| Plan Review Stops For Permit 17120924 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-01-30 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-01-30 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-01-30 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-29 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-12-29 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-12-29 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2017-12-29 09:00:01 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1. THE NEW WALL CONTAINING THE BATHROOM DOOR BECOMES | | | PART OF THE RATED CORRIDOR. | | | PROVIDE CORRIDOR RATING. INCLUDE WALL RATING AND UL | | | LISTING AS WELL AS THE DOOR RATING AND HARDWARE USED. | | | | | | FBC 716.5 TABLE OPENING FIRE PROTECTION ASSEMBLIES, | | | RATINGS AND MARKINGS | | | | | | FBC 716.5.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE | | | BARRIERS. | | | FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE | | | PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN | | | CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A | | | FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 716.5 | | | SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C | | | WITHOUT THE HOSE STREAM TEST. | | | | | | 2. DUCT PENETRATION THROUGH RATED WALL. SHOW HOW THIS | | | WILL BE IN COMPLIANCE WITH FBC 717 DUCTS AND TRANSFER | | | OPENINGS. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-01-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-30 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-30 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-05 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-05 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2018-01-05 07:24:36 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 | | | 2. PROVIDE LOAD CALCULATION FOR PANEL TO CONFIRM IT IS | | | SIZED ADEQUATELY TO HANDLE THE ADDITIONAL LOAD. NEC | | | 215.2, 220.40 | | | 3. IS THERE ANY FIRE ALARM WORK FOR THIS BATHROOM? IF | | | SO, PROVIDE BLOCK NOTE THAT THE REQUIRED SEPARATE | | | PERMIT AND PLAN SUBMITTALS WILL BE PROVIDED. FBC | | | 107.2.1, 105.1 | | | 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. FBC EC 405.2.2, | | | 405.2.2.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-01-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-01-26 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2018-01-26 16:15:14 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS INDICATIONS OF VERIFYING FIRE SPRINKLER | | | PROTECTION IN THE NEWLY CREATED BATHROOM; HOWEVER, | | | THERE IS NO INDICATIONS OF VERIFYING FIRE SPRINKLER | | | PROTECTION IN THE VACANT TENANT SPACE. | | | | | | THIS SPACE SHALL BE CHECKED FOR CODE COMPLIANT FIRE | | | SPRINKLER PROTECTION AND CORRECTED IF FOUND | | | NON-COMPLIANT. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-31 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-24 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-17 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-17 |
Time |
06:12 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-12-27 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-01-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-29 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-29 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-03 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-03 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2018-01-03 09:02:25 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120924 | | | 1/3/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DUCTS PENETRATIONS THROUGH THE FIRE-RATED | | | CORRIDOR WALL MAY HAVE TO BE PROTECTED WITH EITHER FIRE | | | OR SMOKE DAMPERS HOWEVER ADDITIONAL INFORMATION | | | REGARDING THE CORRIDOR WALL NEEDS TO BE ON THE PLAN. | | | INDICATE THE HOURLY FIRE-RATING OF THE CORRIDOR WALL ON | | | THE PLAN AND CLARIFY IF IT IS A FIRE BARRIER OR A FIRE | | | PARTITION. PLEASE REFER TO SECTIONS 607.5.2, 607.5.3, | | | AND 607.5.4 AND PROVIDE | | | | | | THE REQUIRED DAMPERS OR INDICATE HOW THE PENETRATIONS | | | ARE MEETING THE EXCEPTIONS LISTED UNDER THE ABOVE | | | SECTIONS. PLEASE INDICATE THE TYPE AND SIZE OF THE DUCT | | | PENETRATING THE LADIES BATHROOM/CORRIDOR WALL. | | | | | | 2) REFER TO SECTION 607.7 WHICH PROHIBITS FLEX DUCTS | | | FROM PASSING THROUGH ANY FIRE-RESISTANCE-RATED | | | ASSEMBLY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-31 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-31 |
Time |
15:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-17 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-17 |
Time |
06:10 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-16 |
Time |
15:32 |
Sent To |
I |
|
| Notes |
| 2018-01-17 06:12:00 | 01/17/2018 PLUMBING 1ST REVIEW**DENIED** | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | 1) PLUMBING SANITARY ISOMETRIC DRAWING SHOWS THE WET | | | VENT FOR THE LAV FITTING FACING THE WRONG WAY. FBC-P | | | 706.3 | | | | | | 2) SHOW CLEAR FLOOR SPACES FOR FIXTURES AS REQUIRED. | | | FBC-A 604.3 | | | | | | 3) P-1 SHOW GRAB BARS 33?-36? BUT NOT TO THE TOP OF THE | | | GRIPPING SURFACE AS REQUIRED. FBC-A 609.4 | | | | | | 4) YOUR OVERALL DIMENSION OF THE ROOM (6?) DOES NOT | | | ALLOW FOR THE REQUIRED CLEAR FLOOR SPACE. MIN FINISHED | | | OPENING WOULD BE 7? 1? TO COMPLY WITH FBC-A 604.8 USING | | | MIN REQUIREMENTS FOR FIXTURE SIZES. | | | | | | 5)TOILET PAPER DISPENSERS SHALL BE INSTALLED 7?-9? FROM | | | THE FRONT LIP OF THE TOILET. FBC-A 604.7 | | | | | | 6) YOU MIRROR MOUNTED @ 40? WOULD NOT COMPLY AS IT HAS | | | A STEEL FRAME. PER 603.3 THE MIRROR SHALL BE MOUNTED A | | | MAX 40? ABOVE A LAVATORY TO THE REFLECTIVE SURFACE. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|