| Plan Review Stops For Permit 17120809 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-03-22 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-22 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-22 |
Time |
12:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-19 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-01-19 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-01-19 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2018-01-19 13:17:14 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | | 2017 6TH EDITION | | | | | | 1. OK | | | | | | 2. INCLUDE PRESSURES ON THE WINDOW AND DOOR SCHEDULES | | | ON PAGES A 7.01 AND A 7.02. | | | FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-CHAPTER 16. | | | | | | 3. ON PAGE A 4.30 #4 A BAR TOP IS SHOWN AT 42 INCHES. | | | IS AN ADA COMPLIANT BAR TOP PROVIDED AS WELL. | | | | | | 4. WELDED OR BOLTED CONNECTIONS | | | | | | THE CONTRACTOR IS REQUIRED TO PROVIDE A (WPS) WELD | | | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. | | | 2014 FBC-B 2204.1 WELDING | | | 2014 FBC-B 2204.2 BOLTING. | | | | | | 5. PRODUCT APPROVALS | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR | | | SUBMITTALS. | | | ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED | | | SUBMITTAL BY LISTING THEM ON THE COVER SHEET. | | | INCLUDE THE OVERHEAD DOOR ON THIS LIST. | | | | | | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-01-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-30 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-30 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-01-03 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-01-03 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-01-03 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-25 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-25 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-04-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-07 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-07 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2018-04-07 13:38:23 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. THE PLAN NOTES #S 1,2,3 ON THE GAS RISER DO NOT | | | MATCH UP TO THE PLAN NOTES THEMSELVES PLEASE CLARIFY. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | | PER NFPA 58, TABLE 3-2.2.2. | | | | | | 3. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE | | | OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF THE | | | TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | | PER NFPA 58 SECTION 3-2.2.7(H). | | | | | | 4. SECOND STAGE REGULATORS ARE REQUIRED AT THE | | | APPLIANCE TO REDUCE PRESSURE FROM 2PSI DOWN TO 11.0 IN | | | WC PLEASE SHOW ON RISER AND PROVIDE MANUFACTURE | | | SPECIFICATIONS FOR ALL REGULATORS. PER FBC FG 410.1 AND | | | 410.2 | | | | | | 5. IF LP TANK IS UNDER SEPARATE PERMIT PLEASE INDICATE | | | ON PLAN. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-31 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-31 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2018-01-31 15:16:59 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | | PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | | PER NFPA 58 SECTION 3-2.2.7(H). | | | | | | 12. SHT. P0.10 PLAN NOTE #4, #6, #7REFER TO LP GAS NOTE | | | #8 REFERS TO NATURAL GAS PLEASE CLARIFY. PER WPBAMEND | | | TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-05-29 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-04-26 |
Time |
08:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-04-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-07 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-14 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-01-31 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-12-27 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-15 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-15 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-04-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-04-06 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-05 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2018-04-06 11:05:57 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #17120809 | | | 4/6/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M6.02: THE CALCULATED OCCUPANT LOAD USED TO | | | DETERMINE THE VENTILATION FOR THE FITNESS ROOMS IS NOT | | | IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES 40 | | | OCCUPANTS PER 1000 S.F. PLEASE CORRECT. | | | | | | 2) M1.11: AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS- | | | EITHER MOTORIZED OR GRAVITY- SHALL BE PROVIDED FOR THE | | | O/A DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-25 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-25 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2018-01-25 16:04:04 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #17120809 | | | 1/25/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER OF RECORD SHALL PROVIDE ELECTONIC | | | SIGNATURES AND SEALS ON THE MECHANICAL PLANS AND THE | | | ENERGY COMPLINCE FORM C402-2014 IN COMPLIANCE WITH | | | SECTION 61G15-23.005 FAC. | | | | | | 2) SHEET D1.12: SHOW THE LOCATIONS OF KEY NOTE D ON THE | | | PLAN. | | | | | | 3) M1.11: PLEASE LABEL THE OUTSIDE AIR DUCTS ON THE | | | PLAN, AND PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF | | | DAMPERS IN ACCORDANCE WITH SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-10-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-20 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-10-20 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2020-10-20 12:27:53 | PREVIOUS REVIEW BY G.JOHNSON OF "N" APPEARS TO BE AN | | | ERROR; GEORGE STAMPED THE PLANS WITH HIS BLOCK STAMP, | | | NUMEROUS PLUMBING PAGES SUBMITTED, REVIEWED AND ISSUED | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-25 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-25 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-04-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-07 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-07 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2018-04-07 13:23:15 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE JANITORS | | | SINK AND THE BOTTLE FILLING STATION. PER WPB AMEND TO | | | FBC 107.3.5.1.3(13) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-31 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-31 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2018-01-31 15:13:05 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | 1. SHT. A0.02 INDEX OF PLUMBING DRAWINGS IT LIST | | | E1.11P, ED1.11P THESE ARE ELECTRIC SHEETS PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. SHT. A0.02 INDEX OF PLUMBING DRAWINGS P1.11 IS | | | LISTED BUT MISSING FROM PLAN SET, P0.10, P6.02 ARE IN | | | THE PLAN SET BUT NOT LISTED SHEETS PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 3. SHT. A1.21 AND A1.22 LIST C13 FIRE PLACE IN NOTES | | | BUT COULD NOT LOCATE ON PLAN SHEETS PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 4. SHT. A4.21 DETAIL #1 IN BATHROOMS 13, 14 IT SHOWS | | | 17?- 19? TO THE CENTERLINE OF THE TOILET THOSE | | | DIMENSIONS ONLY APPLY TO AMBULATORY STALL THIS IS A | | | WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT AND SHALL BE | | | 16?- 18?.PER FBC ACC 604.2 | | | | | | 5. SHT. P6.01 HOT WATER MIXING VALVE WATTS USG-B IS NOT | | | LISTED AS LEAD FREE YOU CAN USE THE LFUSG-B IT IS | | | LISTED AS LEAD FREE BY MANUFACTURE SPEC. PER FBC PL | | | 605.2.1 | | | | | | 6. SHT P6.02 VALVES REQUIRED AT ALL WATER PIPING DROPS. | | | PER FBC PL 606.1 (5) | | | | | | 7. SHT. P6.02 SHOW AIR HAMMER ARRESTOR VALVES AND TRAP | | | PRIMERS ON ISOMETRIC DRAWINGS. PER FBC PL 604.9, 1002.4 | | | | | | 8. SHT. P6.02 LABEL AND SIZE UNMARKED PIPE ON WATER | | | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 | | | | | | 9. PROVIDE PLUMBING FLOOR PLAN. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 10. PLEASE CLARIFY IS THE JANITOR SINK NEW OR EXISTING. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 11. SHT. P0.10 PROVIDE ISOMETRIC DRAWINGS FOR FLOOR | | | DRAINS. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 12. SHT. P0.10 IF THE FLOOR DRAINS ARE CONNECTED TO | | | SANITARY THEY SHALL BE PROTECTED FROM DISCHARGE OF | | | STORM WATER. PER WPB CODE OF ORDINANCES SEC. 90-126(5) | | | | | | 13. SHT. P0.10 POOL DISCHARGE CANNOT GO TO SANITARY. | | | PER WPB CODE OF ORDINANCES SEC. 90-126(5) | | | | | | 14. PLACE NOTE ON PLAN A SEPARATE PERMIT IS REQUIRED | | | FOR BACKFLOWS AND FOUNTAIN. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2018-05-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-05-29 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-05-29 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2018-01-31 15:21:48 | 1/31/18 DIG SIG ON PLUM OK /GPJ | | 2018-01-25 16:02:53 | NO ELECTROCIC SIGNATURES ON MECH PLANS AND ENERGY | | | COMPLIANCE FORM- CCOLE- 1/25/18 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-01-18 |
|
|
Cont ID |
|
| Sent By |
LL |
Date |
2018-01-18 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-01-18 |
Time |
|
Sent To |
|
|
| Notes |
|
|