Plan Review Details - Permit 17120894
Plan Review Stops For Permit 17120894
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-12 Cont ID  
Sent By ccole Date 2018-01-12 Time 16:20 Rev Time 0.00
Received By ccole Date 2018-01-12 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-05 Time 09:57 Sent To  
Notes
2018-01-08 09:57:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-12-28 Time   Rev Time 0.00
Received By cpuell Date 2017-12-22 Time 11:24 Sent To  
Notes
2017-12-27 11:25:08MECH -$5000

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-12 Cont ID  
Sent By ccole Date 2018-01-12 Time 16:20 Rev Time 0.00
Received By ccole Date 2018-01-12 Time 16:20 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-10 Cont ID  
Sent By ccole Date 2018-01-10 Time 11:28 Rev Time 0.00
Received By ccole Date 2018-01-10 Time 11:28 Sent To I
Notes
2018-01-10 11:30:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120894
 1/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW WSS NOT ADDRESSED. I
 HAVE REPRINTED BELOW- PLEASE COMPLY.
  
 1) THE P100 PLAN IS UNACCEPTABLE FOR REVIEW: A) MINIMUM
 1/8" SCALE REQUIRED PER SECTION 107.2.1.4 WPB
 AMENDMENTS TO THE FBC. B) THE ARCHITECT WHO PREPARED
 THE PLAN SHALL PROVIDE HIS SIGNATURE AND SEAL ON THE
 PLAN- SECTION 61G15-16.003 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By ccole Date 2017-12-28 Time 12:21 Rev Time 0.00
Received By ccole Date 2017-12-28 Time 12:21 Sent To I
Notes
2017-12-28 12:27:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120894
 12/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE P100 PLAN IS UNACCEPTABLE FOR REVIEW: A) MINIMUM
 1/8" SCALE REQUIRED PER SECTION 107.2.1.4 WPB
 AMENDMENTS TO THE FBC. B) THE ARCHITECT WHO PREPARED
 THE PLAN SHALL PROVIDE HIS SIGNATURE AND SEAL ON THE
 PLAN- SECTION 61G15-16.003 FLORIDA ADMINISTRATIVE CODE.
  
 2) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION
 OF THE EXTERIOR CONDENSER PER SECTION 301.15 FBC-14
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  