Plan Review Details - Permit 17120894
| Plan Review Stops For Permit 17120894 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-01-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-12 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-12 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-01-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-01-05 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2018-01-08 09:57:27 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-12-22 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2017-12-27 11:25:08 | MECH -$5000 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-01-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-12 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-12 |
Time |
16:20 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-01-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-10 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-10 |
Time |
11:28 |
Sent To |
I |
|
| Notes |
| 2018-01-10 11:30:39 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120894 | | | 1/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW WSS NOT ADDRESSED. I | | | HAVE REPRINTED BELOW- PLEASE COMPLY. | | | | | | 1) THE P100 PLAN IS UNACCEPTABLE FOR REVIEW: A) MINIMUM | | | 1/8" SCALE REQUIRED PER SECTION 107.2.1.4 WPB | | | AMENDMENTS TO THE FBC. B) THE ARCHITECT WHO PREPARED | | | THE PLAN SHALL PROVIDE HIS SIGNATURE AND SEAL ON THE | | | PLAN- SECTION 61G15-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-28 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-28 |
Time |
12:21 |
Sent To |
I |
|
| Notes |
| 2017-12-28 12:27:37 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120894 | | | 12/28/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE P100 PLAN IS UNACCEPTABLE FOR REVIEW: A) MINIMUM | | | 1/8" SCALE REQUIRED PER SECTION 107.2.1.4 WPB | | | AMENDMENTS TO THE FBC. B) THE ARCHITECT WHO PREPARED | | | THE PLAN SHALL PROVIDE HIS SIGNATURE AND SEAL ON THE | | | PLAN- SECTION 61G15-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | | | 2) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION | | | OF THE EXTERIOR CONDENSER PER SECTION 301.15 FBC-14 | | | MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
|