Plan Review Details - Permit 18010054
Plan Review Stops For Permit 18010054
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-02-07 Cont ID  
Sent By jleahy Date 2018-02-07 Time 11:57 Rev Time 0.00
Received By jleahy Date 2018-02-07 Time 11:57 Sent To  
Notes
2018-02-07 11:58:27CUSTOMER CALLED WITH NEW VALUE $14,500 SENT TO
 PROCESSING JLEAHY

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-02-07 Cont ID  
Sent By jleahy Date 2018-02-05 Time 12:14 Rev Time 0.00
Received By jleahy Date 2018-02-05 Time 11:57 Sent To I
Notes
2018-02-05 12:42:01CONTRACT SUBMITTED SHOWS WAY TO MUCH WORK NOT SHOWN OR
 VALUED INTO THIS JOB.
  
 SUBMIT PLANS SHOW ALL OF THIS ADDITIONAL WORK SHOWN ON
 CONTRACT. $4500 IS NOT
 A REALISTIC VALUE FOR THE WORK SHOWN IN THE CONTRACT.
  
 SEE ITEMS 7, 8 9, 10, 11, 12, 13, 14, 15,

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-26 Cont ID  
Sent By jleahy Date 2018-01-26 Time 10:36 Rev Time 0.00
Received By jleahy Date 2018-01-26 Time 10:36 Sent To  
Notes
2018-01-26 10:42:07FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 DRAWINGS NEED TO SIGNED AND SEALED BY AN ENIGINEER AS
 STATED IN REVIEW #1, YOUR LICESNE IS LIMITED 250 VOLT
 OR LESS FOR SIGNING AND SEALING AS A CONTRACTOR.
  
  
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-09 Cont ID  
Sent By jleahy Date 2018-01-09 Time 15:42 Rev Time 0.00
Received By jleahy Date 2018-01-09 Time 14:41 Sent To  
Notes
2018-01-09 15:46:11FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED LAYOUT OF THE ELEVATOR EQUIPMENT ROOM. SHOW
 LOACTION A EQUIPMENT IN ROOM.
  
 VLAUE OF WORK IS LOW, SUPPLY A SIGNED CONTRACT FOR WORK
 INVOLVED.
  
 300A BRANCH TAPS SHALL BE DONE IN ACCORDANCE WITH
 620.62 SIGNED AND SEALED BY ENGINEER.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-07 Cont ID  
Sent By jleahy Date 2018-02-07 Time 11:57 Rev Time 0.00
Received By jleahy Date 2018-02-07 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-05 Cont ID  
Sent By jleahy Date 2018-02-07 Time 11:53 Rev Time 0.00
Received By jleahy Date 2018-02-02 Time 14:55 Sent To  
Notes
2018-02-02 14:55:50RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-26 Cont ID  
Sent By jleahy Date 2018-01-26 Time 10:42 Rev Time 0.00
Received By jleahy Date 2018-01-24 Time 13:53 Sent To  
Notes
2018-01-25 13:53:18RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-09 Cont ID  
Sent By jleahy Date 2018-01-09 Time 15:46 Rev Time 0.00
Received By jleahy Date 2018-01-03 Time 10:13 Sent To  
Notes
2018-01-05 10:13:40ELEC <5K