Plan Review Details - Permit 17120813
Plan Review Stops For Permit 17120813
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 12:12 Rev Time 0.00
Received By shill Date 2018-06-15 Time 11:17 Sent To  
Notes
2018-06-15 11:51:29****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. S110 FRAMING PLAN WAS REVISED TO INCLUDE COMPONENT
 AND CLADDING PRESSURES, BUT DOES NOT SPECIFY VASD OR
 VULT. THEY APPEARS TO BE VASD.
  
 2. RESIDENT INSPECTOR AGREEMENT REQUIRED.
  
 3. COMPLIANCE WITH ART IN PUBLIC PLACES REQUIRED.
  
 *************************************
 INTERNAL USE ONLY
  
 USC-404 - 437 ADD: NON-RES, NON-HSKPG
 SQUARE FEET - 11,000
  
 CONSTRUCTION TYPE: 14-II-B - 5TH ED TYPE II-B
 UNITS:
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 11,000
 SQ FT FOOTPRINT: 11,000
 SQ FT ROOF: 11,000
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED I-2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-16 Cont ID  
Sent By jwitmer Date 2018-04-16 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2018-04-13 Time 08:42 Sent To  
Notes
2018-04-16 14:51:032014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120813
 ADD: 301 NORTHPOINT PKWY.
 CONT: TBD/ PRO COMMERCIAL LLC
 TEL: 515-597-4700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY, APRIL 16/ 2018
 ACTION: DENIED
  
 NOTICE ONLY NO ACTION NEED TO BE TAKEN AT THIS TIME.
 ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 APPLICABLE BUILDING CODE: THE RESPONSE LETTER STATES
 THAT THE AHCA REVIEW REQUIRES YOUR PLANS BE DESIGNED TO
 THE 2017 FBC, PROBABLY BECAUSE OF THE SUBMITTAL DATE.
 THE BUILDING PLANS WERE SUBMITTED IN DECEMBER OF 2017
 BEFORE THE 31 OF THE MONTH. THAT WAS THE DATE THE 2017
 FLORIDA BUILDING CODE WAS ADOPTED, OUR REVIEWS HAVE TO
 BE UNDER THE 2014 FBC. PLEASE NOTE UNDER THE LIFE
 SAFETY SHEET 02-G010 YOU MAY ELECT TO SHOW THE
 REQUIREMENTS FOR BOTH CODES AND LISTING BOTH CODES.
  
 PLEASE NOTE AHCA REVIEWING UNDER THE 2017 EDITION OF
 THEIR CODE WILL HAVE COMMENTS NOT FOUND UNDER THE 2014
 FBC. THE ENTIRE SECTION OF FBC-B 450 NURSING HOMES HAS
 BEEN REVISED TO UPDATE THE NURSING HOME TO THE NATIONAL
 RECOGNIZED STANDARD FOR NURSING HOME DESIGN SIMILAR TO
 HOW THE HOSPITAL OR AMBULATORY SURGICAL CENTER
 REQUIREMENTS ARE WRITTEN. BECAUSE THE GUIDELINES ARE
 UPDATED EVERY FOUR YEARS THE NURSING HOMES IN FLORIDA
 WILL KEEP UP WITH THE LATEST CHANGES AND TECHNOLOGIES
 OF A NATIONAL ADOPTED AND RECOGNIZED CODE.
  
 1) COMPLIED. BUILDING NOT IN FLOOD ZONE.
  
 2) COMPLIED. ACCESSIBLE PARKING WITH CITY STANDARD
 94-485.
  
 3-5) COMPLIED.
 6) 2ND REQUEST. SEMI- COMPLIED WITH COMBUSTIBLE
 MATERIALS IN TYPE I / II BUILDINGS, . PLEASE NOTE SHEET
 33-A501 SEE DETAILS C2 & C5. DETAIL C2 SHOWS ? INCH AND
 WOOD BLOCKING NOT FIRE RETARDANT TREATED. DETAIL F6
 SHOWS THE USE OF ? INCH MARINE GRADE PLYWOOD
 SUB-STRATE. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B:
 603.1.1 1.FIRE-RETARDANT-TREATED WOOD SHALL BE
 PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2.NONBEARING EXTERIOR WALLS WHERE
 FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED.
 1.3.ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 7) SEE COMMENT FOR APPLICABLE CODES BEFORE PLAN REVIEW
 #1 COMMENT.
  
 8) SEMI-COMPLIED. THE RESPONSE COMMENT INDICATES THE
 SLEEPING ROOMS ARE UNDER SECTION 450 FOR NURSING HOMES.
 THE HEADING OF 450.3.2.5 THE CLEAR OPENING OF THE
 RESIDENT ROOM WINDOW WIDTH AND HEIGHT SHALL HAVE A
 MINIMUM OF 20 FEET (6.10 M) UNOBSTRUCTED VISTA TO ANY
 PERMANENT STRUCTURE, OR EQUIPMENT, AND 15 FEET (4.57 M)
 UNOBSTRUCTED VISTA TO ANY VEHICULAR PARKING AREAS OR
 PROPERTY LINE MEASURED HORIZONTALLY FROM THE PLANE OF
 THE WINDOW. I DO NOT SEE ANY WINDOW SCHEDULE ON THE
 ARCHITECTURAL SHEETS SHOWING COMPLIANCE.
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS ,
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 9A) PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9B) PROVISO: W. P. B. 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9C) PROVISO: NEW COMMENT. EFIS SYSTEMS: PLEASE PROVIDE
 THE PRODUCT APPROVAL FOR THE SYSTEM TO BE INSTALLED.
 PLEASE ALSO PROVIDE THE MANUFACTURERS INSTALLATION
 BROCHURE PROVIDING COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 9D) NEW COMMENT. SHEET S000 INDICATES THE WIND DESIGN
 CRITERIA AS VULT AND EXPOSURE B. PLEASE NOTE IN
 REVIEWING UNDER THE 2014 FBC-B1609.4.2 SURFACE
 ROUGHNESS. THE C SURFACE ROUGHNESS CAN BE AS LITTLE AS
 ANY SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET (30 M) HORIZONTALLY IN
 ANY DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) IN THE UPWIND DIRECTION AND A WIDTH GREATER THAN 150
 FEET (46 M). WITH THE C TYPE EXPOSURE THERE WILL BE
 MULTIPLIERS FOR THE MEAN ROOF HEIGHT OF THE BUILDING.
 SEE 2014 FBC-B TABLE 1609.7(2). ADJUSTMENT FACTOR FOR
 BUILDING HEIGHT AND EXPOSURE, (?). PLEASE EXPRESS
 PRESSURES ALSO IN VASD SINCE THE PRODUCT APPROVALS ARE
 IN VASD.
  
 9E) NEW COMMENT. THE STRUCTURAL CALCULATIONS SUBMITTED
 WILL NEED TO BE RECALCULATED UNDER THE 180 VULT AND
 EXPOSURE C. PLEASE ALSO NOTE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET
 WITH LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET.
  
 10-11) PLEASE NOTE THE PLANS SUBMITTED SHOW ON SHEET
 13-S001 STATEMENT OF SPECIAL INSPECTIONS. PLEASE BE
 AWARE THE REQUIREMENTS UNDER THE 2012 IBC 1704 SECTIONS
 4 & 5 THESE ARE INSPECTIONS REQUIRED FOR MASONRY AND
 UNIQUE WORK NOT SPECIFICALLY ADDRESS IN THE CODE. IN
 THE 2014 & 2017 CODE THESE SECTIONS ARE RESERVED. UNDER
 FLORIDA STATUTE 553.71(7) THRESHOLD BUILDINGS REQUIRES
 A THRESHOLD INSPECTOR (SPECIAL INSPECTOR). / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 UNDER THE 1ST REVIEW OUR BUILDING PLANS REVIEWER SAW
 THE WORDING STATEMENT FOR SPECIAL INSPECTIONS AND TOOK
 IT THAT YOU WISH TO HAVE A THRESHOLD INSPECTOR ONSITE
 FOR THE DURATION OF THE PROJECT AT THE OWNERS OWN COST.
 THE CITY HAS A RESIDENT INSPECTOR PROGRAM FOR SMALLER
 SITES WHICH DO NOT MEET THE STATE THRESHOLD REQUIREMENT
 AND THAT IS A RESIDENT INSPECTOR, THIS CAN QUALIFY AS A
 CONSTRUCTION TYPE II-B BUILDING BUT IT USUALLY STARTS
 AT 20,000 SQ. FT. THIS BUILDING (ADDITION IS ONLY
 11,000 SQ. FT. AND FOR THE MASONRY PORTION THE CITY
 BUILDING INSPECTORS CAN DO THE INSPECTIONS. SINCE THERE
 IS BOLTED AND WELDED STEEL CONNECTIONS TO SIMPLIFY THE
 REQUIREMENTS FOR A RESIDENT INSPECTOR AND ADDITIONAL
 EXPENSE TO THE OWNER WE HAVE REQUESTED THE FOLLOWING
 REQUIREMENTS:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
 FOR ADDITIONAL INFORMATION ON THIS SUBJECT PLEASE
 CONTACT EITHER:
 SAMANTHA HILL CHIEF PLANS EXAMINER 561-805-6724
 OR
 RICHARD GATHRIGHT ASSISTANT B. O. 561-805-6679
  
 11A) NEW COMMENT. PLEASE REVIEW SHEET 02-G010 THE LIFE
 SAFETY PLAN. THE VERSION 2 NOW HAS A NEW MAINTENANCE
 ROOM 104A. NOTE ON THE PLANS STATE TEMPORARY EGRESS
 FROM THE EXISTING BUILDING TO BE THROUGH THE NEW
 MAINTENANCE 104. THIS SPACE IS TO BE CONSTRUCTED,
 EXCEPT FOR MILLWORK PRIOR TO CLOSING THE EXISTING WEST
 EXIT. PLEASE REVIEW UNDER THE 2014 FBC-B 1014.2 EGRESS
 THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. PLEASE SEE EXCEPTION # 4, EGRESS SHALL
 NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES.
  
 11B) NEW COMMENT. THE LIFE SAFETY SHEET 02-G010
 INDICATES BETWEEN THE EXISTING BUILDING AND NEW
 ADDITION A WALL MARKED AS SB-1 A SMOKE BARRIER (1 HOUR
 RATING)/ USE: SMOKE COMPARTMENT WALL WITH DOOR. THE
 FLOOR PLAN ON SHEET 023-A101 INDICATES DOOR 100A IN THE
 DOOR SCHEDULE (34-A600) AS A 20 MINUTE FIRE RATING AND
 DOOR 118 IN THE SAME SMOKE COMPARTMENT WALL WITH NO
 FIRE RATING. PLEASE REVIEW FBC-B
 TABLE 716.5 SMOKE BARRIERS ? HOUR PROTECTION. FBC-B
 709.3 FIRE-RESISTANCE RATING. A 1-HOUR FIRE-RESISTANCE
 RATING IS REQUIRED FOR SMOKE BARRIERS.
  
 11C) NEW COMMENT. THE LIFE SAFETY SHEET 02-G010
 INDICATES A 2ND SMOKE BARRIER / SMOKE COMPARTMENT WALL
 AND DOOR # 400. IN THE DOOR SCHEDULE DOOR # 400 DOES
 NOT INDICATE A FIRE RATING. PLEASE REVIEW FBC-B
 TABLE 716.5 SMOKE BARRIERS ? HOUR PROTECTION. FBC-B
 709.3 FIRE-RESISTANCE RATING. A 1-HOUR FIRE-RESISTANCE
 RATING IS REQUIRED FOR SMOKE BARRIERS.
  
 11D) NEW COMMENT. PLEASE NOTE ON SHEET 24-A102 THE MAIN
 ROOF IS DEPICTED AS A FLAT ROOF WITH 1/4 INCH SLOPE PER
 FOOT. THE PLAN SHOWS WHAT APPEARS TO BE ROOF DRAINS
 WITH OVERFLOW SCUPPERS. IT APPEARS WE HAVE NO ROOF
 DRAINS BUT OD OVERFLOW DRAINS, SEE DETAIL D6 PLEASE
 CLARIFY. THE OTHER ISSUE IS WHAT WOULD APPEAR TO BE
 OVERFLOW SCUPPERS, THEY ARE LEVEL WITH THE LOWES POINT
 IN THE ROOF, MAKING THEM THROUGH THE WALL SCUPPERS WITH
 A CONDUCTOR HEAD ON THE EXTERIOR OF THE WALL. THE
 THROUGH THE WALL SCUPPERS DO NOT STATE THEY ARE FOR
 EMERGENCY USE, IF THEY ARE TO BE USED AS THE OVERFLOW
 SCUPPERS THEY WILL NEED TO COMPLY WITH:
 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR
 SCUPPERS. WHERE ROOF DRAINS ARE REQUIRED, SECONDARY
 (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON. THE INSTALLATION AND SIZING OF SECONDARY
 EMERGENCY OVERFLOW DRAINS, LEADERS AND CONDUCTORS SHALL
 COMPLY WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, PLUMBING.
  
 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By aclange Date 2018-01-25 Time 13:39 Rev Time 0.00
Received By aclange Date 2018-01-19 Time 14:39 Sent To  
Notes
2018-01-25 13:43:46****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FIRST REVIEW:
  
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 1. BUILDING ELEVATION
  
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12,2016,
 AFTER OCT. 11, 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
 AFTER OCTOBER 5TH 2017 THE NGVD HAS BEEN UPDATED TO
 NAVD88. PLEASE UPDATE THE PLANS TO REFLECT THIS AS WELL
 AS THE NEW FREE BOARD OF 2 FEET.
  
 2. PARKING LOTS STRIPING.
  
 ON C-3 PARKING LOT STRIPING SHOWN IS NOT ALL DOUBLE
 STRIPING. SEE ALSO FS 553.5041 (6) FOR PARKING LOT
 SIGNAGE AT ADA SPACES. NOTE: PARKING LOTS AND
 LANDSCAPING SHALL BE UNDER SEPARATE PERMITS.
  
 3. BUILDING CONSTRUCTION TYPE IS SHOWN AS I-2. PLEASE
 CLARIFY THE SUB CATEGORY USE OF THIS NURSING FACILITY
 AND TREATMENT PROVIDED. IS THIS A LONG TERM CARE
 FACILITY AS WELL. FBC 308.4 I-2 USE AND OCCUPANCY
 CLASSIFICATION.
  
 4. ACCESSIBILITY
  
 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
 DOORS AT THE CARE SUITES AND THE ATTACHED BATHROOMS
 SHALL HAVE A CLEAR DISTANCE ON THE LATCH PUSH SIDE OF
 THE DOOR OF A MINIMUM OF 12 INCHES. SEE FLORIDA
 ACCESSIBILITY CODE FIGURE 404.2.4.1 DETAIL (C).
  
 223.1 GENERAL.
 IN LICENSED MEDICAL CARE FACILITIES AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS, PATIENT OR RESIDENT SLEEPING
 ROOMS SHALL BE PROVIDED IN ACCORDANCE WITH 223.
  
 223.2 HOSPITALS, REHABILITATION FACILITIES, PSYCHIATRIC
 FACILITIES AND DETOXIFICATION FACILITIES.
 HOSPITALS, REHABILITATION FACILITIES, PSYCHIATRIC
 FACILITIES AND DETOXIFICATION FACILITIES SHALL COMPLY
 WITH 2223.3 LONG-TERM CARE FACILITIES.
 IN LICENSED LONG-TERM CARE FACILITIES, AT LEAST 50
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE OF
 RESIDENT SLEEPING ROOM SHALL PROVIDE MOBILITY FEATURES
 COMPLYING WITH 805.
  
 5. DOOR HARDWARE
 ON PAGE A 600 INCLUDE DOOR HARDWARE ON THE SCHEDULE.
 FBC 107.3
  
 6. COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION
  
 SEE PLYWOOD USED AT PARAPET WALL ON PAGE A-300. PROVIDE
 FIRE RESISTANT TREATED MATERIALS.
  
 FBC 603.1 ALLOWABLE MATERIALS.
  
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE FIRE-RESISTANCE
 RATED CONSTRUCTION IS NOT REQUIRED.
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 7. FLORIDA BUILDING CODE CRITERIA ON G010 FOR
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILITIES SHOULD BE REFERENCED AS 2014 CODE NOT 2010.
  
 ACCESSIBILITY IS REVIEWED UNDER THE 2014 5TH EDITION
 FLORIDA BUILDING CODE ACCESSIBILITY. THIS IS ADOPTED
 FROM THE 2012 FLORIDA ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION AS ADOPTED PURSUANT TO FS 553.503. PLEASE
 UPDATE THIS ON PAGE G010.
  
 8. SPECIAL DETAILED REQUIREMENTS BASED ON USE AND
 OCCUPANCY
  
 PLEASE SPECIFY HOW THE ROOMS SHOWN AS PRIVATE ON THE
 PLANS WILL BE CLASSIFIED. SEE PAGE A130 FOR EXAMPLE. I
 AM LOOKING TO SEE IF THESE WILL BE CLASSIFIED AS
 RESIDENT ROOMS IN FBC 450 OR CARE SUITES. 407.4.3 GROUP
 I-2 CARE SUITES.
 CARE SUITES IN GROUP I-2 SHALL COMPLY WITH SECTION
 407.4.3.1 THROUGH 407.4.3.4 AND EITHER SECTION
 407.4.3.5 OR 407.4.3.6.
 ONCE THIS DETERMINATION IS MADE SHOW COMPLIANCE WITH
 THESE AREAS. THIS WILL ALSO EFFECT THE SMOKE
 COMPARTMENT CONFIGURATION FBC 407.5 SMOKE BARRIERS.
  
 9. PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET G000.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10. SPECIAL INSPECTORS
 I EMAILED A COPY OF THE SPECIAL INSPECTOR AGREEMENT TO
 STEVE ALDRED FROM PRO COMMERCIAL LLC ON 1/25/18 AT
 1:10PM.
  
 A. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
  
 B. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
  
 C. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
  
 D. PROVIDE STRUCTURAL INSPECTION PLAN.
  
 11. WELDED OR BOLTED CONNECTIONS
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE A (WPS) WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
  
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 12. IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 10:39 Rev Time 0.00
Received By jpearson Date 2018-06-07 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By jpearson Date 2018-04-17 Time 16:50 Rev Time 0.00
Received By jpearson Date 2018-04-17 Time 16:18 Sent To  
Notes
2018-04-17 15:36:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2.CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 (RESPONSE LETTER STATED THIS NOTE WAS ADDED TO SHEET
 E-201, BUT THE NOTE WAS NOT THERE.)
 8. CORRECTED.
 9. CORRECTED.
 10. SPECIFY WIRE SIZES FOR ALL COMPONENTS OF THE
 GROUNDING ELECTRODE SYSTEM. NEC 250.50, 250.66; FBC
 107.2.1 (GROUNDING ELECTRODE CONDUCTORS ARE REQUIRED TO
 BE SIZED FOR THE SEPARATELY DERIVED SYSTEM PER NEC
 250.30. THE # 4 WIRE SPECIFIED ON PLAN IS NOT CODE
 COMPLIANT. PROVIDE CORRECTION.)
 11. CORRECTED.
 12. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-01 Cont ID  
Sent By jpearson Date 2018-02-01 Time 14:32 Rev Time 0.00
Received By jpearson Date 2018-01-31 Time 15:09 Sent To  
Notes
2018-02-01 14:30:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. WHY DOES THE 400 KW GENERATOR, WHICH HAS A CAPACITY
 OF APPROXIMATELY 1111 AMPS, SHOW A 1600 AMP BREAKER?
 WHAT WILL BE THE LOAD ON THIS GENERATOR? PROVIDE LOAD
 CALCULATION. NEC 220, 215.2
 3. PROVIDE LOAD CALCULATION FOR MAIN SERVICE AND EACH
 PANEL, INCLUDING EXISTING AND NEW LOADS. SOME PANEL
 SCHEDULES CURRENTLY SHOW NO LOAD. PROVIDE CORRECTION.
 NEC 220, 215.2, 215.5; FBC 107.2.1
 4. PANEL EME1 IS SHOWN AS BEING FED WITH 4 SETS OF 500
 KCMIL WIRE, WHICH WOULD HAVE AN AMPACITY OF 1520 AMPS,
 ON A 300 AMP BREAKER TO A 300 AMP PANEL. CLARIFY AND/OR
 CORRECT. FBC 107.2.1; NEC 215.2, 408.30
 5. A DISCREPANCY EXIST BETWEEN THE RISER DIAGRAM AND
 THE PANEL SCHEDULE FOR PANEL EMDP. THE RISER DIAGRAM
 SHOWS THIS AS A 1600 AMP PANEL. THE PANEL SCHEDULE
 SHOWS THIS AS A 600 AMP PANEL. CLARIFY AND CORRECT. FBC
 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. FEED FROM NEW LSI TO PANEL MDP1A IS SHOWN AS 5 SETS
 OF 500 KCMIL WIRE, WHICH HAS AN AMPACITY OF 1900 AMPS,
 ON A 600 AMP BREAKER TO A 600 AMP PANEL. CLARIFY AND/OR
 CORRECT. FBC 107.2.1; NEC 215.2, 408.30
 9. SHOW COMPLIANCE WITH PANELBOARD BONDING AS REQUIRED.
 NEC 517.14
 10. SPECIFY WIRE SIZES FOR ALL COMPONENTS OF THE
 GROUNDING ELECTRODE SYSTEM. NEC 250.50, 250.66; FBC
 107.2.1
 11. PROVIDE DETAIL LAYOUT OF MAIN ELECTRICAL ROOM,
 SHOWING ALL REQUIRED CLEARANCES AND MEANS OF EGRESS.
 NEC 110.26; FBC 107.2.1
 12. PROVIDE DETAIL OF LABELING FOR MAINS. NEC 230.2(E)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2018-07-05 Cont ID  
Sent By Mgonzale Date 2018-07-05 Time   Rev Time 1.00
Received By mgonzale Date 2018-07-05 Time   Sent To I
Notes
2018-07-05 13:31:09APPROVED THRU ENGINEERING DEVELOPMENT PERMIT
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 11:13 Rev Time 0.00
Received By shill Date 2018-07-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 10:06 Rev Time 0.00
Received By shill Date 2018-06-15 Time 10:06 Sent To  
Notes
2018-06-15 10:07:03ENGINEERING DEPARTMENT APPROVAL REQUIRED PRIOR TO
 PERMIT ISSUANCE
 ENGINEERING REVIEW FOR THIS PERMIT WILL BE DONE AFTER
 ALL OTHER REVIEWS HAVE PASSED
  
  
  
 CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 10:22 Rev Time 0.00
Received By shill Date 2018-04-21 Time 10:22 Sent To  
Notes
2018-04-21 10:22:49ENGINEERING DEPARTMENT APPROVAL REQUIRED PRIOR TO
 PERMIT ISSUANCE
 ENGINEERING REVIEW FOR THIS PERMIT WILL BE DONE AFTER
 ALL OTHER REVIEWS HAVE PASSED
  
  
  
 CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By squinone Date 2018-01-22 Time   Rev Time 0.00
Received By squinone Date 2018-01-22 Time   Sent To  
Notes
2018-01-22 13:11:321) SITE PLAN HAS NOT BEEN APPROVED. ADDRESS PPRC ENG
 COMMENTS.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-28 Cont ID  
Sent By scaldero Date 2018-03-28 Time 11:03 Rev Time 0.00
Received By scaldero Date 2018-03-28 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By wjolin Date 2018-01-04 Time 14:46 Rev Time 0.00
Received By wjolin Date 2018-01-04 Time 09:57 Sent To  
Notes
2018-01-04 14:44:24301 NORTHPOINT PARKWAY
 PERMIT #17120813
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET C-2: PROVIDE A FIRE HYDRANT ALONG THE DRIVE OF
 THE WEST SIDE OF THE BUILDING.
  
 SHEET C-2: PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES
 SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE
 LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT."
 SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND
 RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN
 HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN
 SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60
 FEET APART. ENSURE EXISTING FIRE DEPARTMENT ACCESS
 ROADS HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 SHEET A101: THE TRAVEL DISTANCE WITHIN THE NEWLY
 CREATED SMOKE COMPARTMENT CREATES A TRAVEL DISTANCE
 EXCEEDING 200 FEET TO THE ADJACENT SMOKE COMPARTMENT
 FOR THE DEFEND-IN-PLACE STRATEGY UTILIZED BY HEALTHCARE
 OCCUPANCIES. PER NFPA 101 SECTION 18.3.7 SUBDIVISION OF
 BUILDING SPACES. BUILDINGS CONTAINING HEALTH CARE
 FACILITIES SHALL BE SUBDIVIDED BY SMOKE BARRIERS, AS
 FOLLOWS: (4) "TO LIMIT THE TRAVEL DISTANCE FROM ANY
 POINT TO REACH A DOOR IN THE REQUIRED SMOKE BARRIER TO
 A DISTANCE NOT EXCEEDING 200 FEET." RECOMMEND DIVIDING
 THE NEW SMOKE COMPARTMENT INTO TWO SMALLER
 COMPARTMENTS.
  
 SHEET F101: NO WATER SUPPLY DATA PROVIDED IN ACCORDANCE
 WITH FLORIDA ADMINISTRATIVE CODE 61G15-32.004.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 09:03 Rev Time 0.00
Received By gjohnson Date 2018-06-13 Time 09:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By gjohnson Date 2018-04-18 Time 15:58 Rev Time 0.00
Received By gjohnson Date 2018-04-18 Time 15:57 Sent To  
Notes
2018-04-18 16:54:511ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE THE SIZING TABLE FROM THE FBC FUEL
 GAS 2014 5TH EDITION THAT WAS USED IN SIZING SYSTEM.
 PER WPB AMEND TO FBC 107.2.1
  
 2. LABEL TYPE OF PIPE BEING USED. PER WPB AMEND TO FBC
 107.2.1
  
 3. PLEASE LIST PRESSURE IN PSI FOR SERVICE PRESSURE AND
 PRESSURE DROP IN OF WC. PER WPB AMEND TO FBC 107.2.1
  
 4. THE TOTAL DEVELOPED LENGTH FROM WATER HEATER SHALL
 BE MEASURED ALL THE WAY TO METER.PER WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 11:13 Rev Time 0.00
Received By shill Date 2018-06-20 Time 13:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 12:18 Rev Time 0.00
Received By shill Date 2018-05-11 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 10:28 Rev Time 0.00
Received By shill Date 2018-03-27 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-12 Cont ID  
Sent By lmarchan Date 2018-02-12 Time 11:13 Rev Time 0.00
Received By lmarchan Date 2017-12-28 Time 07:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2018-07-11 Cont ID  
Sent By shill Date 2018-07-11 Time 06:37 Rev Time 0.00
Received By shill Date 2018-07-11 Time 06:36 Sent To  
Notes
2018-07-11 06:37:46MU 2018-23384
 $12,748.87
 PER EMAIL FROM WILLIE SWOOPE 7/9/18
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2018-07-02 Cont ID  
Sent By shill Date 2018-07-02 Time 10:17 Rev Time 0.00
Received By shill Date 2018-07-02 Time 10:17 Sent To  
Notes
2018-07-02 10:17:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 11:28 Rev Time 0.00
Received By shill Date 2018-06-15 Time 11:28 Sent To  
Notes
2018-06-15 11:28:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-04-16 Cont ID  
Sent By jwitmer Date 2018-04-16 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2018-04-16 Time 14:56 Sent To  
Notes
2018-04-16 14:56:44BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By aclange Date 2018-01-25 Time 13:37 Rev Time 0.00
Received By aclange Date 2018-01-25 Time 13:37 Sent To  
Notes
2018-01-25 13:38:17IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-07-03 Cont ID  
Sent By ccole Date 2018-07-03 Time 11:49 Rev Time 0.00
Received By ccole Date 2018-07-03 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-06-07 Cont ID  
Sent By ccole Date 2018-06-04 Time 09:00 Rev Time 0.00
Received By ccole Date 2018-06-01 Time 17:05 Sent To  
Notes
2018-06-04 09:14:443RD REVIEW FBC-2017 MECHANICAL
 PERMIT #17120813
 6/4/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMPLIANCE DATA LISTED ON THE COMCHECK
 CERTIFICATE NEEDS TO BE UPDATED TO MATCH THE CHANGES TO
 THE AC SYSTEMS.
  
 2) SHEET M202: REFER TO TABLE 305.4 FBC-17 MECHANICAL.
 THE SPACING OF THE PVC CONDENSATE PIPING SUPPORTS SHALL
 BE 4' O.C. PLEASE REVISE NOTE M09 AND SUBMIT A PRODUCT
 DATA SHEET FOR THE SUPPORTS OR LIST AS A DEFFERRED
 SUBMITTAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-20 Cont ID  
Sent By ccole Date 2018-04-20 Time 07:42 Rev Time 0.00
Received By ccole Date 2018-04-17 Time 17:12 Sent To  
Notes
2018-04-20 08:15:252ND REVIEW FBC-2017 MECHANICAL
 PERMIT #17120813
 4/20/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CALCULATIONS INDICATE A COOLING LOAD OF 180
 MBH FOR THE ROOMS AND SPACES SERVED BY RTU-3, HOWEVER
 THE SYSTEM SELECTED HAS A TOTAL COOLING CAPACITY OF
 84.6 MBH- SEE THE RTU-3 SCHEDULE ON M600.
  
 2) AS PREVIOUSLY REQUESTED, AND PER THE REFERENCE NOTE
 IN THE AC SCHEDULES, PLEASE PROVIDE SYMBOLS ON THE
 MECHANICAL PLANS SHOWING THE LOCATIONS OF REQUIRED DUCT
 SMOKE DETECTORS.
  
 3) IT APPEARS FROM THE PLANS AND THE ARCHITECT'S
 RESPONSE NARRATIVE THAT COMPLETE WIND LOAD ENGINEERING
 FOR INSTALLATION OF THE ROOFTOP AC SYSTEMS WILL BE
 DEFERRED. PLEASE NOTE THAT THE ENGINEERING SHALL BE
 SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW AND
 APPROVAL PRIOR TO INSTALLATION, AND THE ENGINEERING
 SHALL BE ONSITE AT TIME OF INSPECTION. PLEASE REVIEW
 SECTION 107.3.4.1 WPB AMENDMENTS TO THE FBC-17:
 DEFERRED SUBMITTALS.
  
 4) SHEET M202: INDICATE THE TYPES AND SIZES OF
 CONDENSATE PIPING, AND INDICATE HOW THE PIPING WILL BE
 SUPPORTED AND ANCHORED TO THE ROOF SURFACE. PLEASE
 PROVIDE A DETAIL THAT SHOWS THE PIPE SUPPORTS AND
 REQUIRED SPACING OF THE SUPPORTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By ccole Date 2018-01-26 Time 17:16 Rev Time 0.00
Received By ccole Date 2018-01-26 Time 12:11 Sent To  
Notes
2018-01-26 17:17:141ST REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION
 CODES , ASHRAE 170-2008, GUIDELINES FOR DESIGN AND
 CONSTRUCTION OF HEALTH CARE FACILITIES- 2010.
 PERMIT #17120057
 1/26/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) IN ACCORDANCE WITH SECTION C403.2.1 FBC-14 PROVIDE
 COOLING AND HEATING CALCULATIONS FOR THE RTU'S, AND THE
 PTAC UNITS.
  
 2) THE ARCHITECT AND ENGINEER OF RECORD SHALL PROVIDE
 ELECTRONIC SIGNATURES AND SEALS ON THE COMCHECK
 COMPLIANCE CERTIFICATE- SECTION 61G15-23.005 FAC.
  
 3) SHEETS G010 & M201: THERE ARE MISSING FIRE DAMPERS
 WHERE DUCTS ARE PENETRATING THE FIRE-RATED WALLS AT
 STORAGE 401, SOILED UTILITY 431, & LINEN STORAGE 433.
  
 4) M201: REFER TO SECTION 607.5.4 AND PROVIDE SMOKE
 DAMPERS FOR ALL DUCTS PENETRATING THE CORRIDOR WALLS,
 UNLESS THE WALL IS NOT REQUIRED TO HAVE SMOKE AND DRAFT
 CONTROL DOORS, OR IF MEETING ONE OF THE THREE
 EXCEPTIONS LISTED UNDER THE CODE SECTION.
  
 5) M201: PROVIDE A SYMBOL ON THE PLAN TO INDICATE THE
 LOCATIONS OF REQUIRED DUCT SMOKE DETECTORS PER SECTION
 606.2.1. INDICATE HOW THE DEVICES WILL BE SUPERVISED,
 AND THE SEQUENCE OF OPERATION RELATING TO SHUTDOWN OF
 THE SYSTEM(S) WHEN A DETECTOR ACTUATES- SECTIONS 606.4
 AND 606.4.1;.
  
 6) PROVIDE THE WIND LOAD DESIGN CRITERIA AND COMPLETE
 ENGINEERED DETAILS FOR INSTALLATION OF THE RTU'S AND
 CURBS- SEE SECTION 301.15 FBC-14 MECHANICAL, AND
 SECTION 1609 FBC-14 BUILDING.
  
 7) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE RTU'S AND
 THE PTAC UNITS- SECTION 307.
  
 8) PROVIDE DUCT INSTALLATION DETAILS: TYPE OF DUCTWORK,
 PRESSURE CLASSIFICATION, INSULATION THICKNESS AND
 R-VALUE, AND SUPPORT, HANGING, AND CONNECTION DETAILS.
  
 9) VERIFY THAT THE PTAC UNITS ARE FOR RECIRCULATION
 ONLY AND WILL NOT PROVIDE OUTSIDE AIR AS NOTED IN
 SECTION 4.1-8.2.1(2) GUIDELINES FOR DESIGN AND
 CONSTRUCTION OF HEALTH CARE FACILITIES. OTHERWISE
 MINIMUM MERV 7 FILTERS ARE REQUIRED PER TABLE 6-1
 ASHRAE 170-2008.
  
 10) REFER TO SECTION 6.3.1 ASHRAE 170-2008 AND VERIFY
 HEIGHT CLEARANCE REQUIREMENTS FOR O/A INTAKES ON THE
 ROOF OR AT GRADE.
  
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 WATER HEATER.
  
 12) SHOW HOW ACCESS WILL BE PROVIDED TO THE ROOF FOR
 SERVICE AND REPLACEMENT OF THE ROOF TOP MECHANICAL
 EQUIPMENT- SECTION 306.5.
  
 13) PLEASE SEE BUILDING REVIEW COMMENTS RELAIVE TO
 FLOOD ELEVATION AND VERIFY ALL MECHANICAL EQUIPMENT
 WILL BE LOCATED AT OR ABOVE THE REQUIRED FLOOD
 ELEVATION HEIGHT- SECTION 301.16.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 09:03 Rev Time 0.00
Received By gjohnson Date 2018-06-12 Time 17:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-18 Cont ID  
Sent By gjohnson Date 2018-04-18 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2018-04-18 Time 10:26 Sent To  
Notes
2018-04-18 15:57:452ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE THE DIMENSIONS FOR THE SINGLE USER
 BATHROOM #437 INCLUDE THE REQUIRED CLEAR FLOOR SPACE
 FOR THE TOILET AND THE LAVATORY. PER WPB AMEND TO FBC
 107.2.1
  
 2. PLEASE PROVIDE THE MANUFACTURE SPECIFICATIONS FOR
 THE MASTER MIXING VALVE TMV-1 LAWLER 802- MS- ARV PER
 WPB AMEND TO FBC 107.2.1
  
 3. SHT. P520 DETAIL 5D A VACUUM BREAKER IS REQUIRED ON
 INLET SIDE OF THE WATER HEATER. PER FBC PL 504.2
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
 THE MASTER MIXING VALVE DOES NOT COMPLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-12 Cont ID  
Sent By gjohnson Date 2018-02-12 Time 09:10 Rev Time 0.00
Received By gjohnson Date 2018-02-08 Time 17:14 Sent To  
Notes
2018-02-12 09:12:161ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW THE CLEAR FLOOR SPACE FOR THE TOILETS AND
 LAVATORY WITH DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
 2. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY.
 THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM
 FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR
 610.3.2. PER FBC ACC 608.4
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR W 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 4. ALL BATHROOMS IN PATIENT ROOMS SHALL COMPLY WITH FBC
 ACC 805.2 PER FBC ACC 223.2.2
  
 5. SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER TYPE
 SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 6. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 COMPLYING WITH FBC PL 403.2 SEPARATE FACILITIES. WHERE
 PLUMBING FIXTURES ARE REQUIRED, SEPARATE FACILITIES
 SHALL BE PROVIDED FOR EACH SEX.
  
 7. PROVIDE DIMENSIONS ON THE SCUPPER. PER WPB AMEND TO
 FBC 107.2.1
  
 8. JUST FOR CLARIFICATION THE SCUPPER IS THE MAIN ROOF
 DRAIN AND THE ROUND ROOF DRAIN LOCATED OUT ON THE ROOF
 DECK IS THE OVERFLOW DRAIN. PER WPB AMEND TO FBC
 107.2.1
  
 9. THE DISCHARGE FROM THE OVERFLOW DRAIN SHALL COMPLY
 WITH FBC PL 1108.2 SEPARATE SYSTEMS REQUIRED.
 SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT
 OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM.
 DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT
 WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONNEL.
  
 10. SHT. P701 SHOW THE TRAPS ON THE FLOOR DRAINS,
 LAVATORY, FLOOR SINKS AND SHOWERS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 11. SHT. P701 DETAIL 3A AND ON THE END OF THE BUILDING
 DRAIN A HORIZONTAL DRY VENT IS SHOWN WITCH IS NOT
 ALLOWED ALL VENT S SHALL CONNECT ABOVE THE CENTERLINE
 OF THE HORIZONTAL DRAIN AND RISE VERTICALLY TO A POINT
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE IT IS
 SERVING. PER FBC PL 905.3 AND 905.4
  
 12. SHT. P701 THE OVER FLOW ROOF DRAINS APPEAR TO
 CONNECT TO THE SANITARY SYSTEM PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 13. SHT. P702 PLEASE SHOW ON THE WATER ISOMETRIC,
 VALVES ON ALL DROPS, AIR HAMMER ARRESTORS. PER FBC PL
 604.9, 606.1(5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-04-16 Cont ID  
Sent By jwitmer Date 2018-04-16 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2018-04-16 Time 14:55 Sent To  
Notes
2018-04-16 14:55:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120813
 ADD: 301 NORTHPOINT PKWY.
 CONT: TBD/ PRO COMMERCIAL LLC
 TEL: 515-597-4700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY, APRIL 16/ 2018
 ACTION: BUILDING PROVISO
  
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTALS:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 , VENTILATORS
  
 2) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By aclange Date 2018-01-25 Time 13:45 Rev Time 0.00
Received By aclange Date 2018-01-25 Time 13:45 Sent To  
Notes
2018-01-25 13:46:07PROVIDE ROOFING PRODUCT APPROVALS AND SUPPORTING
 DOCUMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-07-11 Cont ID  
Sent By shill Date 2018-07-11 Time 06:36 Rev Time 0.00
Received By shill Date 2018-07-11 Time 06:36 Sent To  
Notes
2018-07-03 11:52:38MECH DIG/SIGS GOOD
 CCOLE- 7/3/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 11:29 Rev Time 0.00
Received By shill Date 2018-06-15 Time 11:29 Sent To  
Notes
2018-06-15 11:30:00SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS
 471, FS 481. NEW DOCUMENTS SUBMITTED IN THE NEXT REVIEW
 CYCLE REQUIRE REVIEW.
2018-06-13 09:04:486/13/18 DIG SIG ON PLUMB SHT. OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 10:26 Rev Time 0.00
Received By shill Date 2018-04-21 Time 10:26 Sent To  
Notes
2018-04-21 10:28:20DIGITAL SIGNATURE ON SHEET P201 IS LACKING, FS471.
 CONFIRM ALL.
  
 OTHER PAGES FOR ALL TRADES HAVE BEEN SPOT CHECKED. NEW
 SHEETS UPLOADED FOR 3RD REVIEW CYCLE REQUIRE REVIEW.
  
2018-04-18 16:06:214/17/18 DIG SIG ON SHT P201 IS MISSING/GPJ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By aclange Date 2018-01-25 Time 13:39 Rev Time 0.00
Received By aclange Date 2018-01-25 Time 13:38 Sent To  
Notes
2018-01-25 13:39:31A AND S PAGE SIGNATURES OK

Review Stop Z ZONING
Rev No 4 Status P Date 2018-06-20 Cont ID  
Sent By jroach Date 2018-06-20 Time 11:38 Rev Time 0.00
Received By jroach Date 2018-06-20 Time 11:38 Sent To  
Notes
2018-06-20 11:40:58PROVISO
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED TO, AND REVIEWED AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION.
  
 2. ALL LANDSCAPE PLANS SHALL BE SUBMITTED AND REVIEWED
 UNDER A SEPARATE LANDSCAPE PERMIT APPLICATION PURSUANT
 TO RESOLUTION NO. 127-18, A REVIEW OF THE PREVIOUSLY
 APPROVED LANDSCAPE PLANS SHALL BE COMPLETED FOR THE
 ENTIRE PROPERTY (LOTS 15, 16, AND 17). ANY LANDSCAPE
 MATERIAL THAT IS FOUND TO BE MISSING OR OTHERWISE NEEDS
 TO BE REPLACED ON THE SITE SHALL BE INCORPORATED INTO
 THE SCOPE OF THE PROPOSED PROJECT AND COMPLETED PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY/COMPLETION.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2018-06-07 Cont ID  
Sent By jroach Date 2018-06-07 Time 15:11 Rev Time 0.00
Received By jroach Date 2018-06-07 Time 15:11 Sent To  
Notes
2018-06-07 15:11:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.07.2018
 PERMIT NO.: 17120813
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE NORTHPOINT COMMERCIAL PLANNED
 DEVELOPMENT (CPD) AND DEVELOPMENT OF REGIONAL IMPACT
 (DRI) SHALL BE APPROVED BY THE CITY COMMISSION. ALL
 PLANS SUBMITTED FOR PERMITTING SHALL MATCH THOSE PLANS
 APPROVED BY THE CITY COMMISSION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-16 Cont ID  
Sent By jroach Date 2018-04-16 Time 16:29 Rev Time 0.00
Received By jroach Date 2018-04-16 Time 16:29 Sent To  
Notes
2018-04-16 16:29:45ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.16.2018
 PERMIT NO.: 17120813
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE NORTHPOINT COMMERCIAL PLANNED
 DEVELOPMENT (CPD) AND DEVELOPMENT OF REGIONAL IMPACT
 (DRI) SHALL BE APPROVED BY THE CITY COMMISSION. ALL
 PLANS SUBMITTED FOR PERMITTING SHALL MATCH THOSE PLANS
 APPROVED BY THE CITY COMMISSION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By JR Date 2018-02-08 Time 09:00 Rev Time 0.00
Received By jroach Date 2018-02-08 Time 09:00 Sent To  
Notes
2018-02-08 09:01:03ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.08.2019
 PERMIT NO.: 17120813
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE NORTHPOINT COMMERCIAL PLANNED
 DEVELOPMENT (CPD) AND DEVELOPMENT OF REGIONAL IMPACT
 (DRI) SHALL BE APPROVED BY THE CITY COMMISSION. ALL
 PLANS SUBMITTED FOR PERMITTING SHALL MATCH THOSE PLANS
 APPROVED BY THE CITY COMMISSION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH