Plan Review Details - Permit 17121069
Plan Review Stops For Permit 17121069
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-13 Cont ID  
Sent By jgomez Date 2018-07-13 Time 14:09 Rev Time 0.00
Received By jgomez Date 2018-07-13 Time 14:08 Sent To  
Notes
2018-07-13 14:10:15 
 BUILDING PROVISO:
 1- THE PROPOSED ALTERATION IS A CHANGE IN OCCUPANCY
 WITH NO CHANGE OF OCCUPANCY CLASSIFICATION. A
 CERTIFICATE OF OCCUPANCY SHALL BE ISSUED BEFORE
 OPERATION AS REQUIRED BY SEC. 1001.2 FBC-EXISTING
 BUILDING.
  
 SEC. 1001.2 CHANGE IN OCCUPANCY WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION.
 A CHANGE IN OCCUPANCY, AS DEFINED IN SECTION 202, WITH
 NO CHANGE OF OCCUPANCY CLASSIFICATION SHALL NOT BE MADE
 TO ANY STRUCTURE THAT WILL SUBJECT THE STRUCTURE TO ANY
 SPECIAL PROVISIONS OF THE APPLICABLE FLORIDA BUILDING
 CODES, INCLUDING THE PROVISIONS OF SECTIONS 1002
 THROUGH 1011, WITHOUT THE APPROVAL OF THE CODE
 OFFICIAL. A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED
 WHERE IT HAS BEEN DETERMINED THAT THE REQUIREMENTS FOR
 THE CHANGE IN OCCUPANCY HAVE BEEN MET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-06 Cont ID  
Sent By jgomez Date 2018-07-06 Time 13:04 Rev Time 0.00
Received By jgomez Date 2018-07-06 Time 12:32 Sent To  
Notes
2018-07-06 13:10:25THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  
 BUILDING PROVISO:
 1- THE PROPOSED ALTERATION IS A CHANGE IN OCCUPANCY
 WITH NO CHANGE OF OCCUPANCY CLASSIFICATION. A
 CERTIFICATE OF OCCUPANCY SHALL BE ISSUED BEFORE
 OPERATION AS REQUIRED BY SEC. 1001.2 FBC-EXISTING
 BUILDING.
  
 SEC. 1001.2 CHANGE IN OCCUPANCY WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION.
 A CHANGE IN OCCUPANCY, AS DEFINED IN SECTION 202, WITH
 NO CHANGE OF OCCUPANCY CLASSIFICATION SHALL NOT BE MADE
 TO ANY STRUCTURE THAT WILL SUBJECT THE STRUCTURE TO ANY
 SPECIAL PROVISIONS OF THE APPLICABLE FLORIDA BUILDING
 CODES, INCLUDING THE PROVISIONS OF SECTIONS 1002
 THROUGH 1011, WITHOUT THE APPROVAL OF THE CODE
 OFFICIAL. A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED
 WHERE IT HAS BEEN DETERMINED THAT THE REQUIREMENTS FOR
 THE CHANGE IN OCCUPANCY HAVE BEEN MET.
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-04 Cont ID  
Sent By jgomez Date 2018-05-03 Time 19:21 Rev Time 0.00
Received By jgomez Date 2018-05-03 Time 14:25 Sent To  
Notes
2018-05-03 19:22:01BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) FORM C402-2014 SUBMITTED NEED TO BE CERTIFIED AT THE
 BOTTOM AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY
 CONSERVATION PRIOR TO RECEIVE THE PERMIT.
  
 C103.1.1.2 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM: (1) CLIMATE ZONE IS 1A NOT 8.. SEE SEC. C301.1
 FBC-ENERGY CONSERVATION. (2) SPECIFY THE PERMITTING
 OFFICE. (3) THE COMPLETE PROJECT NAME IS THE YELLOW
 DOOR RESTAURANT. (4) PROVIDE THE NAME OF THE BUILDER.
 SEC. C103.3 FBC-ENERGY CONSERVATION.
  
 3- REPEAT COMMENT. VALUATION DECLARED IN THE PERMIT
 APPLICATION IS TOO LOW. REVISE AS REQUIRED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 4- THE PROPOSED ALTERATION IS A CHANGE IN OCCUPANCY
 WITH NO CHANGE OF OCCUPANCY CLASSIFICATION. A
 CERTIFICATE OF OCCUPANCY SHALL BE ISSUED BEFORE
 OPERATION AS REQUIRED BY SEC. 1001.2 FBC-EXISTING
 BUILDING.
  
 SEC. 1001.2 CHANGE IN OCCUPANCY WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION.
 A CHANGE IN OCCUPANCY, AS DEFINED IN SECTION 202, WITH
 NO CHANGE OF OCCUPANCY CLASSIFICATION SHALL NOT BE MADE
 TO ANY STRUCTURE THAT WILL SUBJECT THE STRUCTURE TO ANY
 SPECIAL PROVISIONS OF THE APPLICABLE FLORIDA BUILDING
 CODES, INCLUDING THE PROVISIONS OF SECTIONS 1002
 THROUGH 1011, WITHOUT THE APPROVAL OF THE CODE
 OFFICIAL. A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED
 WHERE IT HAS BEEN DETERMINED THAT THE REQUIREMENTS FOR
 THE CHANGE IN OCCUPANCY HAVE BEEN MET.
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By aclange Date 2018-01-08 Time 08:26 Rev Time 0.00
Received By aclange Date 2018-01-05 Time 15:16 Sent To  
Notes
2018-01-08 08:25:52****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. OFFICE SIZE IS TOO SMALL IN BOTH DIRECTIONS.
  
 INTERIOR SPACE DIMENSIONS
 FBC 1208.1 MINIMUM ROOM WIDTHS.
 HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION.
 KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN
 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES
 OR COUNTER FRONTS AND WALLS.
  
 2. HOODS / VENTILATION
  
 FBC 1203.5 OTHER VENTILATION AND EXHAUST SYSTEMS.
 VENTILATION AND EXHAUST SYSTEMS FOR OCCUPANCIES AND
 OPERATIONS INVOLVING FLAMMABLE OR COMBUSTIBLE HAZARDS
 OR OTHER CONTAMINANT SOURCES AS COVERED IN THE FLORIDA
 BUILDING CODE, MECHANICAL OR THE FLORIDA FIRE
 PREVENTION CODE SHALL BE PROVIDED AS REQUIRED BY BOTH
 CODES.
  
 3. PROVIDE ELEVATION DETAILS TO SHOW HOW THE SERVICE
 COUNTER WILL BE IN COMPLIANCE WITH FLORIDA
 ACCESSIBILITY CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 4. INTERIOR PARTITION WALLS.
  
 A) ARE ALL OF THESE WALLS SHOWN NEW WALLS? CLARIFY
  
 B) THE WALL FRAMING DETAIL IS SHOWN AT 24 INCHES ON
 CENTER. CEMENT BOARD IS SHOWN ON SOME WALLS. PROVIDE
 MANUFACTURER?S SPECIFICATION ON THE PRODUCT USED SINCE
 MANY REQUIRE FRAMING AT 16 INCHES ON CENTER.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 5. GENERAL NOTES. PLEASE UPDATE THE FLORIDA
 ACCESSIBILITY CODE AND ENERGY CODE TO 2014 5TH EDITION.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 6. PERMIT VALUE IS TOO LOW. ADJUST VALUE WHEN YOUR
 PLANS ARE RESUBMITTED.
  
 FBC 109.3 BUILDING PERMIT VALUATIONS.
  
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By jpearson Date 2018-05-02 Time 12:23 Rev Time 0.00
Received By jpearson Date 2018-05-02 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-11 Cont ID  
Sent By jpearson Date 2018-01-11 Time 15:50 Rev Time 0.00
Received By jpearson Date 2018-01-11 Time 15:50 Sent To  
Notes
2018-01-11 15:50:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEED FROM DISCONNECT TO PANEL A SHOWS A # 8
 EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC
 250.122
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 3. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE EVIDENCE OF
 RESISTANCE TO GROUND OF 25 OHMS OR LESS. NEC 250.56
 4. SHOW ALL AVAILABLE GROUNDING ELECTRODES AT LOCATION
 WITH ATTACHMENT TO THE GROUNDING ELECTRODE CONDUCTOR.
 NEC 250.50; FBC 107.2.1
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2
 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 8. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 10. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-26 Cont ID  
Sent By pleduc Date 2018-04-26 Time   Rev Time 0.00
Received By pleduc Date 2018-04-25 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-03 Cont ID  
Sent By pleduc Date 2018-01-03 Time   Rev Time 0.00
Received By pleduc Date 2018-01-03 Time 11:38 Sent To  
Notes
2018-01-03 12:52:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THE HOOD VENT AND FIRE SUPPRESSION SYSTEMS SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS EACH.
  
  
 2) THE DOOR LOCKS INDICATES ON THE FRONT AND REAR DOORS
 SHALL COMPLY WITH NFPA, 101, CHAPTER 7, MEANS OF EGRESS
  
 PER NFPA 101, CHAPRE 39, NEW BUSINESS OCCUPANCIES
  
 39.2.2.2 DOORS.
 39.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 39.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
 7.2.1.5.5.2 THE ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1
 SHALL BE PERMITTED TO BE REVOKED BY THE AUTHORITY
 HAVING JURISDICTION FOR CAUSE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 12:33 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 12:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 08:13 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 08:13 Sent To  
Notes
2018-05-02 08:25:402ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED 6. SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 402.2 YOUR RESPONSE LETTER
 STATES THE MANUFACTURE SPECIFICATION ARE ATTACHED TO
 THE SUBMITTAL THEY ARE NOT IN THE SUBMITTAL PACKAGE
 PLEASE SUBMIT WE WILL HAVE TO HAVE THEM TO VERIFY CODE
 COMPLIANCE AND BTU LOAD.\
  
 NEW COMMENT:
  
 1. THE BTU LOAD FOR THE GRIDDLE IS SHOWN AT 105
 ON THE RISER AND 60 ON THE GAS LOAD CALCULATION PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE BTU LOAD ON THE MANIFOLD ON THE RISER 7' @ 11/2
 788K PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 13:31 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 13:31 Sent To  
Notes
2018-01-22 13:48:541ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GAS LOAD CALCULATIONS SHOWS 2" @ 59' THE RISER
 SHOWS A 11/2" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE GAS LOAD CALCULATIONS SHOWS 59' OF DEVELOPED
 LENGTH THE CUT SECTION ON THE RISER ADD UP TO 31'
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. THE RISER SHOWS A GRIDDLE @ 105K AND A GRIDDLE @ 60K
 IS THERE 2 GRIDDLES PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 4. ON THE RISER THE MANIFOLD PIPING BEHIND EQUIPMENT IS
 SHOWN AS 1" @ 788K IT SHALL BE 11/2" @ 518K PER FBC FG
 TABLE 402.4(2) PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-06 Cont ID  
Sent By jgomez Date 2018-07-06 Time 13:04 Rev Time 0.00
Received By jgomez Date 2018-06-28 Time 15:51 Sent To I
Notes
2018-06-28 15:52:03RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-30 Cont ID  
Sent By cpuell Date 2018-05-30 Time 09:12 Rev Time 0.00
Received By cpuell Date 2018-04-17 Time 14:07 Sent To  
Notes
2018-04-18 14:07:49B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2017-12-29 Time 11:28 Sent To  
Notes
2018-01-02 11:28:22B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-07-13 Cont ID  
Sent By jgomez Date 2018-07-13 Time 14:07 Rev Time 0.00
Received By jgomez Date 2018-07-13 Time 14:04 Sent To  
Notes
2018-07-13 14:08:49NO FEES. COUNTY STAMP DATED 7/9/18 BY MAB STATES RETAIL
 STRIP CENTER AND ZERO FEES.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-07-06 Cont ID  
Sent By jgomez Date 2018-07-06 Time 12:45 Rev Time 0.00
Received By jgomez Date 2018-07-06 Time 12:45 Sent To  
Notes
2018-07-06 12:46:09BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-04 Cont ID  
Sent By jgomez Date 2018-05-04 Time 07:48 Rev Time 0.00
Received By jgomez Date 2018-05-04 Time 07:39 Sent To  
Notes
2018-05-04 07:49:08BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-26 Cont ID  
Sent By ccole Date 2018-04-26 Time 14:53 Rev Time 0.00
Received By ccole Date 2018-04-26 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-16 Cont ID  
Sent By ccole Date 2018-01-16 Time 10:32 Rev Time 0.00
Received By ccole Date 2018-01-16 Time 10:31 Sent To  
Notes
2018-01-16 11:15:101ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17121069
 1/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A CHANGE OF
 OCCUPANCY IN ACCORDANCE WITH SECTION 202 FBC-14
 EXISTING BUILDING CODE. WPB BUSINESS RECORDS SHOW
 PREVIOUS TENANT WAS A DOG GROOMING BUSINESS- PLEASE
 CORRECT THE LEVEL 3 REFERENCE ON THE COVER SHEET. REFER
 TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND
 SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT. SEE
  
 SECTION C401.2 FOR COMPLIANCE PATH INFORMATION.
  
 2) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 12:33 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 12:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 08:25 Rev Time 0.00
Received By gjohnson Date 2018-05-01 Time 10:43 Sent To  
Notes
2018-05-02 08:40:352ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER TEMPERING DEVICE WATTS FL1170 IS NOT A
 CODE COMPLIANT FORR THE REQUIREMENTS OF TEMPERED WATER
 AT THE LAVATORY'S. PER MANUFACTURE SPECIFICATIONS
 A) IT IS A DISCONTINUED PRODUCT BECAUSE IT IS NOT LEAD
 FREE.
 B) IT DOES NOT MEET ASSE 1070 OR CSA B125.3 AS REQUIRED
 BY FBC PL 614.5
 PLEASE NOTE ON THE PLAN THAT THE WATER-TEMPERATURE
 LIMITING DEVICE IS REQUIRED FO THE LAVATORY'S AND MEETS
 ASSE 1070 OR CSA B125.3
  
 2. TWO COPY'S OF THE GREASE MONKEY SIZING CALCULATION
 SHALL BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL.
 PER WPB AMEND TO FBC 107.2.1.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 12:51 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 08:17 Sent To  
Notes
2018-01-22 12:57:341ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS SHALLL BE A CHANGE OF OCCUPANCY PER FBC EX 202
 AND 1001.2 PLEASE CHANGE PLAN TO INDICATE THIS. PER WPB
 AMEND TO FBC 107.2.1
  
 2. VALUATION OF JOB IS LOW PLEASE PROVIDE DOCUMENTATION
 TO SHOW VALUATION. PER WPB AMEND TO FBC 109.3 BUILDING
 PERMIT VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 3. SHT. 1.0A SHOWS CENTER OF TOILET OFF SIDE WALL AT
 18" MIN IT SHALL BE 16" MIN - 18" MAX. PER FBC ACC
 604.2
  
 4. THE GRAB BARS SHALL BE MEASURED FROM FROM FINISHED
 FLOOR TO TOP OF GRIPPING SURFACE PLEASE SHOW ON PLAN.
 PER FBC ACC 609.4
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE PLAN SHOWS 19 MIN OFF FINISHED FLOOR IT
 SHALL BE 15 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB
 BARS. PER FBC ACC 604.7
  
 6. THE REQUIRED TEMPERED WATER AT THE LAVATORY'S SHAL
 BE DELIVERED BY TEMPERATURE LIMITING DEVISE COMPILING
 WITH ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 PROVIDE
 NOTE ON PLAN.
  
 7. TRAP PRIMERS ARE REQUIRED ON FLOOR DRAIN SHOW ON
 PLAN. PER FBC PL 1002.4
  
 8. PROVIDE GREASE INTERCEPTOR CALCULATION FROM SCHIER.
 PER WPB AMEND TO FBC 107.2.1
  
 9. A TESTPORT IS REQUIRED ON OUTLET OF GREASE
 INTERCEPTOR IT SHALL BE A 4" MIN TWOWAY CLEAN OUT OR A
 PRE MANUFACTURED TEST PORT. PER WPB UTIL. DEPT. PROVIDE
 DETAIL PER MANUFACTURE INSTALLATION GUIDE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-02-20 Cont ID  
Sent By gjohnson Date 2019-02-20 Time 11:14 Rev Time 0.00
Received By gjohnson Date 2019-02-20 Time 11:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-29 Cont ID  
Sent By LL Date 2018-05-29 Time   Rev Time 0.00
Received By llouie Date 2018-05-29 Time   Sent To  
Notes
2018-05-29 10:56:45INTERIOR MODIFICATIONS ONLY. CAFE USE PERMITTED IN
 NMUD-TYPE I.
  
  
  
2018-05-04 07:49:44CHANGE OF OCCUPANCY