Plan Review Details - Permit 17120734
Plan Review Stops For Permit 17120734
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By rmcdouga Date 2017-12-22 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2017-12-21 Time 19:15 Sent To I
Notes
2017-12-22 08:21:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TRUSS DRAWINGS ARE REQUIRED TO HAVE THE TRUSS
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE'S SIGNATURE
 SHALL NOT BE USED. FAC 61G15-23.003
  
 2) THE STURCTURAL ENGINEER OF RECORD FOR THE PROJECT (
 ROBERT EUGENE FETROW ) IS REQUIRED TO REVIEW AND
 APPROVE THE TRUSS LAYOUT PLAN FROM THE DELEGATED
 ENGINEER. FAC61G15-31.003

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-22 Cont ID  
Sent By rmcdouga Date 2017-12-22 Time 09:13 Rev Time 0.00
Received By rmcdouga Date 2017-12-19 Time 12:33 Sent To  
Notes
2017-12-20 12:33:12SUBMITTAL ROUTED TO RMCDOUGAL