Plan Review Details - Permit 17120837
Plan Review Stops For Permit 17120837
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By aclange Date 2018-01-05 Time 11:20 Rev Time 0.00
Received By aclange Date 2018-01-05 Time 08:42 Sent To  
Notes
2018-01-05 11:24:30****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. PROVIDE MANUFACTURER SPECS FOR COOKING EQUIPMENT AND
 HOODS PROVIDED IN THE TEACHING KITCHEN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 2. PROVIDE HOOD AND VENTILATION INFORMATION FOR THE
 TEACHING KITCHEN,
 FBC 1203.5 OTHER VENTILATION AND EXHAUST SYSTEMS.
 VENTILATION AND EXHAUST SYSTEMS FOR OCCUPANCIES AND
 OPERATIONS INVOLVING FLAMMABLE OR COMBUSTIBLE HAZARDS
 OR OTHER CONTAMINANT SOURCES AS COVERED IN THE FLORIDA
 BUILDING CODE, MECHANICAL OR THE FLORIDA FIRE
 PREVENTION CODE SHALL BE PROVIDED AS REQUIRED BY BOTH
 CODES.
  
 3. PROVIDE MANUFACTURER?S SPECS FOR THE HUFCOR SERIES
 22 OPERABLE PARTITION. ENHANCE THE DETAIL 11 / A 4.0 TO
 INCLUDE THE STRUCTURAL ATTACHMENT METHOD.
  
 4. IMPACT FEES
  
 HAVE PLANS CHECKED BY PALM BEACH COUNTY TO SEE IF THERE
 WILL BE A POSSIBLE IMPACT FEE.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By jpearson Date 2018-01-08 Time 09:45 Rev Time 0.00
Received By jpearson Date 2018-01-08 Time 08:17 Sent To  
Notes
2018-01-08 09:45:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. ALL RECEPTACLE OUTLETS IN KITCHEN ARE REQUIRED TO BE
 GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2)
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC 405.7.1
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By pleduc Date 2017-12-27 Time   Rev Time 0.00
Received By pleduc Date 2017-12-27 Time 10:23 Sent To  
Notes
2017-12-27 11:39:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 5 - A TEST KITCHEN WITH EQUIPMENT IS
 INDICATEDWITH A HOOD OVER THE RANGE TOP. THIS RANGE TOP
 SHALL BE PROTECTED PER NFPA 101 & 96
  
 NFPA 101 - EXISTING EDUCATIONAL OCCUPANCIES
  
 14.3.2.2 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH
 9.2.3. OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN FOOD PREPARATION AREAS AND DINING AREAS.
  
 NFPA 101 - CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE REVIEW AND CORRECT. PROVIDE AN APPLICABLE NOTE
 OF COMPLIANCE AND THAT SHOP DRAWING SHALL BE SUBMITTED
 UNDER SEPARATE PERMIT.
  
  
  
 2) SHEET A 5 - INDUCTION COOKERS IS INDICATED. THERE
 ARE NO MANUFACTURES SPEC SHEETS FOR THESE AND THERE IS
 NO HOOD INDICATED OVER THESE COOKERS.
  
 THESE TYPES OF COOKERS CAN NOT BE USED IN AN OPEN
 UNPROTECTED AREA. WHAT IS THE PROPOSED USE, WHAT WILL
 BE COOKED, ARE THEY PORTABLE OR FIXED?
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-19 Cont ID  
Sent By gjohnson Date 2018-01-19 Time 14:16 Rev Time 0.00
Received By gjohnson Date 2017-12-21 Time 10:34 Sent To  
Notes
2017-12-22 10:34:20B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By aclange Date 2018-01-05 Time 11:19 Rev Time 0.00
Received By aclange Date 2018-01-05 Time 11:19 Sent To  
Notes
2018-01-05 11:19:47IMPACT FEES
 HAVE PLANS CHECKED BY PALM BEACH COUNTY TO SEE IF THERE
 WILL BE A POSSIBLE IMPACT FEE.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By ccole Date 2018-01-05 Time 15:52 Rev Time 0.00
Received By ccole Date 2018-01-05 Time 13:58 Sent To  
Notes
2018-01-05 16:43:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120837
 1/5/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1: THE OUTDOOR DRYBULB AND WETBULB
 TEMPERATURES AT 93 AND 80 DEGREES ARE NOT CONSISTENT
 WITH ACCA MANUAL N WHICH ARE SET AT 90 AND 78 DEGREES-
 PLEASE CORRECT THE PLAN AND THE CALCULATIONS.
  
 2) M2.1 EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER
 SQUARE FT. IS REQUIRED FOR THE KITCHEN PER TABLE 403.3.
 ALL AIR SUPPLIED TO THE KITCHEN SHALL BE EXHAUSTED AND
 CANNOT BE RECIRCULATED PER SECTION 403.2.1(3), AND
 TABLE 403.3 FOOTNOTE B. THE CURRENT PLAN IS NOT IN
 COMPLIANCE.
  
 3) A-5.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 COOKING EQUIPMENT: THE INDUCTION COOKTOP, CONVECTION
 MICROWAVE, WALL OVEN, AND INDUCTION COOKER. PLEASE NOTE
 THAT SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS. REFER TO
 SECTIONS 506, 507, AND 508 FOR ALL CODE REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-19 Cont ID  
Sent By gjohnson Date 2018-01-19 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 17:24 Sent To  
Notes
2018-01-19 14:16:251ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SK-1 SHALL DISCHARGE INTO THE GREASE INTERCEPTOR NOT
 INTO SANITARY. PER FBC PL 1003.3.1
  
 2. PROVIDE MANUFACTURE SIZING CALCULATIONS FROM SCHIER
 FOR GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 3. A MIN OF 4" TWO WAY CLEAN OUT IS REQUIRED ON THE
 OUTLET OF INTERCEPTOR TO BE USED AS A TEST PORT OR A
 PRE MANUFACTURED TEST PORT CAN BE USED. PER WPB
 UTILITIES DEPT CONTACT JEFFERY ODOMS WITH ANY QUESTIONS
 561-822-2172
  
 4. A TRAP PRIMER IS REQUIRED ON THE TRENCH DRAIN . PER
 FBC PL 1002.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-04 Cont ID  
Sent By JR Date 2018-01-04 Time 15:02 Rev Time 0.00
Received By jroach Date 2018-01-04 Time 15:02 Sent To  
Notes
2018-01-04 15:04:37ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.04.2018
 PERMIT NO.: 17120837
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CO FOR PHASE 2, ALL
 LANDSCAPING SHOWN ON LANDSCAPE PERMIT #16041001 SHALL
 BE COMPLETED AND PASS INSPECTION.
  
 2. TREE ALTERATION PERMIT #16-1537 SHALL BE EXTENDED. A
 REQUEST FOR SUCH EXTENSION SHALL BE SUBMITTED TO THE
 PLANNING DIVISION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved