| 2017-12-22 04:45:08 | THE SUBMITTED LETTER FROM THOMAS ENGINEERING GROUP |
| | APPEARS TO BEAR A COPY OF THE ENGINEER'S SEAL AND |
| | SIGNATURE. PER FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G15-23.001 - SIGNATURE, DATE AND SEAL SHALL BE |
| | AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL: |
| | (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS, |
| | OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE |
| | AND BEING FILED FOR PUBLIC RECORD; |
| | THEREFORE, BOTH LETTERS FROM JASON MATTHEW GUNTHER |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE F.A.C. RULE. |
| | 2) SUBMIT TWO COMPLETE COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR EACH BACKFLOW DEVICE, INCLUDING THE |
| | FIRE DOUBLE DETECTOR CHECK ASSEMBLY. PLACE THE |
| | SPECIFICATIONS INTO SEPARATE GROUPS FOR EACH INDIVIDUAL |
| | DEVICE. AS SUBMITTED AT THIS TIME, ALL THE |
| | SPECIFICATION SHEETS ARE COMPILED INTO TWO GROUPS AND I |
| | CANNOT DETERMINE WHICH SHEETS ARE FOR WHICH DEVICE. WPB |
| | AMEND. TO FBC SEC. 107.2.1. THERE ARE NO SPECIFICATIONS |
| | FOR THE 8 INCH WILKINS 350 DA, THE 3/4 INCH WILKINS 950 |
| | XLD, AND ONLY ONE PAGE FOR THE WATTS 757 AND 757N. |
| | 3) THE BACKFLOW DEVICES SHALL BE TESTED AND CERTIFIED |
| | BY THE CITY OF WEST PALM BEACH UTILITIES DEPT.PER THE |
| | CITY OF WEST PALM BEACH MANUAL FOR CROSS-CONNECTION |
| | CONTROL WITH A REVISED DATE OF 9-11-17. CALL |
| | 561-822-2240 FOR FURTHER INFORMATON/DDIRECTION. |
| | 4) SHOW THE LOCATIONS OF ALL THE BACKFLOW PREVENTION |
| | DEVICES ON THE SUBMITTED PLAN SHEET C-09. THE DEVICES |
| | SHALL BE IDENTIFIED BY EITHER HIGHLIGHTING OR CLOUDING |
| | THE LOCATION. WPB AMEND. TO FBC SEC. 107.2.1. SUBMIT A |
| | DRAWING THAT CAN BE READ. THE PRINT ON SHT. C-09 IS SO |
| | SMALL IT IS ALMOST ILLEGIBLE. WPB AMEND. TO FBC SEC. |
| | 107.1, 107.2.1. |
| | 5) AS NOTED IN THE COPY OF THE CORRECTION NOTICE, |
| | SUBMIT BACKUP/VERIFICATION DATA AS TO HOW THE |
| | CONCLUSION WAS REACHED TO ACCEPT THE SIZE OF THE |
| | DEVICES THAT HAVE BEEN INSTALLED WHICH DOES NOT |
| | CORRELATE WITH THE APPROVED PLANS. A PLAN REVISION |
| | (AS-BUILTS) OF THE CIVIL PLANS AFFECTED BY THESE |
| | CHANGES SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR |
| | REVIEW AND APPROVAL PRIOR TO RECEIVING A CERTIFICATE OF |
| | OCCUPANCY ON THE BUILDING. WPB AMEND. TO FBC SEC. |
| | 107.4. |
| | |