Plan Review Details - Permit 18010127
Plan Review Stops For Permit 18010127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-10 Cont ID  
Sent By cthroop Date 2018-02-10 Time 07:24 Rev Time 0.00
Received By cthroop Date 2018-02-09 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-01-22 Cont ID  
Sent By cthroop Date 2018-01-22 Time 07:41 Rev Time 0.00
Received By cthroop Date 2018-01-18 Time 14:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-02-20 Cont ID  
Sent By jpearson Date 2018-02-20 Time 11:21 Rev Time 0.00
Received By jpearson Date 2018-02-20 Time 11:01 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-02-07 Cont ID  
Sent By jpearson Date 2018-02-07 Time 11:03 Rev Time 0.00
Received By jpearson Date 2018-02-07 Time 11:03 Sent To  
Notes
2018-02-07 11:03:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED:
  
 1. NO PLAN REVISIONS ARE INDICATED. REVISIONS SHOULD BE
 CLOUDED OR OTHERWISE OBVIOUS. PLEASE RESUBMIT WITH
 REVISIONS IDENTIFIED. FBC 107.2.1
  
 NEW COMMENT:
  
 2. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By jpearson Date 2018-01-17 Time 12:27 Rev Time 0.00
Received By jpearson Date 2018-01-17 Time 12:27 Sent To  
Notes
2018-01-17 12:28:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO PLAN REVISIONS ARE INDICATED. REVISIONS SHOULD BE
 CLOUDED OR OTHERWISE OBVIOUS. PLEASE RESUBMIT WITH
 REVISIONS IDENTIFIED. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-02-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-15 Time 13:37 Sent To  
Notes
2018-02-16 13:37:18RESUB OF REVISION ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-10 Cont ID  
Sent By cthroop Date 2018-02-10 Time 07:24 Rev Time 0.00
Received By cthroop Date 2018-01-26 Time 12:55 Sent To I
Notes
2018-01-29 12:59:55R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By cthroop Date 2018-01-22 Time 07:41 Rev Time 0.00
Received By cthroop Date 2018-01-04 Time 16:01 Sent To I
Notes
2018-01-05 16:01:32R10

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By thunt Date 2018-02-07 Time 15:07 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By gjohnson Date 2018-01-10 Time 06:38 Rev Time 0.00
Received By thunt Date 2018-01-10 Time 06:38 Sent To  
Notes
2018-01-10 06:53:2001/10/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) MIN PLAN REVIEW REQUIRES A SEPERATE SANITARY RISER
 DRAWING. FBC 107.3.5, 107.2.1
  
 2) MIN DIMENSIONS FOR A LAVATORIES IN 15" ON EACH SIDE
 ( TOTAL 30") AND NOT LESS THEN 21" IN FRONT OF FIXTURE.
 FPC P2705.1 (5)
  
 3) MIN SHOWER COMPARTMENTS SHALL NOT BE LESS THEN 30" X
 30" SQUARE, 900 SQUARE INCHES OF INTERIOR DIMENSION
 MIN. EXCEPTION: SHOWER COMPARTMENTS HAVING NOT LESS
 THEN 30" IN MIN DIMENSION SHALL HAVE A CROSS-SECTIONAL
 AREA NO LESS THEN 1300 SQUARE INCHES. FPC P2708.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  