| Plan Review Stops For Permit 17120888 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-11-02 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-11-02 |
Time |
17:46 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2018-10-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-01 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-01 |
Time |
16:08 |
Sent To |
I |
|
| Notes |
| 2018-10-01 16:33:37 | PLAN | | | REVIEW COMMENTS | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED | | | FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE | | | SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS | | | PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT | | | THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO | | | THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318 | | | LBS. WHICH IS LESS THAN THE LIGHTEST MODEL LISTED IN | | | THE TABLE ON THE DRAWINGS. THE LENGTH AND WIDTH | | | DIMENSIONS OF THE GENERATOR ARE SMALLER THAN THE ONES | | | THAT ARE LISTED AND IT IS TALLER. PLEASE SUBMIT | | | ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT | | | HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301. IF THERE | | | ARE NO PREFAB PADS FOR THIS GENERATOR, THEN YOU CAN | | | FORM AND POUR A CONCRETE PAD AT THE SITE. IF YOU WISH | | | TO DO THIS THEN SUBMIT TWO SETS OF DIMENSIONED PAD | | | DETAILS. SPECIFY THE ANCHOR TYPE, LOCATIONS, NUMBER AND | | | TYPE OF FASTENERS ON THE PLANS. THE ADDRESS OF THE | | | PROJECT, THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE | | | DRAWINGS. FBC 107.2.1 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-17 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-17 |
Time |
11:15 |
Sent To |
I |
|
| Notes |
| 2018-09-17 13:26:51 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED | | | FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE | | | SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS | | | PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT | | | THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO | | | THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318 | | | LBS. WHICH IS LESS THAN ONE HALF AS MUCH AS THE | | | LIGHTEST MODEL LISTED IN THE TABLE ON THE DRAWINGS. THE | | | LENGTH AND WIDTH DIMENSIONS OF THE GENERATOR ARE | | | SMALLER THAN THE ONES THAT ARE LISTED. PLEASE SUBMIT | | | ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT | | | HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-06-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:51 |
Sent To |
I |
|
| Notes |
| 2018-06-19 18:52:01 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEERING THAT WAS SUBMITTED FOR THE GENERATOR | | | PAD DOES NOT HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN | | | SIGNATURE AS REQUIRED BY FAC 61G-15-23.003. F.S. | | | 471.025 | | | | | | 2) THE PAD ENGINEERING THAT WAS SUBMITTED REFERENCES | | | THE 2010 FBC AND THIS PROJECT IS UNDER THE 2014 FBC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-05 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-05 |
Time |
17:39 |
Sent To |
Z |
|
| Notes |
| 2018-01-05 17:43:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED SLAB AND | | | ANCHORING DETAILS TO RESIST A 170 MPH VULT WIND SPEED | | | IN EXPOSURE C. FBC-R301.2.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-05-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-29 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-29 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-01-05 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-01-05 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2018-01-05 08:46:32 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | ONLY ON SET OF PLANS SUBMITTED FOR REVIEW. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
7 |
Status |
P |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-05 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-02-05 |
Time |
06:10 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
F |
Date |
2019-01-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-01-28 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-01-28 |
Time |
05:40 |
Sent To |
I |
|
| Notes |
| 2019-01-28 09:10:18 | 1) WHAT STANDARD ARE THE GAS SIZING TABLES FROM? THERE | | | IS NO REFERENCE ON THESE TABLES TO DETERMINE IF THEY | | | ARE FROM A STANDARD REFERENCED IN THE 2014 FBC. | | | 2) REMOVE THE ANCHORING DETAIL FOR THE LP TANK FROM THE | | | SUBMITTAL PACKAGE. THIS GAS SYSTEM IS NATURAL GAS. IN | | | ADDITION, THE ENGINEER'S SIGNATURE AND SEAL ON THIS | | | DOCUMENT CANNOT BE PHOTOCOPIED. IT VIOLATES FL. ADMIN. | | | RULE 61G15-23.001. ALSO, THIS ENGINEER'S SEAL HAS BEEN | | | NULL AND VOID SINCE 2015. | | | 3) THE GAS PERMIT APPLICATION STATES "INSTALL TANK AND | | | LINE" BUT THE GAS DRAWING SHOWS A NATURAL GAS METER. | | | CLARIFY. | | | 4) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE | | | PIPE. CLARIFY. | | | 5) THERE ARE THREE DIFFERENT GAS DRAWINGS THAT HAVE | | | BEEN SUBITTED FOR THIS PROJECT. REMOVE THE OLD DRAWINGS | | | AND SUBMIT TWO COPIES OF A GAS RISER THAT CLEARLY SHOWS | | | THE SCOPE OF WORK TO BE DONE.WPB AMEND TO FBC | | | SEC.107.2.1. 6TH REQUEST. | | | 6) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT | | | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A | | | LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2 | | | PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE | | | PLANS REFERENCING THE SIZING TABLE BEING USED. 6TH | | | REQUEST. | | | 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS | | | TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES | | | 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 4TH | | | REQUEST. | | | 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR | | | WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR | | | SHALL BE LOCATED IN ACCORDANCE WITH THE MANUFACTURER'S | | | INSTALLATION MANUAL OR A MINIMUM OF 5 FEET FROM THE | | | EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE | | | HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. 4TH REQUEST. | | | 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE | | | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. | | | THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW | | | THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE. 4TH | | | REQUEST. | | | 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION | | | SHEETS. FBC SEC. 107.2.1.4TH REQUEST. | | | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR | | | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR 2014 FBC-RES. SEC. G2422.1 .4TH REQUEST. | | | 9) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | 10) SHOW THE PIPE SIZES FOR ALL THE PIPING INCLUDING | | | THE EXISTING. WPB AMEND, TO FBC SEC. 107.2.1. | | | | | | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A | | | COMPRREHENSIVE REVIEW CANNOT BE DONE. | | | NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE | | | PLAN REVIEWER TO SET UP AN APPOINTMENT TO GO OVER THESE | | | REVIEW COMMENTS. | | | | | | THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN | | | REVIEW FEE PER FL. STATUTE 553.80 (2) (B). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-11-02 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-11-02 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2018-11-02 12:56:24 | NOT ONE OF THE FOLLOWING COMMENTS FROM THE PREVIOUS | | | PLAN REVIEW DONE ON 9/14/18 OR 10/1/18 HAVE BEEN | | | ADDRESSED. | | | | | | 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS | | | IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD | | | PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT | | | TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 4TH | | | REQUEST. | | | 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING | | | DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS | | | THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER | | | HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT | | | 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO | | | 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS | | | DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU | | | LOAD. 3RD REQUEST. | | | 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT | | | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A | | | LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2 | | | PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE | | | PLANS REFERENCING THE SIZING TABLE BEING USED. 5TH | | | REQUEST. | | | 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS | | | TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES | | | 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 3RD | | | REQUEST. | | | 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR | | | WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR | | | SHALL BE LOCATED IN ACCORDANCE WITH THE MANUFACTURER'S | | | INSTALLATION MANUAL OR A MINIMUM OF 5 FEET FROM THE | | | EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE | | | HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. 3RD REQUEST. | | | 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE | | | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. | | | THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW | | | THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE.3RD REQUEST. | | | 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION | | | SHEETS. FBC SEC. 107.2.1.3RD REQUEST. | | | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR | | | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR 2014 FBC-RES. SEC. G2422.1 .3RD REQUEST. | | | | | | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A | | | COMPRREHENSIVE REVIEW CANNOT BE DONE. | | | NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE | | | PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS. | | | | | | THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN | | | REVIEW FEE PER FL. STATUTE 553.80 (2) (B). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2018-10-01 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-01 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-01 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2018-10-01 11:18:42 | NOT ONE OF THE FOLLOWING COMMENTS FROM THE PREVIOUS | | | PLAN REVIEW DONE ON 9/14/18 HAVE BEEN ADDRESSED. | | | | | | 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS | | | IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD | | | PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT | | | TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 3RD | | | REQUEST. | | | 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING | | | DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS | | | THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER | | | HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT | | | 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO | | | 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS | | | DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU | | | LOAD. 2ND REQUEST | | | 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT | | | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A | | | LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2 | | | PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE | | | PLANS REFERENCING THE SIZING TABLE BEING USED. 4TH | | | REQUEST. | | | 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS | | | TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES | | | 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 2ND | | | REQUEST. | | | 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR | | | WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR | | | SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE EXTERIOR | | | WALL OF THE STRUCTURE UNLESS THE WALL IS ONE HOUR FIRE | | | RATED PER NFPA 37 SEC. 4.1.4. 2ND REQUEST. | | | 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE | | | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. | | | THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW | | | THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE.2ND REQUEST. | | | 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION | | | SHEETS. FBC SEC. 107.2.1.2ND REQUEST. | | | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR | | | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR 2017 FBC-RES. SEC. G2422.1 (8).2ND REQUEST. | | | | | | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A | | | COMPRREHENSIVE REVIEW CANNOT BE DONE. | | | NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE | | | PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-09-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-09-14 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-09-12 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2018-09-13 05:58:04 | 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS | | | IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD | | | PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT | | | TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 2ND | | | REQUEST. | | | 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING | | | DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS | | | THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER | | | HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT | | | 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO | | | 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS | | | DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU | | | LOAD. | | | 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT | | | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A | | | LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2 | | | PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE | | | PLANS REFERENCING THE SIZING TABLE BEING USED. 3RD | | | REQUEST. | | | 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS | | | TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES | | | 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. | | | 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR | | | WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR | | | SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE EXTERIOR | | | WALL OF THE STRUCTURE UNLESS THE WALL IS ONE HOUR FIRE | | | RATED PER NFPA 37 SEC. 4.1.4. | | | 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE | | | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. | | | THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW | | | THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE. | | | 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION | | | SHEETS. FBC SEC. 107.2.1. | | | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR | | | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR 2017 FBC-RES. SEC. G2422.1 (8). | | | | | | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A | | | COMPRREHENSIVE REVIEW CANNOT BE DONE. | | | NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE | | | PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-05-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-30 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2018-05-30 12:38:31 | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A | | | COMPRREHENSIVE REVIEW CANNOT BE DONE. COMPLY WITH THE | | | FOLLOWING COMMENTS. | | | | | | 1) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE | | | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. | | | SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED | | | TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL | | | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 | | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, | | | G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED | | | SIZING TABLE DOES NOTE SHOW THAT IT IS FROM THE 2014 | | | FBC-FUEL GAS. | | | | | | 2) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYTEM BUT | | | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR LESS | | | THAN A 2 PSI SYSTEM. CLARIFY. | | | | | | 4) CLEARLY IDENTIFY THE REGULATORS ON THE GAS DRAWING. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4 | | | FOR THE PROPER PIPE SIZE AND BTU LOAD. | | | | | | 6) SHOW THE TYPE OF UNDERGROUND PIPING AND THE PIPE | | | SIZE FOR THE GENERATOR. NOTE: GALVANIZED PIPE IS NOT | | | PERMITTED TO BE INSTALLED UNDERGROUND. | | | | | | 7) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE | | | OUTLET OF THE GAS METER. | | | | | | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR | | | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR 2017 FBC-RES. SEC. G2422.1 (8). | | | | | | 9) SHOW THE DISTANCE FROM THE GAS METER TO EACH | | | PRESSURE REGULATOR | | | | | | 10) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION | | | MANUAL. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | 11) SHOW THE DISTANCE OF THE GENERATOR FROM THE | | | EXTERIOR WALL OF THE STRUCTURE ON THE SURVEY. THE | | | GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE | | | EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE | | | HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. | | | | | | 12) DELETE THE OLD GAS DRAWINGS FROM THE PERMIT PACKAGE | | | AND SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-01-02 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-01-02 |
Time |
13:36 |
Sent To |
E |
|
| Notes |
| 2018-01-02 13:39:48 | 1) MIN PLAN REVIEW CRITERIA REQUIRES 2-SETS OF PLAN AND | | | ALL DOCUMENTS FBC-107.3.5 | | | | | | 2) YOUR ISOMETRIC ONLY SHOWS 10? OF GALV PIPING BUT YOU | | | STATE 2PSI P.E PIPING AS A GAS TABLE. SUBMIT AN | | | ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL | | | CUT SECTIONS OF PIPE PER 2014 FBC-FUEL GAS, SECS | | | . 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413 | | | | | | 3) TABLE YOU ARE USING TO SIZE YOU ?? GALV IN NOT THE | | | CURRENT 2014 5TH ED OF THE FUEL AND GAS CODE CURRENTLY | | | IN USE AND IS FOR L.P GAS WHEN YOUR SYSTEM IS NATURAL | | | GAS. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL | | | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 | | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, | | | G2412.8, G2413.1, G2413.2, & G2413.3. | | | | | | 4) CITY RECORDS SHOW THE EXISTING GAS SYSTEM AS .5LB | | | BUT YOUR ARE SHOWING 2LB SYSTEM. THE PLANS INDICATE AN | | | EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS | | | SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE | | | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. | | | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | | G2413.2, G2413.3. | | | | | | 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2014 FGC SEC.410.1. | | | | | | 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4 | | | FOR THE PROPER PIPE SIZE AND BTU LOAD. | | | | | | 7) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, | | | FBC-RESIDENTIAL SEC. G 2420.4. I | | | | | | 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, | | | FBC-RESIDENTIAL SEC. G 2420.4. I | | | | | | 9) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS | | | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 | | | (37) OR 2014 FBC-RES. SEC. G2413. | | | | | | 10) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014 | | | FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G | | | 2413.3. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-05 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-02-05 |
Time |
06:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2019-01-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-01-28 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-01-23 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2019-01-24 15:53:39 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-11-02 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-31 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2018-11-01 15:08:18 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-10-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-01 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-25 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2018-09-26 16:02:31 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-17 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-06 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2018-09-07 14:00:02 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-19 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-18 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2018-05-21 13:21:17 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-01-18 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-12-22 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2017-12-27 11:21:59 | GEN BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-01-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-01-18 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|