Plan Review Details - Permit 17120895
Plan Review Stops For Permit 17120895
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-30 Cont ID  
Sent By jgomez Date 2018-04-30 Time 18:31 Rev Time 0.00
Received By jgomez Date 2018-04-30 Time 13:41 Sent To  
Notes
2018-04-30 13:44:35BUILDING REVIEW APPROVED WITH PROVISO:
 1- SUBMIT ALL DEFERRED SUBMITTAL ITEMS PRIOR TO
 INSTALLATION (EXTERIOR DOORS, WINDOWS, PANEL WALLS,
 STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS SYSTEMS,
 ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 EXHAUST FANS, EXTERIOR COOLER, FREEZERS &
 PRE-ENGINEERED A/C STANDS) APPROVED BY THE DESIGNER OF
 RECORD.
 2- WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS.
 2014 FBC-B 2204.1 WELDING. 201404.4.2 BOLTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-09 Cont ID  
Sent By aclange Date 2018-01-09 Time 10:49 Rev Time 0.00
Received By aclange Date 2018-01-08 Time 11:50 Sent To  
Notes
2018-01-09 10:49:08****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOOR, STOREFRONT SYSTEMS AND A/C ROOF STANDS
 SUBMITTALS.
  
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2. SELECT TYPE OF CONSTRUCTION. IT IS SHOWN AS IIIB
 UNSPRINKLERED ON PAGES A.0. ON PAGE LSP 1.0 IT IS SHOWN
 AS TYPE IIB UNSPRINKLERED.
 FBC 601 TYPES OF CONSTRUCTION
 FBC 602.1 GENERAL.
 BUILDINGS AND STRUCTURES ERECTED OR TO BE ERECTED,
 ALTERED OR EXTENDED IN HEIGHT OR AREA SHALL BE
 CLASSIFIED IN ONE OF THE FIVE CONSTRUCTION TYPES
 DEFINED IN SECTIONS 602.2 THROUGH 602.5. THE BUILDING
 ELEMENTS SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS
 THAN THAT SPECIFIED IN TABLE 601 AND EXTERIOR WALLS
 SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS THAN THAT
 SPECIFIED IN TABLE 602. WHERE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING BY TABLE 601, BUILDING ELEMENTS
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 703.2. THE PROTECTION OF OPENINGS, DUCTS AND AIR
 TRANSFER OPENINGS IN BUILDING ELEMENTS SHALL NOT BE
 REQUIRED UNLESS REQUIRED BY OTHER PROVISIONS OF THIS
 CODE.
  
 FBC 602.1.1 MINIMUM REQUIREMENTS.
 A BUILDING OR PORTION THEREOF SHALL NOT BE REQUIRED TO
 CONFORM TO THE DETAILS OF A TYPE OF CONSTRUCTION HIGHER
 THAN THAT TYPE WHICH MEETS THE MINIMUM REQUIREMENTS
 BASED ON OCCUPANCY EVEN THOUGH CERTAIN FEATURES OF SUCH
 A BUILDING ACTUALLY CONFORM TO A HIGHER TYPE OF
 CONSTRUCTION.
  
 3. ACCESSIBILITY. WOMAN?S RESTROOM DOOR. PROVIDE A
 MINIMUM OF 12? ON THE FRONT APPROACH AT THE LATCHED
 SIDE OF A DOOR WITH A CLOSURE. SEE PAGES A.1.0 AND
 A.1.1. NOTE. DETAIL PROVIDED AT 1/A 6.0 IS AT THE
 MINIMUM.
  
 FBC ACCESSIBILITY 404.2.4.1 DETAIL (C) SWINGING DOORS
 AND GATES.
  
 4. INTERIOR SPACE DIMENSIONS
  
 (A)SEE DISTANCE AROUND CART 006.
  
 (B) DISTANCE BETWEEN BUN RACK 027 AND SINK 060.
  
 FBC 1208.1 MINIMUM ROOM WIDTHS.
  
 KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN
 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES
 OR COUNTER FRONTS AND WALLS.
  
 5. PROVIDE A WPS (WELDING PROCEDURE SPEC). HAVE THIS ON
 SITE AT TIME OF INSPECTION.
  
 WELDED OR BOLTED CONNECTIONS
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE A (WPS) WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 6. BUILDING DEMOLITION.
  
 PROVIDE RELEASES FROM THE FOLLOWING UTILITIES:
  
 (A) FLORIDA POWER AND LIGHT (FPL) ELECTRIC, FLORIDA
 PUBLIC UTILITIES (GAS), WEST PALM BEACH UTILITIES AND
 WEST PALM BEACH HISTORIC PRESERVATIONS.
  
 (B) EXTERMINATION LETTER FROM A LICENSED PEST CONTROL
 COMPANY.
  
 (C) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 FBC 3303.1 CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS AND A SCHEDULE FOR DEMOLITION
 SHALL BE SUBMITTED WHERE REQUIRED BY THE BUILDING
 OFFICIAL. WHERE SUCH INFORMATION IS REQUIRED, NO WORK
 SHALL BE DONE UNTIL SUCH CONSTRUCTION DOCUMENTS OR
 SCHEDULE, OR BOTH, ARE APPROVED.
  
 FBC 3303.2 PEDESTRIAN PROTECTION.
 THE WORK OF DEMOLISHING ANY BUILDING SHALL NOT BE
 COMMENCED UNTIL PEDESTRIAN PROTECTION IS IN PLACE AS
 REQUIRED BY THIS CHAPTER.
  
 I HAVE INCLUDED THE DEMOLITION CHECKLIST ALONG WITH
 YOUR PERMIT APPLICATION. THIS FORM CAN BE DOWNLOADED ON
 OUR WEBSITE AS WELL.
  
 7. SEPARATE PERMITS REQUIRED FOR THE FOLLOWING.
  
 (A) PARKING LOT, LANDSCAPING, SIGNS, HOODS, TEMP
 FENCING, TEMP TRAILERS AND AWNINGS.
  
 (B) TRELLIS WORK WILL BE UNDER A SEPARATE PERMIT. A
 NOTE WAS FOUND ON A 1.3. SEE ALSO TRELLIS SHOWN ON SP
 1.3 REFERENCES A DETAIL ON A 1.3 THAT WAS NOT PROVIDED.
  
 (C) BEFORE SUBMITTING FOR A PARKING LOT PERMIT CHECK ON
 WEST PALM BEACH?S PARKING REQUIREMENTS REGARDING SIZES
 OF SPACING AND STRIPING DETAILS. MANY OF THE DETAILS
 SHOWN ON SP 1.0 ARE NOT COMPLIANT.
  
 8. ENERGY EFFICIENCY.
  
 PROVIDE ENERGY CALCULATIONS AND SHOW COMPLIANCE WITH
 FBC 1301.1.1 CRITERIA.
  
 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION, 103.1.1.1.2 COMMERCIAL AND
 MULTIPLE-FAMILY RESIDENTIAL.
 COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH
 THIS CODE FOR COMMERCIAL AND MULTIPLE-FAMILY
 RESIDENTIAL BUILDINGS SHALL BE IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 481.229, FLORIDA STATUTES, OR
 SECTION 471.003, FLORIDA STATUTES.
  
 9. IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 12:22 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 09:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-23 Cont ID  
Sent By jpearson Date 2018-01-23 Time 13:15 Rev Time 0.00
Received By jpearson Date 2018-01-23 Time 10:24 Sent To  
Notes
2018-01-23 13:15:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ESTIMATED AIC INFORMATION IS NOT ACCEPTABLE. PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 2. BASED ON THE CURRENT AIC CALCULATIONS, PANELS M AND
 B DO NOT MEET OR EXCEED THE RATING REQUIRED. WHEN
 ACCURATE CALCULATION IS COMPLETED, CONFIRM THAT ALL
 PANELS HAVE THE PROPER AIC RATING. NEC 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. CIRCUIT B-23,25 SHOWS #12 WIRE ON A 25 AMP BREAKER
 FOR THE COFFEE MAKER. THE OCP FOR #12 WIRE SHALL NOT
 EXCEED THE VALUES IN 240.4(D). PROVIDE CORRECTION. NEC
 240.4(D)
 5. BASED ON THE AREA DESIGNATED FOR "NO ELECTRICAL
 CONDUIT IN HOOD AREA" ON SHEET E-2, IT APPEARS THAT
 THERE IS ELECTRICAL OUTLETS UNDER THE HOOD THAT WILL
 NOT BE SHUT OFF DURING HOOD SHUTDOWN. I SEE A NOTE ON
 SHEET E-5 UNDER "HOOD VENTILATION SYSTEM" THAT CALLS
 FOR ALL CONTROLLED COOKING EQUIPMENT UNDER HOOD TO BE
 SHUT DOWN, BUT THIS SHOULD INCLUDE ALL ELECTRICAL UNDER
 HOOD. THIS APPEARS TO INCLUDE CIRCUITS M-2,4,6; B-4;
 B-18; B-20; B-37; AND B-41. PROVIDE CLARIFICATION
 AND/OR CORRECTIONS AS NEEDED. NFPA 96, SECTION 10.4.1,
 FBC 107.2.1
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 11:19 Rev Time 0.00
Received By shill Date 2018-04-21 Time 11:19 Sent To  
Notes
2018-04-21 11:20:55PLEASE ADVISE IF ALL OTHER REVIEWS HAVE PASSED.
 ENGINEERING REVIEW WILL BE DONE AFTER ALL OTHER REVIEWS
 HAVE PASSED.
 [email protected], 561-805-6724
  
  
  
 CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By squinone Date 2018-01-22 Time   Rev Time 0.00
Received By squinone Date 2018-01-22 Time   Sent To I
Notes
2018-01-22 10:49:561. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: HTTP
 ://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-
 PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-
 PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 3. MUST PROVIDE UTILITY CONFLICT TABLE (BOTTOM AND TOP
 OF CROSSING PIPES) AT THE CONFLICT POINTS OF ALL WATER,
 STORM AND SANITARY SEWER PIPES AS WELL AS OTHER
 FRANCHISE UTILITIES. EXISTING UTILITIES WITHIN THE
 PROPOSED SANITARY SEWER LATERAL ARE TO BE VERIFIED VIA
 SOFTDIGS, PROVIDE ALL UTILITY CROSSING INFORMATION;
  
 4. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE
 THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM
 BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT
 TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA
 TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 5. HOW WILL THE SITE/BUILDING BE SERVED FOR WATER,
 SEWER AND FIRE PROTECTION. SHOW ALL EXISTING UTILITIES
 WITHIN THE VICINITY OF THE PROPOSED SITE AS WELL AS
 PROPOSED UTILITIES TO SERVE THE DEVELOPMENT (LABEL SIZE
 AND MATERIAL OF ALL PIPES AND CONDUITS ETC.);
  
 6. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND
 SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND
 PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO
 VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS
 ON THE UTILITY PLAN SHEET AS WELL;
  
 7. PROVIDE DRAINAGE CALCULATIONS;
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-11 Cont ID  
Sent By pleduc Date 2018-04-11 Time   Rev Time 0.00
Received By pleduc Date 2018-04-10 Time 15:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-28 Cont ID  
Sent By pleduc Date 2017-12-28 Time   Rev Time 0.00
Received By pleduc Date 2017-12-28 Time 10:58 Sent To  
Notes
2017-12-28 11:31:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY CONSTRUCTION TRAILERS LOCATED WITHIN THE SITE
 BOUNDARIES SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND
 LOCATED PER NFPA 241.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE ENSURE PROPER PERMITING AND CODE COMPLAINCE.
  
  
  
 2) THERE ARE LIGHTWEIGHT ROOF TRUSS DESIGN INDICATED.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE ENSURE A SIGN IS INSTALLED FOR FINAL FIRE
 INSPECTION.
  
  
  
 3) A HOOD VENT SYSTEM AND FIRE SUPPRESSION SYSTEM IS
 INDICATED. THESE SYSTEM SHALL BE SUBMITTED UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 07:55 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 07:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By gjohnson Date 2018-01-26 Time 09:52 Rev Time 0.00
Received By gjohnson Date 2018-01-26 Time 09:52 Sent To  
Notes
2018-01-26 09:54:481ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-04 Cont ID  
Sent By cpuell Date 2018-05-04 Time 09:29 Rev Time 0.00
Received By cpuell Date 2018-04-04 Time 14:31 Sent To  
Notes
2018-04-05 14:31:18C01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-21 Cont ID  
Sent By cpuell Date 2018-02-21 Time 16:48 Rev Time 0.00
Received By cpuell Date 2017-12-22 Time 11:50 Sent To  
Notes
2018-02-21 15:42:00TO L MERCHANT.
2017-12-27 11:50:13C01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By jgomez Date 2018-04-30 Time 18:53 Rev Time 0.00
Received By jgomez Date 2018-04-30 Time 18:53 Sent To  
Notes
2018-04-30 18:54:111-BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By aclange Date 2018-01-08 Time 11:50 Rev Time 0.00
Received By aclange Date 2018-01-08 Time 11:50 Sent To  
Notes
2018-01-08 11:50:22****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-24 Cont ID  
Sent By ccole Date 2018-04-24 Time 16:09 Rev Time 0.00
Received By ccole Date 2018-04-24 Time 15:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By ccole Date 2018-01-18 Time 11:12 Rev Time 0.00
Received By ccole Date 2018-01-18 Time 11:12 Sent To  
Notes
2018-01-18 11:25:151ST REVIEW FBC-2014 MECHANICAL, FLORIDA ENERGY
 CONSERVATION CODES
 PERMIT #17120895
 1/18/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION
 AND SECTION 312.1 FBC-14 MECHANICAL.
  
 2) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION C101.2 FBC-14 ENERGY CONSERVATION.
  
 3) SHEET A-1.1: EQUIPMENT 0.32 & 040A ARE SHOWN ON THE
 PLAN BUT NOT IN THE SCHEDULE.
  
 4) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES- SECTION 304.
  
 5) M-1: THE 1028 SQ. FT. DINING AREA SHOWN IN THE
 VENTILATION TABLE DOES NOT MATCH THE 1551 SQ. FT. AREA
 SHOWN IN THE TABLE ON LSP-1.0- PLEASE CORRECT.
  
 6) M-1: PLEASE EMBOLDEN THE FAINTLY PRINTED NOTES AND
 RTU AND O/A LABELS SHOWN ON THE MECHANICAL PLAN-
 SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC.
  
 7) M-1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKES- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 8) M-2: PROVIDE THE WIND DESIGN CRITERIA FOR THE RTU
 AND CURB ATTACHMENT DETAILS- SECTION 1609 FBC-14
 BUILDING.
  
 9) SHOW THE CONDENSATE PIPING RUNS AND DISCHARGE
 LOCATIONS, AND PROVIDE PIPING AND SUPPORT DETAILS-
 SECTION 307.
  
 10) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOODS, THE FIRE SUPPRESSION SYSTEMS,
 AND THE WALK-IN COOLERS AND FREEZER. PLEASE NOTE THAT
 COMPLIANCE WITH SECTIONS 508.1.1 (MAKEUP AIR
 TEMPERATURE) AND 301.15 WIND RESISTANCE FOR ROOFTOP
 FANS WILL BE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 07:56 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 06:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By gjohnson Date 2018-01-26 Time 09:06 Rev Time 0.00
Received By gjohnson Date 2018-01-24 Time 13:02 Sent To  
Notes
2018-01-26 09:52:151ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A.0.1 AND A.0.2 PLEASE REMOVE DETAILS AND
 REQUIREMENTS THAT DO NOT APPLY TO THIS PROJECT. PER WPB
 AMEND TO FBC 107.2.1
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE MAIN BACKFLOW,
 GAS AND GREASE INTERCEPTOR IF A NEW ONE IS INSTALLED
 PLEASE PLACE NOTE ON THE PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 3. THE EXISTING GREASE INTERCEPTOR SHALL BE CERTIFIED
 BY WPB UTILITIES DEPT CONTACT JEFFERY ODOMS
 561-822-2172 OR [email protected]. PLEASE PLACE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 4. SHOW ON PLAN, THE MAIN BACKFLOW SHALL BE INSTALLED
 NEXT TO THE WATER METER. PER WPB CROSS CONNECTION
 MANUAL
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. MOST OF THESE ARE
 POINT OF USE.
 PER FBC PL 416.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-01-08 Cont ID  
Sent By aclange Date 2018-01-08 Time 15:23 Rev Time 0.00
Received By aclange Date 2018-01-08 Time 15:23 Sent To  
Notes
2018-01-08 15:24:31****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
  
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
  
 PROVIDE ROOFING PRODUCT APPROVALS AND SUPPORTING
 DOCUMENTS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED.
  
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By aaponte Date 2018-05-03 Time 16:12 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
2018-05-03 16:42:171. LANDSCAPE PERMIT NO. 16120301 SUBMITTED IN 2016
 NEEDS TO BE UPDATED TO REFLECT THE FINAL SITE PLAN
 APPROVAL CONDITIONS.
 2. PLEASE CORRECT PARKING STRIPING DETAIL TO COMPLY
 WITH CITY STANDARD (SEC 94-485(J)). SHEET SP-1.0 STILL
 INCLUDES THE WRONG STRIPING DETAIL.
 3. PLEASE CORRECT THE ZONING DESIGNATION INDICATED ON
 SHEET SP -1.0. THE ENTIRE PROPERTY IS ZONED BPD-5.
 4. SIGNS NOT INCLUDED UNDER THIS PERMIT. PLEASE SUBMIT
 A SEPARATE APPLICATION AND INDICATE SIGNS IN THIS
 PERMIT ONLY WITH A DASHED LINE. PLEASE NOTE THAT THE
 MAXIMUM SIGN ALLOWED IS A 36' IN VERTICAL DIMENSION BY
 60% OF THE STOREFRONT WIDTH.
 5. PLEASE PROVIDE INFORMATION TO CONFIRM ALL MECHANICAL
 EQUIPMENT ON ROOF WILL BE SCREEN BY PARAPET WALLS.
 EQUIPMENT NO. 7 INDICATED ON SHEET A-5.0 SEEMS TO
 PROJECT ABOVE THE PARAPET LINE. PLEASE VERIFY.
 6. SATISFIED - METAL CANOPY OVER THE WINDOW ON NORTH
 ELEVATION SHALL BE THE SAME SIZE OR LARGER THAN WINDOW
 OPENING.
 7. PLEASE CONFIRM ALL WINDOWS ARE LIGHT TINTED NOT
 REFLECTIVE, AND ALLOW THE VIEW OF THE INTERIOR FROM THE
 EXTERIOR.
 8. DECORATIVE TRELLIS SCREEN PANELS ALONG PALM BEACH
 LAKES BOULEVARD SHALL BE WOOD OR SIMILAR MATERIAL TO
 MAINTAIN THE APPROVED APPEARANCE, NOT ALUMINUM.SCREEN
 PANEL FRAME CAN BE ALUMINUM.
 9. A PEDESTRIAN CROSSING TO ACCESS THE TRELLIS AREA
 SHALL BE INCLUDED AT THE EXIT OF THE DRIVE TRU.
 10. HARDSCAPE DRAWINGS SHALL BE SUBMITTED INDICATING
 THE LOCATION OF DECORATIVE LIGHT FIXTURES REQUIRED
 ALONG THE PALM BECH LAKES AND DIXIE AVE FRONTAGE.
 FIXTURE AND POLE SHALL FOLLOW CITY STANDARDS. THIS CAN
 BE SUBMITTED AS A SEPARATE LIGHTING PERMIT. IF LIGHT
 POLES ALREADY EXIST, PLEASE INDICATE THEM IN THE SITE
 PLAN.
 11. PLEASE INDICATE THE LOCATION OF THE EXISTING BUS
 STOP ALONG DIXIE HWAY. A BENCH SHALL BE PROVIDED.
 12. LANDSCAPE DRAWING DOES NOT ACCURATELY REFLECT THE
 PROPOSED BIKE RACKS INDICATED IN THE SITE PLAN. SITE
 PLAN SHALL ACCURATELY REFLECT THE PROPOSED LANDSCAPE.
 13. PLEASE SUBMIT CIVIL DRAWING TO IDENTIFY ANY
 POSSIBLE CONFLICTS BETWEEN UTILITIES AND LANDSCAPE.
 14. PLEASE PROVIDE ADDITIONAL DETAILS FOR THE TRELLIS
 DESIGN. SEE COMMENT NO. 8.
 15. MINIMUM SIDEWALK WIDTH ALONG PALM BEACH LAKES
 BOULEVARD SHALL BE 6 FEET.
 16. REMOVED.
 17. PLEASE SUBMIT A SURVEY OF THE PROPERTY, INCLUDING
 ALL INFORMATION UP TO CENTER LINE OF ADJACENT ROW.
 18. BIKE RACK INCLUDED IN SHEET SP-1.1 IS NOT
 ACCEPTABLE. PLEASE USE ANY HITCH AND POST TYPE OF RACK.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-21 Cont ID  
Sent By AA Date 2018-02-21 Time 14:16 Rev Time 0.00
Received By aaponte Date 2018-02-13 Time 12:05 Sent To  
Notes
2018-02-21 15:41:341. PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT.
 2. PLEASE CORRECT PARKING STRIPING DETAIL TO COMPLY
 WITH CITY STANDARD (SEC 94-485(J))
 3. PLEASE CORRECT THE ZONING DESIGNATION INDICATED ON
 SHEET SP -1.0.
 4. SIGNS NOT INCLUDED UNDER THIS PERMIT. PLEASE SUBMIT
 A SEPARATE APPLICATION AND INDICATE SIGNS IN THIS
 PERMIT ONLY WITH A DASHED LINE.
 5. PLEASE PROVIDE INFORMATION TO CONFIRM ALL MECHANICAL
 EQUIPMENT ON ROOF WILL BE SCREEN BY PARAPET WALLS.
 EQUIPMENT NO. 7 INDICATED ON SHEET A-5.0 SEEMS TO
 PROJECT ABOVE THE PARAPET LINE. PLEASE VERIFY.
 6. METAL CANOPY OVER THE WINDOW ON NORTH ELEVATION
 SHALL BE THE SAME SIZE OR LARGER THAN WINDOW OPENING.
 7. PLEASE CONFIRM ALL WINDOWS ARE LIGHT TINTED NOT
 REFLECTIVE, AND ALLOW THE VIEW OF THE INTERIOR FROM THE
 EXTERIOR.
 8. DECORATIVE TRELLIS SCREEN PANELS ALONG PALM BEACH
 LAKES BOULEVARD SHALL BE WOOD OR SIMILAR MATERIAL TO
 MAINTAIN THE APPROVED APPEARANCE, NOT ALUMINUM.SCREEN
 PANEL FRAME CAN BE ALUMINUM.
 9. A PEDESTRIAN CROSSING TO ACCESS THE TRELLIS AREA
 SHALL BE INCLUDED AT THE EXIT OF THE DRIVE TRU.
 10. HARDSCAPE DRAWINGS SHALL BE SUBMITTED INDICATING
 THE LOCATION OF DECORATIVE LIGHT FIXTURES REQUIRED
 ALONG THE PALM BECH LAKES AND DIXIE AVE FRONTAGE.
 FIXTURE AND POLE SHALL FOLLOW CITY STANDARDS.
 11. PLEASE INDICATE THE LOCATION OF THE EXISTING BUS
 STOP ALONG DIXIE HWAY. A BENCH SHALL BE PROVIDED.
 12. LANDSCAPE DRAWING DOES NOT ACCURATELY REFLECT THE
 PROPOSED BIKE RACKS INDICATED IN THE SITE PLAN. SITE
 PLAN SHALL ACCURATELY REFLECT THE PROPOSED LANDSCAPE.
 13. PLEASE SUBMIT CIVIL DRAWING TO IDENTIFY ANY
 POSSIBLE CONFLICTS BETWEEN UTILITIES AND LANDSCAPE.
 14. PLEASE PROVIDE ADDITIONAL DETAILS FOR THE TRELLIS
 DESIGN.
 15. MINIMUM SIDEWALK WITH ALONG PALM BEACH LAKES
 BOULEVARD SHALL BE 6 FEET.
 16. THE CITY IS EXPLORIGN THE POSSIBLE ADDITION OF A
 BIKE LANE ALONG PALM BEACH LAKES BOULEVARD, THEREFORE
 SOME ADJUSTMENT TO THE PROPOSED STREETSCAPE ALONG PBL
 MAY BE NECESSARY. FURTHER DISCUSSION WITH STAFF NEEDED.
 17. PLEASE SUBMIT A SURVEY OF THE PROPERTY, INCLUDING
 ALL INFORMATION UP TO CENTER LINE OF ADJACENT ROW.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  