| 2018-01-29 08:07:29 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17121049 |
| | ADD: 1603 S. DIXIE HWY. |
| | CONT: MARION CONSTRUCTION INC. |
| | TEL: 561-324-3163 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 25/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: BUILDING PLAN REVIEW |
| | 1. CODE CYCLE THE PLANS WERE CREATED TOO. |
| | 2. OCCUPANCY GROUP |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 4) BUILDING FIRE SPRINKLERED OR NOT. |
| | |
| | 2A) SHEET A101 LIST THE 2010 FBC IN THE UPPER LEFT |
| | PORTION OF THE SHEET. THIS PLAN WAS SUBMITTED UNDER THE |
| | LAST DAY OF THE 2014 FBC-B. THE PLANS ARE SILENT AS TO |
| | THE 2014 EXISTING BUILDING CODE AND CHAPTERS THAT THE |
| | PLANS WERE DESIGNED UNDER, CHAPTER 11 ADDITIONS AND |
| | LEVEL III ALTERATIONS. |
| | |
| | 2B) THIS ALTERATION IS TO BE CONSIDERED A SUBSTANTIAL |
| | STRUCTURAL ALTERATION HAVING TO COMPLY WITH 907.4.2 OF |
| | THE EXISTING BUILDING CODE, SUBSTANTIAL STRUCTURAL |
| | ALTERATION. WHERE MORE THAN 30 PERCENT OF THE TOTAL |
| | FLOOR AND ROOF AREAS OF THE BUILDING OR STRUCTURE HAVE |
| | BEEN OR ARE PROPOSED TO BE INVOLVED IN STRUCTURAL |
| | ALTERATION WITHIN A FIVE-YEAR PERIOD, THE EVALUATION |
| | AND ANALYSIS SHALL DEMONSTRATE THAT THE ALTERED |
| | BUILDING OR STRUCTURE COMPLIES WITH THE FLORIDA |
| | BUILDING CODE, BUILDING FOR WIND LOADING AND WITH |
| | REDUCED IBC-LEVEL SEISMIC FORCES. THE AREAS TO BE |
| | COUNTED TOWARD THE 30 PERCENT SHALL BE THOSE AREAS |
| | TRIBUTARY TO THE VERTICAL LOAD-CARRYING COMPONENTS, |
| | SUCH AS JOISTS, BEAMS, COLUMNS, WALLS AND OTHER |
| | STRUCTURAL COMPONENTS THAT HAVE BEEN OR WILL BE |
| | REMOVED, ADDED OR ALTERED. |
| | |
| | 2C) PLEASE PROVIDE COMPLIANCE WITH 2014 EXISTING |
| | BUILDING CODE SECTION 907.4.1 EVALUATION AND ANALYSIS. |
| | AN ENGINEERING EVALUATION AND ANALYSIS THAT ESTABLISHES |
| | THE STRUCTURAL ADEQUACY OF THE ALTERED STRUCTURE SHALL |
| | BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE CODE OFFICIAL. |
| | |
| | 2D) SUBMITTED IS AN ENERGY FORM C402 AND HAND WRITTEN |
| | ON THE FORM HISTORIC BUILDING STATUS, EXEMPT UNDER THE |
| | FLORIDA ENERGY CONSERVATION CODE. PLEASE SEE ATTACHED |
| | LETTER FROM FRIEDERIKE MITTNER AS TO ENERGY |
| | REQUIREMENTS AND HOW TO BE MET. |
| | |
| | UNDER THE ENERGY CODE THIS IS CONSIDERED A RENOVATION. |
| | DEFINITION. RENOVATED BUILDING. A RESIDENTIAL OR |
| | NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT |
| | VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER |
| | HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, |
| | PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 |
| | PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. DER THE |
| | FLORIDA ENERGY CONSERVATION CODE. |
| | 2014 FBC-ENERGY CODE C401.2 APPLICATION. COMMERCIAL |
| | BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL |
| | COMPLY WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND |
| | C405.7. THE BUILDING ENERGY COST SHALL BE EQUAL TO OR |
| | LESS THAN 85 PERCENT OF THE STANDARD |
| | REFERENCE DESIGN BUILDING. |
| | C401.2.1 APPLICATION TO EXISTING BUILDINGS. ADDITIONS, |
| | ALTERATIONS AND REPAIRS TO EXISTING BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. SECTIONS C402, C403, C404 AND C405; OR |
| | 2. ANSI/ASHRAE/IESNA 90.1. |
| | |
| | 3) DISCREPANCY IN PLANS, SHEET A000 IS USING NGVD |
| | ELEVATION OF 16.91, SHEET C-1 IS USING NAVD ELEV. OF |
| | 15.40 AND SHEET S100 IS USING NGVD AND ELEV. 16.91 |
| | FEET. THE CITY ADOPTED THE NEW FLOOD MAPS OCT. 05/2017 |
| | AND AT THE SAME TIME CHANGING THE MEASURING STANDARD |
| | FOR ELEVATION TO NAVD88. NEW JOBS THAT ARE STARTED |
| | AFTER THAT DATE SHOULD BE USING THE NAVD STANDARD ON |
| | ALL PLANS. ONE PROJECT CAME IN WITH BOTH STANDARDS AND |
| | WAS STARTED 18 INCHES TO LOW!!! |
| | |
| | 4) SHEET C1 SHOWS A 1250 GALLON GREASE TRAP WITHIN 1-0 |
| | FOOT OF THE PROPOSED COURTYARD CANOPY. SCHEDULING AND |
| | BUILDING SEQUENCE WILL BE ESSENTIAL TO MAINTAINING |
| | SOLID GROUND BENEATH THE PROPOSED FOUNDATION. PLEASE |
| | SEE THE REQUIREMENTS FOR SETBACKS FOR POOLS FROM |
| | FOUNDATIONS. PLEASE PROVIDE ON THE PLANS SEQUENCE OF |
| | SCHEDULING FOR COMPLIANCE. |
| | FBC-B 1804.1 EXCAVATION NEAR FOUNDATIONS. EXCAVATION |
| | FOR ANY PURPOSE SHALL NOT REMOVE LATERAL SUPPORT FROM |
| | ANY FOUNDATION WITHOUT FIRST UNDERPINNING OR PROTECTING |
| | THE FOUNDATION AGAINST SETTLEMENT OR LATERAL |
| | TRANSLATION. |
| | FBC-B 1808.7.3 POOLS. THE SETBACK BETWEEN POOLS |
| | REGULATED BY THIS CODE AND SLOPES SHALL BE EQUAL TO |
| | ONE-HALF THE BUILDING FOOTING SETBACK DISTANCE REQUIRED |
| | BY THIS SECTION. THAT PORTION OF THE POOL WALL WITHIN A |
| | HORIZONTAL DISTANCE OF 7 FEET (2134 MM) FROM THE TOP OF |
| | THE SLOPE SHALL BE CAPABLE OF SUPPORTING THE WATER IN |
| | THE POOL WITHOUT SOIL SUPPORT. |
| | |
| | 5) SHEET S100 NOTE # 1 INDICATES WELL COMPACTED TERMITE |
| | TREATED CLEAN SAND FILL. SHEET S200 HAS NOTES FOR 10 |
| | MIL VAPOR BARRIER OVER WELL COMPACTED FILL. THE PLANS |
| | DO NOT GIVE A MINIMUM SAFE BEARING VALUE FOR THE FILL. |
| | PLEASE COMPLY WITH: |
| | FBC-B 1804.5 COMPACTED FILL MATERIAL. WHERE SHALLOW |
| | FOUNDATIONS WILL BEAR ON COMPACTED FILL MATERIAL, THE |
| | COMPACTED FILL SHALL COMPLY WITH THE PROVISIONS OF AN |
| | APPROVED GEOTECHNICAL REPORT, AS SET FORTH IN SECTION |
| | 1803. |
| | |
| | 6) SHEET S100 CUT SECTIONS AND S200 SHOW NEW STEEL |
| | COLUMNS, STEEL BEAMS, BAR JOIST, AND METAL B DECK. |
| | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 7) PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 9A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | |
| | 9B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10) ROOFING/ FLAT ROOFS: FOR ALL ROOFING PRODUCTS |
| | PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| | ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| | PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| | ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL |
| | BE INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| | CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 11A) LATERAL FORCE-RESISTING SYSTEM FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | |
| | 11B) FOR ROOF TOP A/C STAND PRODUCT APPROVAL A |
| | MIAMI-DADE OR FLORIDA PRODUCT APPROVAL IS TO BE |
| | SUBMITTED, REVIEWED BY THE DESIGNER OF RECORD. PLEASE |
| | IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE |
| | AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS, |
| | CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE |
| | STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN |
| | PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES |
| | MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE |
| | ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 12) SHEET S304 THE WIND DESIGN PRESSURES FOR COMPONENTS |
| | AND CLADDING ARE IN VASD ARE GOOD IN ROOF ZONES 1, 2, |
| | AND 3 AND WALL ZONE 4. THE NEGATIVE PRESSURES FOR WALL |
| | ZONE 5 APPEAR TO BE 3 LBS. LESS CONSISTENTLY FOR ALL |
| | SQUARE FEET IN AREA THAN OUR CHARTS, 2014 FBC-B TABLE |
| | 1609.6.2. |
| | |
| | 13) SHEET A401 IS A FLOOR PLAN WITH SEATING BUT DOES |
| | NOT SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY |
| | CODE; |
| | |
| | 13A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 13B) 226.2 DISPERSION. DINING SURFACES AND WORK |
| | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 13C) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 14)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 14)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 15) SIGNAGE 703. 703.1 SIGNS SHALL COMPLY WITH 703. |
| | WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE REQUIRED, |
| | EITHER ONE SIGN WITH BOTH VISUAL AND TACTILE |
| | CHARACTERS, OR TWO SEPARATE SIGNS, ONE WITH VISUAL, AND |
| | ONE WITH TACTILE CHARACTERS, SHALL BE PROVIDED. |
| | |
| | 15A) 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE |
| | FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS |
| | SHALL BE LOCATED 48 INCHES MINIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND SURFACE, MEASURED FROM THE BASELINE OF |
| | THE LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM |
| | THE BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| | |
| | 15B) SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH FLOOR OR |
| | GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 |
| | INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST |
| | TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| | |
| | 16) CLOSING. WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |