Plan Review Details - Permit 18010014
Plan Review Stops For Permit 18010014
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-08-04 Cont ID  
Sent By shill Date 2018-08-04 Time 13:55 Rev Time 0.00
Received By shill Date 2018-08-04 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 18:17 Rev Time 0.00
Received By shill Date 2018-07-30 Time 18:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:10 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-09 Cont ID  
Sent By aclange Date 2018-04-09 Time 15:58 Rev Time 0.00
Received By aclange Date 2018-04-09 Time 15:55 Sent To  
Notes
2018-04-09 15:56:10ACTION: BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
  
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
  
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-08 Cont ID  
Sent By jwitmer Date 2018-03-08 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2018-03-08 Time 06:44 Sent To  
Notes
2018-03-08 07:00:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010014
 ADD: 1100 S. FLAGLER DR. SUITE; 12A
 CONT: PDC DEVELOPMENT CORP.
 TEL: 561-793-5852
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. MARCH 08/2018
 ACTION: BUILDING PROVISO
  
 1) SHEET 002-A-2 INDICATES THE USE OF TILE, MARBLE, BUT
 THERE HAS BEEN NO SUBMISSION FOR CODE COMPLIANCE FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) COMPLIED. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014 1207.2
 AIR-BORNE SOUND.WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 2C) PROVISO / DEFERRED SUBMITTAL: FLAME SPREAD- FBC-B
 2014 603.1. EXCEPTION 2. INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-07 Cont ID  
Sent By jwitmer Date 2018-02-07 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2018-02-07 Time 13:13 Sent To  
Notes
2018-02-07 13:58:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010014
 ADD: 1100 S. FLAGLER DR. SUITE; 12A
 CONT: PDC DEVELOPMENT CORP.
 TEL: 561-793-5852
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. MARCH 08/2018
 ACTION: BUILDING PROVISO
  
 1) SHEET 002-A-2 DOES NOT COMPLY WIT THE FAIR HOUSING
 GUIDELINE IN THE KITCHEN FOR THE WIDTH BETWEEN THE
 KITCHEN SINK AND THE ISLAND GAS RANGE. SEE REQUIREMENT
 # 7 SECTION (1)(B) (B)CLEARANCE BETWEEN COUNTERS AND
 ALL OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES OR
 WALLS IS AT LEAST 40 INCHES.
 100.205(C)(3)(IV)
  
 2) SHEET 002-A-2 INDICATES THE USE OF TILE, MARBLE, BUT
 THERE HAS BEEN NO SUBMISSION FOR CODE COMPLIANCE FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A). FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014 1207.2
 AIR-BORNE SOUND.WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 2C) PROVISO / DEFERRED SUBMITTAL: FLAME SPREAD- FBC-B
 2014 603.1. EXCEPTION 2. INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) SUFFOLK CONSTRUCTION HAS COMPLETED SITE SPECIFIC
 TESTING FOR (AIIC) STRUCTURE BORNE SOUND, THE BUILDING
 DEPARTMENT DOES NOT KNOW IF THIS TESTING WILL BE MADE
 AVAILABLE TO THE OTHER GENERAL CONTRACTORS?
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-07 Cont ID  
Sent By jleahy Date 2018-02-07 Time 07:17 Rev Time 0.00
Received By jleahy Date 2018-02-07 Time 07:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-25 Cont ID  
Sent By pleduc Date 2018-01-25 Time   Rev Time 0.00
Received By pleduc Date 2018-01-25 Time 13:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-04-21 Cont ID  
Sent By gjohnson Date 2018-04-21 Time 09:21 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 09:21 Sent To  
Notes
2018-04-21 09:22:47GAS PROVISO:
  
 1. PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR PRESURE
 REGULATOR AND APPLIANCES TO VARIFY BTU LOAD. AND
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2
 ON JOBSITE FOR SECOND ROUGH INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 11:39 Rev Time 0.00
Received By gjohnson Date 2018-03-26 Time 11:39 Sent To  
Notes
2018-03-26 11:40:331ST REVIEW: FBC 2010 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 1. PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR PRESURE
 REGULATOR AND APPLIANCES TO VARIFY BTU LOAD. AND
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-26 Cont ID  
Sent By gjohnson Date 2018-02-26 Time 07:18 Rev Time 0.00
Received By gjohnson Date 2018-02-26 Time 07:18 Sent To  
Notes
2018-02-26 07:21:341ST REVIEW: FBC 2010 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR PRESURE
 REGULATOR AND APPLIANCES TO VARIFY BTU LOAD. AND
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2018-08-14 Cont ID  
Sent By shill Date 2018-08-14 Time 18:07 Rev Time 0.00
Received By shill Date 2018-08-13 Time 15:36 Sent To  
Notes
2018-08-14 15:36:29SIGNATURES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 15:54 Rev Time 0.00
Received By shill Date 2018-08-08 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-08-04 Cont ID  
Sent By shill Date 2018-08-04 Time 13:55 Rev Time 0.00
Received By shill Date 2018-08-01 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 18:17 Rev Time 0.00
Received By shill Date 2018-07-02 Time 12:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:10 Rev Time 0.00
Received By shill Date 2018-05-15 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-04-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-02 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 11:41 Rev Time 0.00
Received By gjohnson Date 2018-03-06 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-22 Cont ID  
Sent By cpuell Date 2018-02-22 Time 15:46 Rev Time 0.00
Received By cpuell Date 2018-01-16 Time 14:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2018-08-10 Cont ID  
Sent By ccole Date 2018-08-10 Time 14:32 Rev Time 0.00
Received By ccole Date 2018-08-10 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2018-08-01 Cont ID  
Sent By ccole Date 2018-08-01 Time 16:14 Rev Time 0.00
Received By ccole Date 2018-08-01 Time 16:06 Sent To  
Notes
2018-08-01 16:23:565TH REVIEW FBC-2007 MECHANICAL
 PERMIT #18010014
 8/1/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-100 & M-101: THE REVISED PLAN NOW INDICATES
 HP-F IS SUPPLYING 1350 CFMS OF SUPPLY AIR WHICH IS
 STILL 250 CFMS SHORT OF THE UNIT'S CAPACITY OF 1600
 CFMS PER THE EQUIPMENT SCHEDULE. THIS UNIT STILL
 APPEARS TO BE OVERSIZED FOR THE AREA IT IS SERVING.
 PLEASE PROVIDE AC COOLING AND HEATING CALCULATIONS
 SPECIFIC TO THE AREA THIS UNIT IS SERVING- SECTION
 503.2.2 FBC-10 ENERGY
 CONSERVATION.
  
 2) THE REVISED SHEETS M-100 & M-101 MUST BE
 ELECTRONICALLY SIGNED AND SEALED BY THE EOR- SECTION
 61G15-23.005 FLORIDA ADMININSTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2018-07-30 Cont ID  
Sent By ccole Date 2018-07-30 Time 17:26 Rev Time 0.00
Received By ccole Date 2018-07-25 Time 10:27 Sent To  
Notes
2018-07-30 17:40:204TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 4/2518
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100 & M101: HP-F APPEARS TO BE OVERSIZED AT
 4-TONS AND 1600 CFMS OF SUPPLY AIR BECAUSE THE LAYOUT
 PLAN INDICATES IT IS ONLY REQUIRED TO PRODUCE 1000 CFMS
 WHICH WOULD BE MORE TYPICAL OF A 2.5 TON SYSTEM- PLEASE
 CLARIFY.
  
 2) IT HAS BEEN DETERMINED THAT ALL APARTMENT BUILDOUTS
 WILL BE DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES
 UNTIL WHICH TIME THE BUILDING RECEIVES A CERTIFICATE OF
 OCCUPANCY. PLEASE CORRECT THE 2014 REFERENCE ON THE A-1
 COVER SHEET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-06-08 Cont ID  
Sent By ccole Date 2018-06-08 Time 09:33 Rev Time 0.00
Received By ccole Date 2018-06-07 Time 17:23 Sent To  
Notes
2018-06-08 10:00:323RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 4/2518
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 4TH REQUEST FOR ENERGY CALCULATIONS FOR
 THE APARTMENT BUILDOUT. SUBMITTED FOR THIS REVIEW IS A
 COVER SHEET FROM THE EOR STANTEC WHICH IS TITLED
 "ENERGY COMPLIANCE CALCULATIONS FOR THE BRISTOL ". THE
 COVER SHEET DOES NOT SPECIFICALLY REFERENCE THE
 APARTMENT, AND THERE IS NO COMPLIANCE DATA TO GO WITH
 THE SHEET, EXCEPT UPLOADED FOR REVIEW IS THE ORIGNAL
 2010 ENERGY GAUGE COMPLIANCE SUBMITTAL FOR THE ENTIRE
 BUILDING. PLEASE NOTE THE NEW APARTMENT BUILDOUT IS
 UNDER THE 2017 CODE, THEREFORE REVISED CALCULATIONS
 SPECIFIC TO THE APARTMENT MUST BE SUBMITTED.
  
 2) COMMENT #8 FROM THE PREVIOUS REVIEW ABOUT THE
 MISSING FIRE DAMPERS FOR THE 6" FLEX DUCT AND THE O/A
 DUCT PENETRATING THE LAUNDRY ROOM WALL STILL EXISTS.
 PLEASE REMOVE THE FIRE-RATED WALL SYMBOL AT THE
 PENETRATIONS IF THE WALL IS NOT RATED, OR PROVIDE THE
 DAMPERS.
  
 3) M.100: AS PREVIOUSLY REQUESTED, A SMOKE DETECTOR IS
 REQUIRED IN THE SUPPLY TRUNK OF HP-G PER SECTION
 606.2.1.
  
 4) M.100: ACKNOWLEDGED THAT MANUFACTURER'S
 SPECIFICATIONS FOR THE GAS RANGE, KITCHEN EXHAUST HOOD
 AND DUCT, AND THE DRYER WILL BE DEFERRED SUBMITTALS.L
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-04-25 Cont ID  
Sent By ccole Date 2018-04-25 Time 10:41 Rev Time 0.00
Received By ccole Date 2018-04-25 Time 10:22 Sent To  
Notes
2018-04-25 10:56:073RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 4/2518
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST AND 2ND REVIEW COMMENTS HAVE BEEN PARTIALLY
 ADDRESSED. COMMENTS, OR PARTS OF COMMENTS REMAINING ARE
 LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER.
  
 1) THE REQUESTED AC CALCULATIONS WERE NOT PROVIDED.
  
 2) THE REQUESTED ENERGY CALCULATIONS WERE NOT PROVIDED.
  
 3) INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO THE
 HEAT PUMPS PER TABLE 403.3, AND HOW THE O/A SUPPLY WILL
 BE AUTOMATICALLY DAMPERED PER SECTION C403.2.4.3 FBC-17
 ENERGY CONSERVATION.
  
 4) SHEET M1.00: THERE IS NO TEXT ON THE PLAN FOR KEYED
 NOTES #1 & 2.
  
 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
 (NOT PROVIDED)
  
 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2.
 (NOT PROVIDED)
  
 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT, AND THE
 DRYER. (NOT PROVIDED).
  
 8) M.100: IT APPEARS THAT FIRE DAMPERS ARE MISSING
 WHERE THE 6" FLEX DUCT AND O/A DUCT ARE PENETRATING THE
 CORE WALL SEPARATING THE HALL AND THE LAUNDRY- SECTION
 607.5.2.
  
 9) M102.02: PLEASE INDICATE WHICH OF THE SUBDUCT
 DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET
 EXHAUST, AND THE RANGE EXHAUST. (NOT PROVIDED).
  
 10) M.100: A SMOKE DETECTOR IS REQUIRED IN THE SUPPLY
 TRUNK OF HP-G PER SECTION 606.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-21 Cont ID  
Sent By ccole Date 2018-03-21 Time 17:51 Rev Time 0.00
Received By ccole Date 2018-03-21 Time 17:36 Sent To  
Notes
2018-03-21 17:59:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 3/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND THE
 REQUESTED RESPONSE LETTER FROM THE DESIGN PROFESSIONAL
 WAS NOT PROVIDED. PLEASE NOTE THAT IT IS ACKNOWLEDGED
 THAT ENERGY, AC, AND VENTILATION CALCULATIONS WERE
 SUBMITTED FOR THE APARTMENT UNDER THE MAIN PERMITS FOR
 THE BRISTOL, HOWEVER THIS IS A SEPARATE PERMIT TO BE
 FILED FOR THE PUBLIC RECORD, AND THEREFORE IT IS
 NECESSARY
  
 THAT ALL COMPLIANCES SPECIFICALLY FOR THIS UNIT
 BUILD-OUT ARE MET. I HAVE COPIED MY 1ST REVIEW
 COMMENTS, INCLUDING THE REQUEST FOR THE CALCULATIONS
 BELOW- PLEASE COMPLY:
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 4) M1.00: CLARIFY HOW SUPPLY AIR IS BEING RETURNED INTO
 THE AC CLOSETS- SECTION 601.6.
  
 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2
  
 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT, AND THE
 DRYER.
  
 8) M.100: IT APPEARS THAT FIRE DAMPERS ARE MISSING
 WHERE THE 6" FLEX DUCT AND O/A DUCT ARE PENETRATING THE
 CORE WALL SEPARATING THE HALL AND THE LAUNDRY- SECTION
 607.5.2.
  
 9) M102.02: PLEASE INDICATE WHICH OF THE SUBDUCT
 DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET
 EXHAUST, AND THE RANGE EXHAUST.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-16 Cont ID  
Sent By ccole Date 2018-02-16 Time 10:23 Rev Time 0.00
Received By ccole Date 2018-02-16 Time 10:23 Sent To  
Notes
2018-02-16 11:06:031ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010014
 2/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 4) M1.00: CLARIFY HOW SUPPLY AIR IS BEING RETURNED INTO
 THE AC CLOSETS- SECTION 601.6.
  
 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2
  
 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE A
 DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT INTO
 THE SHAFT.
  
 8) M1.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION OF
 THE EXHAUST DUCT INTO THE SHAFT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-06-15 Cont ID  
Sent By gjohnson Date 2018-06-15 Time 08:36 Rev Time 0.00
Received By gjohnson Date 2018-06-15 Time 08:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-21 Cont ID  
Sent By gjohnson Date 2018-04-21 Time 09:13 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 09:25 Sent To  
Notes
2018-04-21 09:18:37PLUMBING PROVISO:
  
 3. REINFORCEMENT FOR GRAB BARS IS REQUIRED IN ALL THE
 BATHROOM LOCATED IN DWELLING UNIT PLEASE PROVIDE
 DETAILS SHOWING MOUNTING HEIGHTS OF GRAB BAR BACKING.
 PER FHA DESIGN MANUAL REQUIREMENT #6
  
 4. SHT. A-4 DETAIL #4 THE WATER PROOF MEMBRANE FOR THE
 SHOWER PAN SHALL BE SLOPED TO THE DRAIN MIN OF 2% SLOPE
 .PER FBC PL 417.5.2 THE WATER PROF MEMBRANE IS SHOWN AS
 FLAT ON THE CONCRETE SLAB. THE WATER PROOF MEMBRANE
 SHALL BE SLOPED NOT JUST THE TILE.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 11:34 Rev Time 0.00
Received By gjohnson Date 2018-03-26 Time 11:34 Sent To  
Notes
2018-03-26 11:39:312ND REVIEW: FBC 2010
  
 PLUMBING COMMENTS: A COMMENT RESPONSE LETTER FOR
 PLUMBING WAS NOT PROVIDED, TO EXPEDITE APPROVAL PLEASE
 PROVIDE RESPONSE LETTER AND CONTACT PLAN REVIEWER.
  
 PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 2. PLEASE INDICATE ON THE PLAN THE SAFE HARBOR DESIGN
 DOCUMENT THAT WAS USED TO DESIGN THIS UNIT TO THE FHA
 REQUIREMENTS. WPB AMEND TO FBC 107.2.1
  
 3. REINFORCEMENT FOR GRAB BARS IS REQUIRED IN ALL THE
 BATHROOM LOCATED IN DWELLING UNIT PLEASE PROVIDE
 DETAILS SHOWING MOUNTING HEIGHTS AND LOCATION OF GRAB
 BAR BACKING. PER FHA DESIGN MANUAL REQUIREMENT #6
  
 4. SHT. A-4 DETAIL #4 THE WATER PROOF MEMBRANE FOR THE
 SHOWER PAN SHALL BE SLOPED TO THE DRAIN MIN OF 2% SLOPE
 .PER FBC PL 417.5.2
  
 5. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND
 INSTALLATION GUIDE FOR THE WATER PROOF MEMBRANE FOR
 SHOWER LINER SHALL COMPLY WITH FBC PL 417.5.2.5
  
 6. PROVIDE DETAIL FOR HEIGHT OF LAVATORY SANITARY TO
 COMPLY WITH FHA
  
 7. SHT. P001.00 THIS PROJECT IS DESIGNED UNDER FBC 2010
 UNDER THE BUILDING DEPARTMENT NOTES IT LIST 2014. THE
 GAS SHALL COMPLY WITH FBC FG 2010 PLEASE CLARIFY PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-22 Cont ID  
Sent By gjohnson Date 2018-02-22 Time 14:16 Rev Time 0.00
Received By gjohnson Date 2018-02-22 Time 14:14 Sent To  
Notes
2018-02-22 14:38:261ST REVIEW: FBC 2010
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE
 FOR THE TOILET IN THE SPEC B MASTER BATHROOM. PER FHA
 DESIGN MANUAL REQUIREMENT #7 PG 7.43
  
 2. PLEASE INDICATE ON THE PLAN THE SAFE HARBOR DESIGN
 DOCUMENT THAT WAS USED TO DESIGN THIS UNIT TO THE FHA
 REQUIREMENTS. WPB AMEND TO FBC 107.2.1
  
 3. REINFORCEMENT FOR GRAB BARS IS REQUIRED IN ALL THE
 BATHROOM LOCATED IN DWELLING UNIT PLEASE PROVIDE
 DETAILS SHOWING MOUNTING HEIGHTS AND LOCATION OF GRAB
 BAR BACKING. PER FHA DESIGN MANUAL REQUIREMENT #6
  
 4. SHT. A-4 DETAIL #4 THE WATER PROOF MEMBRANE FOR THE
 SHOWER PAN SHALL BE SLOPED TO THE DRAIN MIN OF 2% SLOPE
 .PER FBC PL 417.5.2
  
 5. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND
 INSTALLATION GUIDE FOR THE WATER PROOF MEMBRANE FOR
 SHOWER LINER SHALL COMPLY WITH FBC PL 417.5.2.5
  
 6. PROVIDE DETAIL FOR HIEGHT OF LAVATORY VANITARY TO
 COMPLY WITH FHA
  
 7. SHT. P001.00 THIS PROJECT IS DESIGNED UNDER FBC 2010
 UNDER THE BUILDING DEPARTMENT NOTES IT LIST 2014. THE
 GAS SHALL COMPLY WITH FBC FG 2010 PLEASE CLARIFY PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2018-08-14 Cont ID  
Sent By shill Date 2018-08-14 Time 18:07 Rev Time 0.00
Received By shill Date 2018-08-14 Time 18:07 Sent To  
Notes
2018-08-14 18:07:34S&S ORIGINAL PAPER A SHEETS PROVIDED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 15:54 Rev Time 0.00
Received By shill Date 2018-08-10 Time 15:54 Sent To  
Notes
2018-08-10 15:57:27SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ARCHITECTURAL SHEETS ARE NOT DIGITALLY SIGNED AND
 SEALED
  
 PROVIDE ONE PAPER SIGNED AND SEALED ORIGINAL TO RESOLVE
 THIS COMMENT
  
2018-08-10 14:34:29MECH DIG/SIGS GOOD
 CCOLE- 8/10/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-08-04 Cont ID  
Sent By shill Date 2018-08-04 Time 13:52 Rev Time 0.00
Received By shill Date 2018-08-04 Time 13:52 Sent To  
Notes
2018-08-04 13:54:09SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ARCHITECTURAL SHEETS ARE NOT DIGITALLY SIGNED AND
 SEALED
  
 NEW MECHANICAL SHEETS UPLOADED ARE NOT DIGITALLY SIGNED
 AND SEALED - PLEASE CONFIRM PRIOR TO UPLOADING. IF YOU
 DO NOT KNOW HOW TO DO SO, PLEASE CONTACT ME FOR
 ASSISTANCE.
  
 PROVIDE ONE PAPER SIGNED AND SEALED ORIGINAL TO RESOLVE
 THIS COMMENT
  
 E, P SHEETS OK
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 18:10 Rev Time 0.00
Received By shill Date 2018-07-30 Time 18:10 Sent To  
Notes
2018-07-30 18:10:26SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ARCHITECTURAL SHEETS ARE NOT DIGITALLY SIGNED AND
 SEALED
 PROVIDE ONE PAPER SIGNED AND SEALED ORIGINAL TO RESOLVE
 THIS COMMENT
 E, P SHEETS OK
  
  
  
  
2018-07-30 17:43:07MECH SIGS OK
 CCOLE-7/30/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:09 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:08 Sent To  
Notes
2018-06-16 15:09:49SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ARCHITECTURAL SHEETS ARE NOT DIGITALLY SIGNED AND
 SEALED
 PROVIDE ONE PAPER SIGNED AND SEALED ORIGINAL TO RESOLVE
 THIS COMMENT
  
  
2018-04-25 11:19:41MECH DIG/SIGS GOOD
 CCOLE-4/25/18
2018-02-22 14:40:444/21/18 DIG SIG ON PLUMB PAGES IS GOOD/GPJ
2018-02-16 11:08:54MECH DIG/SIGS GOOD- 1ST REVIEW
 CCOLE