Plan Review Details - Permit 17120913
Plan Review Stops For Permit 17120913
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-10 Cont ID  
Sent By lcrespo Date 2018-01-10 Time 14:59 Rev Time 0.00
Received By lcrespo Date 2018-01-10 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By tklarge Date 2017-12-28 Time 14:02 Rev Time 0.00
Received By tklarge Date 2017-12-28 Time 14:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-10 Cont ID  
Sent By lcrespo Date 2018-01-10 Time 14:59 Rev Time 0.00
Received By lcrespo Date 2018-01-10 Time 14:59 Sent To  
Notes
2018-01-10 15:00:221/10/18 APPROVED BY PLUMBING, EMAILED CUSTOMER AND
 PLACED IN SMALL "G" UP FRONT, LAC
2018-01-10 14:59:5701/10/18 APPROVED BY PLUMBING, SENT TO UTILITIES FOR
 REVIEW. LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By tklarge Date 2017-12-28 Time 14:02 Rev Time 0.00
Received By tklarge Date 2017-12-28 Time 14:02 Sent To  
Notes
2017-12-28 14:02:451) THE WILKINS 975 XL IS NOT A LEAD FREE DEVICE. THE
 975 XL 2 IS LEAD FREE. SUBMIT TWO COPIES OF THE
 SPECIFICATIONS SHOWING THAT THE DEVICE TO BE INSTALLED
 IS LEAD FREE.
 2) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
 3) ALL BACKFLOW DEVICES MUST BE LEAD FREE PER THE CITY
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
 4) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  