM | | | | | | DATE: 04/25/2018 07:30 PM | | | SUBJECT: PERMIT #18010190 | | | | | | MR GOMEZ | | | AS PER OUR LAST CONVERSATION WE HAD SENT YOU THE | | | ORIGINAL DRAWINGS OF THE UNIT SHOWING THE ELEVATION OF | | | THE SAME WITH THE HEIGHT RESTRICTION OF 8' INTERIOR | | | FROM CONCRETE SLAB TO CONCRETE SLAB.? THE ORIGINAL | | | DESIGN HAS R-11.1 INSULATION ON THE ROOF AND? R-11 ON | | | THE WALLS.? PER OUR CONVERSATION YOU EXPRESSED THAT THE | | | EVALUATION SHOULD BE DONE USING THE PERFORMANCE METHOD | | | FORM R405-2017. ATTACHED IS A COPY OF THE SAME BUT AS I | | | HAD EXPRESSED TO YOU THE PROGRAM WILL NOT ALLOW AN | | | INPUT OF LESS THAN R-19 FOR THE ROOF THEREFORE THE | | | ATTACHED FOR IS WRONG IN THAT THE ROOFING HAS R-19 | | | INSULATION. | | | AT THIS POINT WE ARE AT A STANDSTILL.? EVEN THOUGH WE | | | HAVE A PERMIT CONTINGENT ON THIS ITEM BEING RESOLVED, | | | WE CANNOT PROCEED DUE TO THE FACT THAT THIS ITEM IS NOT | | | RESOLVED.? | | | SINCE THIS IS AN EXISTING UNIT IN A TOWN HOUSE THAT | | | SHARES THE ROOF WITH 3 OTHER UNITS AND BEING THIS THE | | | CASE THE UNIT OWNER DOES NOT OWN THE ROOF OR | | | INSULATION, THE SAME BELONGS TO THE ASSOCIATION, HOW DO | | | WE PROCEED. | | | IF WE REFER TO THE 2017 FBC-ENERGY SECTION C501.2 AND | | | C501.3 | | | | | | RESPONSE: | | | GOOD MORNING MR. HERRERO, | | | AFTER SOME RESEARCH, I THINK YOU MIGHT BE ABLE TO | | | COMPLY WITH SEC. 503.1 FBC-ENERGY CONSERVATION (2017) | | | BY JUST FILING THE EXPOSED CEILING AND WALL CAVITIES | | | WITH INSULATION. NO NEED TO SUBMIT ENERGY CALCULATIONS. | | | NOTE: THIS IS ONLY IF THERE IS NO RECONFIGURATION OF | | | ANY OF THE SPACES IN THE TOWNHOUSE. | | | I HOPE THIS HELPS, | | | THANK YOU | | | | | | JULIO C. GOMEZ | | | CITY OF WEST PALM BEACH | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-28 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-28 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2018-03-28 11:51:17 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE ENERGY CALCULATIONS FORM R402-2017 SUBMITTED; | | | A) ITEM #10B DOESN'T COMPLY WITH GENERAL INSTRUCTIONS | | | NOTE #1. NEED TO COMPLY WITH ALL THE REQUIREMENTS OF | | | TABLE R402A OR USE PERFORMANCE METHOD FORM 405-2017. | | | B) COMPLETE TABLE R402B AS REQUIRED BY GENERAL | | | INSTRUCTIONS NOTE#3. | | | C) ENGINEER OF RECORD PREPARING THE ENERGY CALCULATIONS | | | SUBMITTED TO PROVIDE HIS INFORMATION AS REQUIRED BY | | | CHAPTER 471 F. S. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-12 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-12 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2018-03-12 11:13:58 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017). | | | | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR | | | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME | | | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT | | | ISSUANCE. | | | | | | | | | | | | | | | 1- ENERGY CALCULATIONS SUBMITTED PRESCRIPTIVE FORM | | | R402-2017 SUBMITTED; | | | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM AS | | | REQUIRED BY GENERAL INSTRUCTIONS NOTE#4 OF FORM | | | SUBMITTED AND SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | B) ITEM #10B DOESN'T COMPLY WITH GENERAL INSTRUCTIONS | | | NOTE #1. NEED TO COMPLY WITH ALL THE REQUIREMENTS OF | | | TABLE R402A WHEN USING THE PRESCRIPTIVE METHOD. NEED | | | R-30 CEILING INSULATION OR USE PERFORMANCE METHOD FORM | | | 405-2017. | | | NOTE: ENGINEER WROTE DOWN SEC. R405.2.1. THIS ONLY | | | APPLIES WHEN USING PERFORMANCE METHOD FORM R405-2017. | | | | | | C) COMPLETE TABLE R402B AS REQUIRED BY GENERAL | | | INSTRUCTIONS NOTE#3. SEC. R101.5.1.1.1 FBC-ENERGY | | | CONSERVATION. | | | | | | D) ENGINEER OF RECORD PREPARING THE ENERGY CALCULATIONS | | | SUBMITTED TO PROVIDE HIS INFORMATION AS REQUIRED BY | | | CHAPTER 471 F. S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC | | | RECORDS. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE | | | VALUATION AS REQUIRED AND INCLUDE THE DESIGN | | | PROFESSIONAL FEES. | | | REPEAT COMMENT. | | | | | | | | | NOTE: | | | PLANS SUBMITTED ARE MISSING ONE MECHANICAL DRAWING M-1. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-01-26 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-01-26 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2018-01-26 10:12:00 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- PROVIDE COMPLETE ENERGY CALCULATIONS (2 COPIES) AS | | | REQUIRED BY SEC. R501.1 FBC-ENERGY CONSERVATION, 6TH | | | EDITION (2017). | | | | | | 2- PLANS TO SHOW INSULATION ON WALLS AND CEILINGS AS | | | REQUIRED BY SEC. R103.2 FBC-ENERGY CONSERVATION. NOTE: | | | COORDINATE WITH ITEM #1 ABOVE TO AVOID | | | CONFLICTS/DELAYS. | | | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE | | | VALUATION AS REQUIRED AND INCLUDE THE DESIGN | | | PROFESSIONAL FEES. | | | | | | 4- SHEET A-1: | | | A) THE CURRENT CODE IN EFFECT IS THE FBC 6TH EDITION | | | (2017) NOT THE FBC 2014. REVISE INFORMATION BELOW THE | | | LEGAL DESCRIPTION. CHAPTER 553 F.S. | | | | | | B) PROPERTY LEGAL DESCRIPTION SHOWN IS INCORRECT. | | | REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | C) CLARIFY WHY THERE IS A NOTE UNDER THE SCOPE OF WORK | | | STATING THAT "RECONSTRUCTION OF UNIT UNDER SEPARATE | | | PERMIT"?. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | D) CLARIFY WHAT THE LETTERS A,B AND C LOCATED NEXT TO | | | EACH EXTERIOR DOOR STANDS FOR?. THERE IS NOT LEGEND. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-02-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-23 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-23 |
Time |
11:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-01-26 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-26 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2018-01-26 13:24:24 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | SMOKE ALARMS REQUIRED, AND SHALL BE ON ARC FAULT | | | CIRCUIT. | | | PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC | | | R314.3 | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | R314.3, FBC 107.2.1 | | | | | | PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONIES. | | | NEC 210.52(E)(3); FBC RE3901.7 | | | | | | WASHING MACHINE MAY HAVE TO BE ON GFCI IF WITHIN 6" OF | | | THE SINK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-04-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-04-26 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-26 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2018-04-26 11:06:33 | RECEIVED E-MAIL FROM DARIO HERRERO (ENGINEER) REGARDING | | | ENERGY CODE. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-28 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-28 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2018-03-28 11:46:27 | MET WITH CONTRACTOR (MARTY). HE AGREED TO ISSUE PERMIT | | | WITH PROVISO. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-12 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-02-09 |
Time |
15:28 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-01-26 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-08 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-08 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-08 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2018-05-08 11:11:27 | ONE MECHANICAL DRAWING WAS MISSING AT TIME OF PERMIT | | | ISSUANCE. CONTRACTOR BROUGHT A NEW SIGNED AND SEALED | | | DRAWING. DRAWING SUBMITTED MATCHES APPROVED PLAN BY | | | CHRIS MONTELLO. RE-STAMPED PLAN. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-02-13 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-02-13 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-02-13 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-01-25 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-01-25 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-03-02 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-03-02 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-03-02 |
Time |
07:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-25 |
Time |
05:49 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-25 |
Time |
05:49 |
Sent To |
|
|
| Notes |
| 2018-01-25 05:59:04 | 01/25/2018 PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PLEASE CLARIFY SCOPE OF WORK. ARE THE WALLS AND | | | PLUMBING FIXTURE AT ALL BEING RELOCATED FROM THERE | | | ORIGINAL LOCATION? FBC 107.2.1 | | | | | | 2) PLEASE CHANGE BOX AND LIST CURRENT EFFECTIVE | | | BUILDING CODE AS FBC 2017 | | | | | | 3) MINIMUM PLAN REVIEW CRITERIA REQUIRES A PLUMBING | | | SANITARY ISOMETRIC DRAWING. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|