| Plan Review Stops For Permit 17120734 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-12-22 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-12-21 |
Time |
19:15 |
Sent To |
I |
|
| Notes |
| 2017-12-22 08:21:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE TRUSS DRAWINGS ARE REQUIRED TO HAVE THE TRUSS | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, DIGITALLY | | | CREATED OR COPIED IMAGE OF THE LICENSEE'S SIGNATURE | | | SHALL NOT BE USED. FAC 61G15-23.003 | | | | | | 2) THE STURCTURAL ENGINEER OF RECORD FOR THE PROJECT ( | | | ROBERT EUGENE FETROW ) IS REQUIRED TO REVIEW AND | | | APPROVE THE TRUSS LAYOUT PLAN FROM THE DELEGATED | | | ENGINEER. FAC61G15-31.003 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-12-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-12-22 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-12-19 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2017-12-20 12:33:12 | SUBMITTAL ROUTED TO RMCDOUGAL |
|
|
|