Plan Review Details - Permit 17120837
| Plan Review Stops For Permit 17120837 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-01-05 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-01-05 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2018-01-05 11:24:30 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1. PROVIDE MANUFACTURER SPECS FOR COOKING EQUIPMENT AND | | | HOODS PROVIDED IN THE TEACHING KITCHEN. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE | | | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. | | | | | | 2. PROVIDE HOOD AND VENTILATION INFORMATION FOR THE | | | TEACHING KITCHEN, | | | FBC 1203.5 OTHER VENTILATION AND EXHAUST SYSTEMS. | | | VENTILATION AND EXHAUST SYSTEMS FOR OCCUPANCIES AND | | | OPERATIONS INVOLVING FLAMMABLE OR COMBUSTIBLE HAZARDS | | | OR OTHER CONTAMINANT SOURCES AS COVERED IN THE FLORIDA | | | BUILDING CODE, MECHANICAL OR THE FLORIDA FIRE | | | PREVENTION CODE SHALL BE PROVIDED AS REQUIRED BY BOTH | | | CODES. | | | | | | 3. PROVIDE MANUFACTURER?S SPECS FOR THE HUFCOR SERIES | | | 22 OPERABLE PARTITION. ENHANCE THE DETAIL 11 / A 4.0 TO | | | INCLUDE THE STRUCTURAL ATTACHMENT METHOD. | | | | | | 4. IMPACT FEES | | | | | | HAVE PLANS CHECKED BY PALM BEACH COUNTY TO SEE IF THERE | | | WILL BE A POSSIBLE IMPACT FEE. | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-08 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-08 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2018-01-08 09:45:20 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, | | | 107.2.1 | | | 2. ALL RECEPTACLE OUTLETS IN KITCHEN ARE REQUIRED TO BE | | | GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2) | | | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | | EC 405.7.1 | | | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-12-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-27 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2017-12-27 11:39:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 5 - A TEST KITCHEN WITH EQUIPMENT IS | | | INDICATEDWITH A HOOD OVER THE RANGE TOP. THIS RANGE TOP | | | SHALL BE PROTECTED PER NFPA 101 & 96 | | | | | | NFPA 101 - EXISTING EDUCATIONAL OCCUPANCIES | | | | | | 14.3.2.2 COOKING FACILITIES SHALL BE PROTECTED IN | | | ACCORDANCE WITH | | | 9.2.3. OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED | | | BETWEEN FOOD PREPARATION AREAS AND DINING AREAS. | | | | | | NFPA 101 - CHAPTER 9, BUILDING SERVICE AND FIRE | | | PROTECTION EQUIPMENT | | | 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING | | | EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD | | | FOR VENTILATION CONTROL AND FIRE PROTECTION OF | | | COMMERCIAL COOKING OPERATIONS, UNLESS SUCH | | | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, | | | WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE. | | | | | | NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS | | | 4.1 GENERAL. | | | 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING | | | SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN | | | EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND | | | PERFORMANCE REQUIREMENTS OF THIS STANDARD. | | | 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN | | | VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE | | | IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE | | | PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT. | | | | | | PLEASE REVIEW AND CORRECT. PROVIDE AN APPLICABLE NOTE | | | OF COMPLIANCE AND THAT SHOP DRAWING SHALL BE SUBMITTED | | | UNDER SEPARATE PERMIT. | | | | | | | | | | | | 2) SHEET A 5 - INDUCTION COOKERS IS INDICATED. THERE | | | ARE NO MANUFACTURES SPEC SHEETS FOR THESE AND THERE IS | | | NO HOOD INDICATED OVER THESE COOKERS. | | | | | | THESE TYPES OF COOKERS CAN NOT BE USED IN AN OPEN | | | UNPROTECTED AREA. WHAT IS THE PROPOSED USE, WHAT WILL | | | BE COOKED, ARE THEY PORTABLE OR FIXED? | | | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-19 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-12-21 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-01-05 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-01-05 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2018-01-05 11:19:47 | IMPACT FEES | | | HAVE PLANS CHECKED BY PALM BEACH COUNTY TO SEE IF THERE | | | WILL BE A POSSIBLE IMPACT FEE. | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-05 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-05 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2018-01-05 16:43:30 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120837 | | | 1/5/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.1: THE OUTDOOR DRYBULB AND WETBULB | | | TEMPERATURES AT 93 AND 80 DEGREES ARE NOT CONSISTENT | | | WITH ACCA MANUAL N WHICH ARE SET AT 90 AND 78 DEGREES- | | | PLEASE CORRECT THE PLAN AND THE CALCULATIONS. | | | | | | 2) M2.1 EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER | | | SQUARE FT. IS REQUIRED FOR THE KITCHEN PER TABLE 403.3. | | | ALL AIR SUPPLIED TO THE KITCHEN SHALL BE EXHAUSTED AND | | | CANNOT BE RECIRCULATED PER SECTION 403.2.1(3), AND | | | TABLE 403.3 FOOTNOTE B. THE CURRENT PLAN IS NOT IN | | | COMPLIANCE. | | | | | | 3) A-5.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | COOKING EQUIPMENT: THE INDUCTION COOKTOP, CONVECTION | | | MICROWAVE, WALL OVEN, AND INDUCTION COOKER. PLEASE NOTE | | | THAT SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN | | | EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS. REFER TO | | | SECTIONS 506, 507, AND 508 FOR ALL CODE REQUIREMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-19 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-18 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2018-01-19 14:16:25 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SK-1 SHALL DISCHARGE INTO THE GREASE INTERCEPTOR NOT | | | INTO SANITARY. PER FBC PL 1003.3.1 | | | | | | 2. PROVIDE MANUFACTURE SIZING CALCULATIONS FROM SCHIER | | | FOR GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. A MIN OF 4" TWO WAY CLEAN OUT IS REQUIRED ON THE | | | OUTLET OF INTERCEPTOR TO BE USED AS A TEST PORT OR A | | | PRE MANUFACTURED TEST PORT CAN BE USED. PER WPB | | | UTILITIES DEPT CONTACT JEFFERY ODOMS WITH ANY QUESTIONS | | | 561-822-2172 | | | | | | 4. A TRAP PRIMER IS REQUIRED ON THE TRENCH DRAIN . PER | | | FBC PL 1002.4 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-01-04 |
|
|
Cont ID |
|
| Sent By |
JR |
Date |
2018-01-04 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-01-04 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2018-01-04 15:04:37 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 01.04.2018 | | | PERMIT NO.: 17120837 | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. PRIOR TO THE ISSUANCE OF A CO FOR PHASE 2, ALL | | | LANDSCAPING SHOWN ON LANDSCAPE PERMIT #16041001 SHALL | | | BE COMPLETED AND PASS INSPECTION. | | | | | | 2. TREE ALTERATION PERMIT #16-1537 SHALL BE EXTENDED. A | | | REQUEST FOR SUCH EXTENSION SHALL BE SUBMITTED TO THE | | | PLANNING DIVISION. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|