Plan Review Details - Permit 17120888
Plan Review Stops For Permit 17120888
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-11-02 Cont ID  
Sent By rmcdouga Date 2018-11-02 Time 17:56 Rev Time 0.00
Received By rmcdouga Date 2018-11-02 Time 17:46 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-10-01 Cont ID  
Sent By rmcdouga Date 2018-10-01 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2018-10-01 Time 16:08 Sent To I
Notes
2018-10-01 16:33:37PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED
 FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE
 SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS
 PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT
 THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO
 THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318
 LBS. WHICH IS LESS THAN THE LIGHTEST MODEL LISTED IN
 THE TABLE ON THE DRAWINGS. THE LENGTH AND WIDTH
 DIMENSIONS OF THE GENERATOR ARE SMALLER THAN THE ONES
 THAT ARE LISTED AND IT IS TALLER. PLEASE SUBMIT
 ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT
 HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301. IF THERE
 ARE NO PREFAB PADS FOR THIS GENERATOR, THEN YOU CAN
 FORM AND POUR A CONCRETE PAD AT THE SITE. IF YOU WISH
 TO DO THIS THEN SUBMIT TWO SETS OF DIMENSIONED PAD
 DETAILS. SPECIFY THE ANCHOR TYPE, LOCATIONS, NUMBER AND
 TYPE OF FASTENERS ON THE PLANS. THE ADDRESS OF THE
 PROJECT, THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE
 DRAWINGS. FBC 107.2.1
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2018-09-17 Time 11:15 Sent To I
Notes
2018-09-17 13:26:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED
 FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE
 SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS
 PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT
 THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO
 THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318
 LBS. WHICH IS LESS THAN ONE HALF AS MUCH AS THE
 LIGHTEST MODEL LISTED IN THE TABLE ON THE DRAWINGS. THE
 LENGTH AND WIDTH DIMENSIONS OF THE GENERATOR ARE
 SMALLER THAN THE ONES THAT ARE LISTED. PLEASE SUBMIT
 ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT
 HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-19 Cont ID  
Sent By rmcdouga Date 2018-06-19 Time 18:51 Rev Time 0.00
Received By rmcdouga Date 2018-06-19 Time 18:51 Sent To I
Notes
2018-06-19 18:52:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEERING THAT WAS SUBMITTED FOR THE GENERATOR
 PAD DOES NOT HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AS REQUIRED BY FAC 61G-15-23.003. F.S.
 471.025
  
 2) THE PAD ENGINEERING THAT WAS SUBMITTED REFERENCES
 THE 2010 FBC AND THIS PROJECT IS UNDER THE 2014 FBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By rmcdouga Date 2018-01-05 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2018-01-05 Time 17:39 Sent To Z
Notes
2018-01-05 17:43:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED SLAB AND
 ANCHORING DETAILS TO RESIST A 170 MPH VULT WIND SPEED
 IN EXPOSURE C. FBC-R301.2.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-29 Cont ID  
Sent By jleahy Date 2018-05-29 Time 13:58 Rev Time 0.00
Received By jleahy Date 2018-05-29 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By jleahy Date 2018-01-05 Time 08:57 Rev Time 0.00
Received By jleahy Date 2018-01-05 Time 08:44 Sent To  
Notes
2018-01-05 08:46:32FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 ONLY ON SET OF PLANS SUBMITTED FOR REVIEW.

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2019-02-05 Cont ID  
Sent By tklarge Date 2019-02-05 Time 06:32 Rev Time 0.00
Received By tklarge Date 2019-02-05 Time 06:10 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2019-01-28 Cont ID  
Sent By tklarge Date 2019-01-28 Time 09:34 Rev Time 0.00
Received By tklarge Date 2019-01-28 Time 05:40 Sent To I
Notes
2019-01-28 09:10:181) WHAT STANDARD ARE THE GAS SIZING TABLES FROM? THERE
 IS NO REFERENCE ON THESE TABLES TO DETERMINE IF THEY
 ARE FROM A STANDARD REFERENCED IN THE 2014 FBC.
 2) REMOVE THE ANCHORING DETAIL FOR THE LP TANK FROM THE
 SUBMITTAL PACKAGE. THIS GAS SYSTEM IS NATURAL GAS. IN
 ADDITION, THE ENGINEER'S SIGNATURE AND SEAL ON THIS
 DOCUMENT CANNOT BE PHOTOCOPIED. IT VIOLATES FL. ADMIN.
 RULE 61G15-23.001. ALSO, THIS ENGINEER'S SEAL HAS BEEN
 NULL AND VOID SINCE 2015.
 3) THE GAS PERMIT APPLICATION STATES "INSTALL TANK AND
 LINE" BUT THE GAS DRAWING SHOWS A NATURAL GAS METER.
 CLARIFY.
 4) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE
 PIPE. CLARIFY.
 5) THERE ARE THREE DIFFERENT GAS DRAWINGS THAT HAVE
 BEEN SUBITTED FOR THIS PROJECT. REMOVE THE OLD DRAWINGS
 AND SUBMIT TWO COPIES OF A GAS RISER THAT CLEARLY SHOWS
 THE SCOPE OF WORK TO BE DONE.WPB AMEND TO FBC
 SEC.107.2.1. 6TH REQUEST.
 6) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A
 LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2
 PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE
 PLANS REFERENCING THE SIZING TABLE BEING USED. 6TH
 REQUEST.
 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 4TH
 REQUEST.
 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR
 SHALL BE LOCATED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION MANUAL OR A MINIMUM OF 5 FEET FROM THE
 EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE
 HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. 4TH REQUEST.
 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW
 THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE. 4TH
 REQUEST.
 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION
 SHEETS. FBC SEC. 107.2.1.4TH REQUEST.
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2014 FBC-RES. SEC. G2422.1 .4TH REQUEST.
 9) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 10) SHOW THE PIPE SIZES FOR ALL THE PIPING INCLUDING
 THE EXISTING. WPB AMEND, TO FBC SEC. 107.2.1.
  
 THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE.
 NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN
 REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE
 PLAN REVIEWER TO SET UP AN APPOINTMENT TO GO OVER THESE
 REVIEW COMMENTS.
  
 THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN
 REVIEW FEE PER FL. STATUTE 553.80 (2) (B).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2018-11-02 Cont ID  
Sent By tklarge Date 2018-11-02 Time 13:34 Rev Time 0.00
Received By tklarge Date 2018-11-02 Time 11:46 Sent To  
Notes
2018-11-02 12:56:24NOT ONE OF THE FOLLOWING COMMENTS FROM THE PREVIOUS
 PLAN REVIEW DONE ON 9/14/18 OR 10/1/18 HAVE BEEN
 ADDRESSED.
  
 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS
 IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD
 PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 4TH
 REQUEST.
 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING
 DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS
 THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER
 HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT
 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO
 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS
 DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU
 LOAD. 3RD REQUEST.
 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A
 LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2
 PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE
 PLANS REFERENCING THE SIZING TABLE BEING USED. 5TH
 REQUEST.
 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 3RD
 REQUEST.
 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR
 SHALL BE LOCATED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION MANUAL OR A MINIMUM OF 5 FEET FROM THE
 EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE
 HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. 3RD REQUEST.
 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW
 THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE.3RD REQUEST.
 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION
 SHEETS. FBC SEC. 107.2.1.3RD REQUEST.
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2014 FBC-RES. SEC. G2422.1 .3RD REQUEST.
  
 THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE.
 NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN
 REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE
 PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS.
  
 THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN
 REVIEW FEE PER FL. STATUTE 553.80 (2) (B).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2018-10-01 Cont ID  
Sent By tklarge Date 2018-10-01 Time 11:17 Rev Time 0.00
Received By tklarge Date 2018-10-01 Time 11:02 Sent To  
Notes
2018-10-01 11:18:42NOT ONE OF THE FOLLOWING COMMENTS FROM THE PREVIOUS
 PLAN REVIEW DONE ON 9/14/18 HAVE BEEN ADDRESSED.
  
 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS
 IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD
 PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 3RD
 REQUEST.
 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING
 DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS
 THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER
 HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT
 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO
 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS
 DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU
 LOAD. 2ND REQUEST
 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A
 LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2
 PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE
 PLANS REFERENCING THE SIZING TABLE BEING USED. 4TH
 REQUEST.
 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 2ND
 REQUEST.
 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR
 SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE EXTERIOR
 WALL OF THE STRUCTURE UNLESS THE WALL IS ONE HOUR FIRE
 RATED PER NFPA 37 SEC. 4.1.4. 2ND REQUEST.
 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW
 THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE.2ND REQUEST.
 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION
 SHEETS. FBC SEC. 107.2.1.2ND REQUEST.
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2017 FBC-RES. SEC. G2422.1 (8).2ND REQUEST.
  
 THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE.
 NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN
 REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE
 PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-09-14 Cont ID  
Sent By tklarge Date 2018-09-14 Time 06:56 Rev Time 0.00
Received By tklarge Date 2018-09-12 Time 14:36 Sent To  
Notes
2018-09-13 05:58:041) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS
 IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD
 PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 2ND
 REQUEST.
 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING
 DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS
 THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER
 HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT
 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO
 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS
 DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU
 LOAD.
 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A
 LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2
 PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE
 PLANS REFERENCING THE SIZING TABLE BEING USED. 3RD
 REQUEST.
 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD.
 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR
 SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE EXTERIOR
 WALL OF THE STRUCTURE UNLESS THE WALL IS ONE HOUR FIRE
 RATED PER NFPA 37 SEC. 4.1.4.
 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW
 THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE.
 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION
 SHEETS. FBC SEC. 107.2.1.
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2017 FBC-RES. SEC. G2422.1 (8).
  
 THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE.
 NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN
 REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE
 PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-05-30 Time   Rev Time 0.00
Received By tklarge Date 2018-05-30 Time 12:14 Sent To  
Notes
2018-05-30 12:38:31THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE. COMPLY WITH THE
 FOLLOWING COMMENTS.
  
 1) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED
 SIZING TABLE DOES NOTE SHOW THAT IT IS FROM THE 2014
 FBC-FUEL GAS.
  
 2) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR LESS
 THAN A 2 PSI SYSTEM. CLARIFY.
  
 4) CLEARLY IDENTIFY THE REGULATORS ON THE GAS DRAWING.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4
 FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 6) SHOW THE TYPE OF UNDERGROUND PIPING AND THE PIPE
 SIZE FOR THE GENERATOR. NOTE: GALVANIZED PIPE IS NOT
 PERMITTED TO BE INSTALLED UNDERGROUND.
  
 7) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE
 OUTLET OF THE GAS METER.
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2017 FBC-RES. SEC. G2422.1 (8).
  
 9) SHOW THE DISTANCE FROM THE GAS METER TO EACH
 PRESSURE REGULATOR
  
 10) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION
 MANUAL. WPB AMEND. TO FBC SEC. 107.2.1.
  
 11) SHOW THE DISTANCE OF THE GENERATOR FROM THE
 EXTERIOR WALL OF THE STRUCTURE ON THE SURVEY. THE
 GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE
 EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE
 HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4.
  
 12) DELETE THE OLD GAS DRAWINGS FROM THE PERMIT PACKAGE
 AND SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By thunt Date 2018-01-02 Time 13:37 Rev Time 0.00
Received By thunt Date 2018-01-02 Time 13:36 Sent To E
Notes
2018-01-02 13:39:481) MIN PLAN REVIEW CRITERIA REQUIRES 2-SETS OF PLAN AND
 ALL DOCUMENTS FBC-107.3.5
  
 2) YOUR ISOMETRIC ONLY SHOWS 10? OF GALV PIPING BUT YOU
 STATE 2PSI P.E PIPING AS A GAS TABLE. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2014 FBC-FUEL GAS, SECS
 . 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 3) TABLE YOU ARE USING TO SIZE YOU ?? GALV IN NOT THE
 CURRENT 2014 5TH ED OF THE FUEL AND GAS CODE CURRENTLY
 IN USE AND IS FOR L.P GAS WHEN YOUR SYSTEM IS NATURAL
 GAS. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 4) CITY RECORDS SHOW THE EXISTING GAS SYSTEM AS .5LB
 BUT YOUR ARE SHOWING 2LB SYSTEM. THE PLANS INDICATE AN
 EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4
 FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 7) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4. I
  
 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4. I
  
 9) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 10) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2019-02-05 Cont ID  
Sent By tklarge Date 2019-02-05 Time 06:32 Rev Time 0.00
Received By tklarge Date 2019-02-05 Time 06:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-01-28 Cont ID  
Sent By tklarge Date 2019-01-28 Time 09:35 Rev Time 0.00
Received By tklarge Date 2019-01-23 Time 15:53 Sent To  
Notes
2019-01-24 15:53:39RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-11-02 Cont ID  
Sent By rmcdouga Date 2018-11-02 Time 17:57 Rev Time 0.00
Received By rmcdouga Date 2018-10-31 Time 15:08 Sent To  
Notes
2018-11-01 15:08:18RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-01 Cont ID  
Sent By rmcdouga Date 2018-10-01 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2018-09-25 Time 16:02 Sent To  
Notes
2018-09-26 16:02:31RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-17 Cont ID  
Sent By rmcdouga Date 2018-09-17 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2018-09-06 Time 13:59 Sent To  
Notes
2018-09-07 14:00:02RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By rmcdouga Date 2018-06-19 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2018-05-18 Time 13:21 Sent To  
Notes
2018-05-21 13:21:17RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-18 Cont ID  
Sent By cpuell Date 2018-01-18 Time 11:11 Rev Time 0.00
Received By cpuell Date 2017-12-22 Time 11:21 Sent To  
Notes
2017-12-27 11:21:59GEN BOX

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2018-01-18 Time   Rev Time 0.00
Received By pgreilic Date 2018-01-18 Time 11:02 Sent To  
Notes
2018-01-18 11:03:19PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy