Plan Review Details - Permit 17120961
Plan Review Stops For Permit 17120961
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By shill Date 2018-07-03 Time 09:42 Rev Time 0.00
Received By shill Date 2018-07-03 Time 09:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By jgomez Date 2018-01-10 Time 18:29 Rev Time 0.00
Received By jgomez Date 2018-01-10 Time 09:41 Sent To  
Notes
2018-01-10 13:24:31RESIDENTIAL (R3) CHANGE OF OCCUPANCY FROM CARPORT TO
 LIVABLE AREA, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE EGRESS WINDOW "B" DOESN'T COMPLY WITH THE
 MINIMUM CLEAR HEIGHT AND TOTAL CLEAR OPENING AS
 REQUIRED BY SEC. R310.1.2 AND R310.1.1 FBC-RESIDENTIAL,
 5TH EDITION (2014). REVISE SIZE OF WINDOW AS REQUIRED
 OR PROVIDE MANUFACTURER'S SPECIFICATIONS SHOWING THAT
 THE PROPOSED SIZE WILL COMPLY WITH ALL THE EGRESS
 REQUIREMENTS. NOTE: NORMAL WINDOW OPERATION IS REQUIRED
 TO ACHIEVE THE EGRESS REQUIREMENTS. ADDITIONAL STEPS OR
 KNOWLEDGE TO OPERATE THE WINDOW IS NOT ALLOWED.
  
 3- CEILING INSULATION R-VALUE SPECIFIED ON THE TYPICAL
 WALL SECTION "A" ON SHEET A-1 DOESN'T MATCH R-VALUE
 REQUIRED ON THE ENERGY CALCULATIONS SUBMITTED. REVISE
 AS REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 4- SHEET SP-1: THE NOTE BELOW THE SCOPE OF WORK STATES
 THAT THE LEVEL OF ALTERATION SHALL COMPLY WITH SEC. 404
 AND ALTERATION LEVEL 2 OF THE EXISTING BUILDING CODE.
 THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. THIS IS A
 PARTIAL CHANGE OF CHANGE OF OCCUPANCY FROM GROUP U TO
 GROUP R. REVISE NOTE AS REQUIRED. SEC. 506 FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
  
 5- SHEET A-4: REVISE THE STRUCTURAL NOTE #1. THE
 BUILDING CODE IN EFFECT AT THE TIME OF THIS PERMIT
 APPLICATION IS THE FBC 5TH EDITION (2014) NOT 2010. AND
 THE ACI 318 AND ACI 530 REFERENCED EDITION IS THE 11
 EDITION NOT THE 08 EDITION. REVISE AS REQUIRED. SEE
 CHAPTER 46 FC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 6- PROVIDE CURRENT FLORIDA PRODUCT APPROVAL FOR THE
 SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. ICC
 EVALUATION REPORT ESR-2613 SUBMITTED EXPIRED ON
 06/2016. PROVIDE CURRENT FLORIDA PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001.
  
 NOTE:
 FOR INFORMATION PURPOSES ONLY. COPY OF THE SURVEY
 SUBMITTED STATES THAT THIS PROPERTY IS LOCATED IN FLOOD
 ZONE "C". THIS IS INCORRECT. THIS PROPERTY WAS
 CONSIDERED AS FLOOD ZONE "B" BEFORE THE NEW FLOOD MAPS
 WENT INTO EFFECT. AFTER THE NEW FLOOD MAPS WENT INTO
 EFFECT ON 10/05/17 THIS BUILDING IS LOCATED BETWEEN 2
 DIFFERENT FLOOD ZONES: X500 AND AE. THEREFORE, TAKE
 THIS INTO CONSIDERATION FOR FUTURE WORK.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-26 Cont ID  
Sent By ppetty Date 2018-06-26 Time 11:41 Rev Time 0.00
Received By ppetty Date 2018-06-26 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By jpearson Date 2018-01-18 Time 09:25 Rev Time 0.00
Received By jpearson Date 2018-01-18 Time 09:25 Sent To I
Notes
2018-01-18 09:25:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. FORMAT SHOULD BE AS DETAILED IN FBC RESIDENTIAL.
 NEC 220; FBC RE3602.3
 2. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE FOR ENTIRE DWELLING. SHOW ON
 PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING OR NOT
 TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC
 107.2.1
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2018-07-31 Cont ID  
Sent By jgomez Date 2018-07-31 Time 16:05 Rev Time 0.00
Received By jgomez Date 2018-07-30 Time 11:28 Sent To  
Notes
2018-07-31 16:05:58NO FEES. MU-2018-26603.
2018-07-31 11:29:04IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-03 Cont ID  
Sent By shill Date 2018-07-03 Time 09:42 Rev Time 0.00
Received By shill Date 2018-05-30 Time 15:41 Sent To  
Notes
2018-05-31 15:41:10R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-01-18 Time   Rev Time 0.00
Received By cpuell Date 2017-12-27 Time 09:09 Sent To  
Notes
2017-12-28 09:09:59R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-07-31 Cont ID  
Sent By jgomez Date 2018-07-31 Time 16:06 Rev Time 0.00
Received By jgomez Date 2018-07-31 Time 15:45 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-10 Cont ID  
Sent By jgomez Date 2018-01-10 Time 18:33 Rev Time 0.00
Received By jgomez Date 2018-01-10 Time 18:33 Sent To  
Notes
2018-01-10 18:34:081- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-01-05 Cont ID  
Sent By cmontell Date 2018-01-05 Time 14:48 Rev Time 0.00
Received By cmontell Date 2018-01-05 Time 14:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-01-10 Cont ID  
Sent By jgomez Date 2018-01-10 Time 14:08 Rev Time 0.00
Received By jgomez Date 2018-01-10 Time 13:59 Sent To  
Notes
2018-01-10 14:08:43NO PLUMBING WORK SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-11 Cont ID  
Sent By awooten Date 2018-06-11 Time   Rev Time 0.00
Received By awooten Date 2018-06-11 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By AW Date 2018-01-09 Time   Rev Time  
Received By   Date 2018-01-09 Time   Sent To  
Notes
***NONE***