Plan Review Details - Permit 17120924
Plan Review Stops For Permit 17120924
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-30 Cont ID  
Sent By aclange Date 2018-01-30 Time 10:59 Rev Time 0.00
Received By aclange Date 2018-01-30 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By aclange Date 2017-12-29 Time 09:00 Rev Time 0.00
Received By aclange Date 2017-12-29 Time 08:57 Sent To  
Notes
2017-12-29 09:00:01****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. THE NEW WALL CONTAINING THE BATHROOM DOOR BECOMES
 PART OF THE RATED CORRIDOR.
 PROVIDE CORRIDOR RATING. INCLUDE WALL RATING AND UL
 LISTING AS WELL AS THE DOOR RATING AND HARDWARE USED.
  
 FBC 716.5 TABLE OPENING FIRE PROTECTION ASSEMBLIES,
 RATINGS AND MARKINGS
  
 FBC 716.5.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN
 CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 716.5
 SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C
 WITHOUT THE HOSE STREAM TEST.
  
 2. DUCT PENETRATION THROUGH RATED WALL. SHOW HOW THIS
 WILL BE IN COMPLIANCE WITH FBC 717 DUCTS AND TRANSFER
 OPENINGS.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-30 Cont ID  
Sent By jpearson Date 2018-01-30 Time 08:01 Rev Time 0.00
Received By jpearson Date 2018-01-30 Time 08:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By jpearson Date 2018-01-05 Time 07:24 Rev Time 0.00
Received By jpearson Date 2018-01-05 Time 06:32 Sent To  
Notes
2018-01-05 07:24:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 2. PROVIDE LOAD CALCULATION FOR PANEL TO CONFIRM IT IS
 SIZED ADEQUATELY TO HANDLE THE ADDITIONAL LOAD. NEC
 215.2, 220.40
 3. IS THERE ANY FIRE ALARM WORK FOR THIS BATHROOM? IF
 SO, PROVIDE BLOCK NOTE THAT THE REQUIRED SEPARATE
 PERMIT AND PLAN SUBMITTALS WILL BE PROVIDED. FBC
 107.2.1, 105.1
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC 405.2.2,
 405.2.2.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-26 Cont ID  
Sent By pleduc Date 2018-01-26 Time   Rev Time 0.00
Received By pleduc Date 2018-01-26 Time 14:37 Sent To  
Notes
2018-01-26 16:15:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INDICATIONS OF VERIFYING FIRE SPRINKLER
 PROTECTION IN THE NEWLY CREATED BATHROOM; HOWEVER,
 THERE IS NO INDICATIONS OF VERIFYING FIRE SPRINKLER
 PROTECTION IN THE VACANT TENANT SPACE.
  
 THIS SPACE SHALL BE CHECKED FOR CODE COMPLIANT FIRE
 SPRINKLER PROTECTION AND CORRECTED IF FOUND
 NON-COMPLIANT.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-31 Cont ID  
Sent By thunt Date 2018-01-31 Time 15:54 Rev Time 0.00
Received By thunt Date 2018-01-24 Time 13:46 Sent To  
Notes
2018-01-25 13:46:41B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-17 Cont ID  
Sent By thunt Date 2018-01-17 Time 06:12 Rev Time 0.00
Received By thunt Date 2017-12-27 Time 13:41 Sent To  
Notes
2018-01-03 11:36:04B09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-29 Cont ID  
Sent By ccole Date 2018-01-29 Time 15:57 Rev Time 0.00
Received By ccole Date 2018-01-29 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-03 Cont ID  
Sent By ccole Date 2018-01-03 Time 08:35 Rev Time 0.00
Received By ccole Date 2018-01-03 Time 08:35 Sent To  
Notes
2018-01-03 09:02:251ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120924
 1/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DUCTS PENETRATIONS THROUGH THE FIRE-RATED
 CORRIDOR WALL MAY HAVE TO BE PROTECTED WITH EITHER FIRE
 OR SMOKE DAMPERS HOWEVER ADDITIONAL INFORMATION
 REGARDING THE CORRIDOR WALL NEEDS TO BE ON THE PLAN.
 INDICATE THE HOURLY FIRE-RATING OF THE CORRIDOR WALL ON
 THE PLAN AND CLARIFY IF IT IS A FIRE BARRIER OR A FIRE
 PARTITION. PLEASE REFER TO SECTIONS 607.5.2, 607.5.3,
 AND 607.5.4 AND PROVIDE
  
 THE REQUIRED DAMPERS OR INDICATE HOW THE PENETRATIONS
 ARE MEETING THE EXCEPTIONS LISTED UNDER THE ABOVE
 SECTIONS. PLEASE INDICATE THE TYPE AND SIZE OF THE DUCT
 PENETRATING THE LADIES BATHROOM/CORRIDOR WALL.
  
 2) REFER TO SECTION 607.7 WHICH PROHIBITS FLEX DUCTS
 FROM PASSING THROUGH ANY FIRE-RESISTANCE-RATED
 ASSEMBLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-31 Cont ID  
Sent By thunt Date 2018-01-31 Time 15:54 Rev Time 0.00
Received By thunt Date 2018-01-31 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By thunt Date 2018-01-17 Time 06:10 Rev Time 0.00
Received By thunt Date 2018-01-16 Time 15:32 Sent To I
Notes
2018-01-17 06:12:0001/17/2018 PLUMBING 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1) PLUMBING SANITARY ISOMETRIC DRAWING SHOWS THE WET
 VENT FOR THE LAV FITTING FACING THE WRONG WAY. FBC-P
 706.3
  
 2) SHOW CLEAR FLOOR SPACES FOR FIXTURES AS REQUIRED.
 FBC-A 604.3
  
 3) P-1 SHOW GRAB BARS 33?-36? BUT NOT TO THE TOP OF THE
 GRIPPING SURFACE AS REQUIRED. FBC-A 609.4
  
 4) YOUR OVERALL DIMENSION OF THE ROOM (6?) DOES NOT
 ALLOW FOR THE REQUIRED CLEAR FLOOR SPACE. MIN FINISHED
 OPENING WOULD BE 7? 1? TO COMPLY WITH FBC-A 604.8 USING
 MIN REQUIREMENTS FOR FIXTURE SIZES.
  
 5)TOILET PAPER DISPENSERS SHALL BE INSTALLED 7?-9? FROM
 THE FRONT LIP OF THE TOILET. FBC-A 604.7
  
 6) YOU MIRROR MOUNTED @ 40? WOULD NOT COMPLY AS IT HAS
 A STEEL FRAME. PER 603.3 THE MIRROR SHALL BE MOUNTED A
 MAX 40? ABOVE A LAVATORY TO THE REFLECTIVE SURFACE.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  