Plan Review Details - Permit 18010164
Plan Review Stops For Permit 18010164
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By jleahy Date 2018-05-11 Time 14:55 Rev Time 0.00
Received By jleahy Date 2018-05-11 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By jleahy Date 2018-05-03 Time 16:18 Rev Time 0.00
Received By jleahy Date 2018-05-01 Time 12:14 Sent To  
Notes
2018-05-03 16:20:38FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE SHOWN FOR THE AMOUNT OF FIXTURES AND LABOR IS LOW
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By jleahy Date 2018-01-17 Time 13:11 Rev Time 0.00
Received By jleahy Date 2018-01-17 Time 13:11 Sent To  
Notes
2018-01-17 13:12:16SEE ZONING NOTES JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-03 Cont ID  
Sent By jleahy Date 2018-05-03 Time 16:20 Rev Time 0.00
Received By jleahy Date 2018-04-04 Time 13:36 Sent To  
Notes
2018-04-05 13:36:12RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-17 Cont ID  
Sent By jleahy Date 2018-01-17 Time 14:38 Rev Time 0.00
Received By jleahy Date 2018-01-05 Time 15:24 Sent To  
Notes
2018-01-09 16:21:32TO ELECTRIC
2018-01-08 15:24:22ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-01 Cont ID  
Sent By aaponte Date 2018-05-01 Time 11:49 Rev Time 0.00
Received By aaponte Date 2018-05-01 Time 11:49 Sent To  
Notes
2018-05-01 11:49:48PROVISO: ADDITIONAL DECORATIVE LIGHTING SHALL BE
 PROVIDED ALONG QUADRILLE BLVD TO COMPLY WITH THE
 MINIMUM 0.6 FOOTCANDLE REQUIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-09 Cont ID  
Sent By AA Date 2018-01-09 Time 16:13 Rev Time 0.00
Received By aaponte Date 2018-01-09 Time 12:09 Sent To  
Notes
2018-01-09 16:21:161. PLEASE PROVIDE PHOTOMETRICS FOR THE ENTIRE SIDEWALK
 AROUND PROJECT. MINIMUM FOOTCANDLE REQUIREMENT IS 0.6
 FOOTCANDLE AT 1 FOOT ABOVE SIDEWALK AT THE BACK OF
 CURB. LIGHT SOUCES CAN COMBINE STREET POLES AND
 FIXTURES ATTACHED TO BUILDING.
 2. PLEASE CONFIRM THE PROPOSED FIXTURE IS EQUIVALENT TO
 CITY STANDARD FOR DOWNTOWN. CONTACT ANA MARIA APONTE
 FOR DETAILS (561-822-1439)
 3. DECORATIVE LIGHT FIXTURE SHALL BE INSTALLED AROUND
 THE ENTIRE PROJECT. IF EXISTING COBRA HEAD OR OTHER
 NON-DECORATIVE POLES AND FIXTURES EXIST, THEY SHALL BE
 REMOVED AND REPLACED WITH NEW DECORATIVE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.