Plan Review Details - Permit 17120971
Plan Review Stops For Permit 17120971
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 17:40 Rev Time 0.00
Received By shill Date 2018-08-25 Time 17:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 14:32 Rev Time 0.00
Received By shill Date 2018-06-16 Time 14:31 Sent To  
Notes
2018-06-16 14:32:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. SEE PLUMBING REVIEW; ACCESSIBILITY COMMENTS ARE
 APPLICABLE FOR BUILDING REVIEW. PLEASE REVISE PLAN
 ACCORDINGLY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 08:39 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 08:22 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-02 Cont ID  
Sent By aclange Date 2018-03-02 Time 09:16 Rev Time 0.00
Received By aclange Date 2018-03-02 Time 07:54 Sent To  
Notes
2018-03-02 09:16:00****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5H EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 SECOND REVIEW:
  
 1. PRODUCT APPROVALS.
  
 A) TWO DIFFERENT PRODUCT APPROVALS WERE SUBMITTED FOR
 THE ONE OVERHEAD DOOR OPENING. NOTE, THE OPENING IS 15
 FT.. THE PRODUCT APPROVALS SUBMITTED ARE FOR A WIDTH OF
 12 FT 2 INCHES.
  
 B) A CASEMENT WINDOW PRODUCT APPROVAL WAS RECEIVED.
 PROVIDE ADDITIONAL PRODUCT APPROVALS FOR MULLIONS AND
 FIXED WINDOWS.
  
 C) PROVIDE PRODUCT APPROVAL FOR SINGLE ENTRY DOOR.
  
 D) ROOFING HAS BEEN REMOVED FROM THE SCOPE OF WORK PER
 ARCHITECTS REQUEST. FBC 107.1 SUBMITTAL DOCUMENTS
  
 2. PAGE S300 MISSING FROM ONE SET. FBC 107.1 SUBMITTAL
 DOCUMENTS
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By aclange Date 2018-01-02 Time 16:05 Rev Time 0.00
Received By aclange Date 2018-01-02 Time 14:57 Sent To  
Notes
2018-01-02 16:08:03****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
  
 1. PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING.
 EXTERIOR DOORS, OVERHEAD DOORS, WINDOWS AND ROOFING.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 ALTERNATIVELY YOU CAN LIST THESE ON THE COVER SHEET AND
 PROVIDE THEM LATER AS DEFERRED SUBMITTALS.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
  
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2. NOTE: ONE SET OF PLANS HAS TWO SETS OF S PAGES.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-08-14 Cont ID  
Sent By jpearson Date 2018-08-14 Time 09:52 Rev Time 0.00
Received By jpearson Date 2018-08-14 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-12 Cont ID  
Sent By ppetty Date 2018-06-12 Time 09:23 Rev Time 0.00
Received By ppetty Date 2018-06-12 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 07:53 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 07:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-11 Cont ID  
Sent By jpearson Date 2018-01-11 Time 11:33 Rev Time 0.00
Received By jpearson Date 2018-01-11 Time 11:33 Sent To  
Notes
2018-01-11 11:33:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A DISCREPANCY EXIST BETWEEN PANEL SCHEDULE AND
 ELECTRICAL PLAN IN REFERENCE TO THE FUSE SIZE OF
 DISCONNECT. THE PLAN STATES THAT THE FUSE IS 125 AMP
 AND THE PANEL SCHEDULE STATES THAT THE FUSE IS 150 AMP.
 PROVIDE RISER DIAGRAM SHOWING EXISTING WIRE AND FUSE
 SIZE TO HANDLE LOAD STATED IN PANEL SCHEDULE OF
 APPROXIMATELY 142 AMPS. NEC 215.2, 215.5, 240.4; FBC
 17.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-01 Cont ID  
Sent By pleduc Date 2018-06-01 Time   Rev Time 0.00
Received By pleduc Date 2018-05-31 Time 16:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 14:37 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 14:36 Sent To  
Notes
2018-01-22 14:37:36GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 17:40 Rev Time 0.00
Received By shill Date 2018-07-24 Time 15:05 Sent To  
Notes
2018-07-26 15:05:29C05

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 14:32 Rev Time 0.00
Received By shill Date 2018-05-25 Time 10:34 Sent To  
Notes
2018-05-30 10:34:23C05

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-02 Cont ID  
Sent By ccole Date 2018-04-02 Time 10:55 Rev Time 0.00
Received By ccole Date 2018-03-20 Time 15:51 Sent To  
Notes
2018-03-22 15:51:19RESUB ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 07:13 Rev Time 0.00
Received By gjohnson Date 2018-02-26 Time 15:05 Sent To  
Notes
2018-02-27 15:05:37C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-30 Cont ID  
Sent By cpuell Date 2018-01-30 Time 10:48 Rev Time 0.00
Received By cpuell Date 2017-12-27 Time 09:21 Sent To  
Notes
2017-12-28 09:22:50C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By shill Date 2018-11-15 Time 15:38 Rev Time 0.00
Received By shill Date 2018-11-15 Time 15:38 Sent To  
Notes
2018-11-15 15:39:24MU-2018-030532
 $1,565.28 PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 17:47 Rev Time 0.00
Received By shill Date 2018-08-25 Time 17:47 Sent To  
Notes
2018-08-25 17:47:41PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-06-07 Cont ID  
Sent By ccole Date 2018-06-07 Time 17:22 Rev Time 0.00
Received By ccole Date 2018-06-07 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-02 Cont ID  
Sent By ccole Date 2018-04-02 Time 10:41 Rev Time 0.00
Received By ccole Date 2018-04-02 Time 10:27 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By ccole Date 2018-03-08 Time 15:57 Rev Time 0.00
Received By ccole Date 2018-03-08 Time 15:56 Sent To  
Notes
2018-03-08 16:06:132ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120971
 3/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE ARCHITECTURAL PLANS TO SHOW THE REQUIRED
 WALL AND ROOF INSULATIONS THAT ARE SHOWN ON THE
 MECHANICAL PLANS AND IN THE ENERGY CALCULATIONS. THE
 ARCHITECT OF RECORD SHALL REVIEW THE ENERGYGAUGE
 COMPLIANCE SUBMITTAL, MAKE ANY REQUIRED CHANGES TO THE
 PLANS, AND CERTIFY THE PROJECT BY PROVIDING HIS/HER
 SIGNATURE ON PAGE 3 OF THE SUBMITTAL- SECTION
 C103.1.1.2 FBC-14
  
 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-11 Cont ID  
Sent By ccole Date 2018-01-11 Time 09:34 Rev Time 0.00
Received By ccole Date 2018-01-11 Time 09:05 Sent To  
Notes
2018-01-11 10:30:481ST REVIEW FBC-2014 BUILDING
 PERMIT #17120971
 1/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENGINEERING FOR INSTALLATION OF THE RTU IS
 INCOMPLETE:
  
 A) PROVIDE STRUCTURAL DETAILS FOR THE NEW ROOF OPENING.
  
 B) PROVIDE THE WIND LOAD DESIGN CRITERIA AS OUTLINED IN
 SECTION 1609 FBC-14 BUILDING.
  
 C) PROVIDE THE NOA FOR THE THYBAR CURB WITH SHOP
 DRAWING STAMP BY THE EOR.
  
 D) PROVIDE COMPLETE ATTACHMENT DETAILS- CURB TO ROOF,
 RTU TO CURB.
  
 2) CLARIFY HOW ACCESS TO THE NEW RTU WILL BE PROVIDED.
 WHAT IS THE HEIGHT OF THE ROOF SURFACE FROM GRADE- SEE
 SECTION 306.5.
  
 3) PLEASE CLARIFY WHY AIR CONDITIONING IS BEING
 PROVIDED FOR A WAREHOUSE. IDENTIFY WHAT PURPOSE THE
 SPACE WILL SEVE AND WHAT MATERIALS WILL BE STORED
 THERE.
  
 4) ENERGYGAUGE COMPLIANCE FORM AND INPUT DATA REPORT:
  
 A) NO DATA PROVIDED FOR THE OVERHEAD DOORS.
  
 B) NO DATA PROVIDED FOR THE NORTH AND WEST WALLS
 ENCLOSING THE 3100 SF WAREHOUSE BUILDING.
  
 C) SHOW ON THE PLANS WHERE ALL THE INSULATIONS THAT ARE
 LISTED ON PAGE 5 OF THE INPUT DATA REPORT ARE TO BE
 INSTALLED OR ARE EXISTING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-08-23 Cont ID  
Sent By gjohnson Date 2018-08-23 Time 17:43 Rev Time 0.00
Received By gjohnson Date 2018-08-23 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-06-15 Cont ID  
Sent By gjohnson Date 2018-06-15 Time 12:54 Rev Time 0.00
Received By gjohnson Date 2018-06-15 Time 10:49 Sent To  
Notes
2018-06-15 14:44:343RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A8.1 DETAIL #1 FOR THE ACCESSIBLE BATHROOMS THE
 CLEAR FLOOR SPACE FOR THE TOILET SHALL EXTEND FROM THE
 SIDE WALL OF THE TOILET 60" ACROSS TO THE LAVATORY IT
 APPEARS ON THE DETAIL THAT THE CLEAR FLOOR SPACE IS
 TURNED 180* AND THERE IS ONLY 56" WHERE THERE SHOULD BE
 60" AND 60" WHERE THERE SHOULD BE 56" PLEASE CLARIFY
 PER FBC ACC 604.3.1 SIZE. CLEARANCE AROUND A WATER
 CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 2. SHT. A8.1 DETAIL #1 PLEASE SHOW THE 30" X 48" CLEAR
 FLOOR SPACE FOR THE LAVATORY. PER FBC ACC 606.2 CLEAR
 FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3. THE DOOR SHALL NOT SWING INTO THE BATHROOM UNLESS A
 30"X48" CLEAR FLOOR SPACE CLEAR OF THE ARC OF THE DOOR.
 PER FBC ACC 603.2.3
  
 4. SHOW COMPLIANCE FOR FBC ACC 604.7 DISPENSERS. TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR
  
 5. THE MIRROR SHALL BE 40" TO THE REFLECTIVE SURFACE
 NOT TO THE FRAME. PER FBC ACC 603.3
  
 6.SHT. A8.1 PLEASE REVISE DETAIL TO SHOW COMPLIANCE
 WITH FBC ACC 604.5.2 REAR WALL. THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE.
  
 7. THE TOILET IN THE BACK OF THE WARE HOUSE AND THE ONE
 NEXT TO THE BREAK BOTH APPEAR TO HAVE BEEN ENLARGED IF
 SO THEY BOTH SHALL COMPLY WITH FBC ACC 213, 603, 604,
 606
  
 8. THE SINKS IN THE BREAK ROOM AND NEXT TO STORAGE
 ROOMS 102- 103 SHALL COMPLY WITH FBC ACC 603.2, 606.3
  
 9. PROVIDE GPM FOR THE 3" ROOF DRAIN RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 10. IF THE HOT WATER RUN FROM THE WATER HEATER #1 TO
 BATHROOM 107 IS OVER 50' A RECIRCULATION SYSTEM WILL BE
 REQUIRED IT LOOKS CLOSE IT WILL BE MEASURED IN THE
 FIELD. PER FBC PL 607.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 07:05 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 07:05 Sent To  
Notes
2018-03-17 07:09:27NO PLUMBING WORK UNDER THIS SCOPE OF WORK PER RESPONSE
 LETTER FROM ARCHITECT.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 14:37 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 14:37 Sent To  
Notes
2018-01-22 14:44:361ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DETAILED SCOPED OF PLUMBING WORK BEING DONE.
 PER WPB AMEND TO FBC 107.2.1
  
 2. IT APPEARS A BATHROOM IS BEING ELIMINATED PROVIDE A
 PLUMBING FIXTURE COUNT CALCULATION TO SHOW THE REQUIRED
 PLUMBING FIXTURES ARE PROVIDED FOR THE OCCUPANT LOAD.
 PER FBC PL 403.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 07:13 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 07:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-14 Cont ID  
Sent By llouie Date 2018-06-14 Time   Rev Time 0.00
Received By llouie Date 2018-06-14 Time 09:56 Sent To  
Notes
2018-06-14 15:32:11ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) THE VALUE OF CONSTRUCTION FOR THIS PERMIT
 ($775,000) EXCEEDS 50% OF THE VALUE OF THE EXISTING
 STRUCTURE ($576,995). THEREFORE, THE LANDSCAPING ON THE
 PROPERTY SHALL BE IMPROVED/UPGRADED ON THE PROPERTY TO
 MEET THE CURRENT LANDSCAPE REQUIREMENTS OF THE CITY AS
 BEST AS POSSIBLE. A LANDSCAPE PERMIT SHALL BE REQUIRED
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY.
  
 2.) AN EXPANSION OF THE USE TO THE BUILDING LOCATED AT
 424 PALM STREET WILL BE REQUIRED A UNITY OF TITLE/UNITY
 OF CONTROL. PLEASE CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR MORE INFORMATION @ (561) 494-1040.
  
 3.) SEPARATE PERMITS REQUIRED FOR: FENCE/WALL, PARKING
 AREA, LANDSCAPE AND IRRIGATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-01 Cont ID  
Sent By llouie Date 2018-03-01 Time   Rev Time 0.00
Received By llouie Date 2018-03-01 Time   Sent To  
Notes
2018-03-01 15:08:35ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) THE VALUE OF CONSTRUCTION FOR THIS PERMIT IS
 $225,000. ANY FURTHER IMPROVEMENTS TO THE BUILDING MAY
 TRIGGER THE 50% LANDSCAPE IMPROVEMENT REQUIREMENT.
 ASSESS IMPROVEMENT VALUE PER PAPA (2017) IS $576,995.
  
 2.) AN EXPANSION OF THE USE TO THE BUILDING LOCATED AT
 424 PALM STREET WILL REQUIRE A UNITY OF TITLE/UNITY OF
 CONTROL. PLEASE CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR MORE INFORMATION @ (561) 494-1040.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-29 Cont ID  
Sent By LL Date 2018-01-29 Time   Rev Time  
Received By llouie Date 2018-01-24 Time   Sent To  
Notes
2018-01-29 17:33:46** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ELEVATIONS INCORRECT. PLEASE ADDRESS.
  
 2.) EAST ELEVATION ON SHEET A3.1 SEEMS TO BE THE SOUTH
 ELEVATION. PLEASE ADDRESS.
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * PROPOSED USE: RETAIL BUSINESS AND WAREHOUSING HAVING
 MODERATE EXTERNAL IMPACTS.
  
 * THE VALUE OF CONSTRUCTION FOR THIS PERMIT IS
 $225,000. ANY FURTHER IMPROVEMENTS TO THE BUILDING MAY
 TRIGGER THE 50% LANDSCAPE IMPROVEMENT REQUIREMENT.
 ASSESSED IMPROVEMENT VALUE PER PAPA (2017) IS $576,995.
  
 * AN EXPANSION OF THE USE TO THE BUILDING LOCATED AT
 424 PALM STREET WILL REQUIRE A UNITY OF TITLE/UNITY OF
 CONTROL. PLEASE CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR MORE INFORMATION @ (561) 494-1040.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  