Plan Review Details - Permit 17120731
Plan Review Stops For Permit 17120731
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 10:45 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-07 Cont ID  
Sent By aclange Date 2018-03-07 Time 08:02 Rev Time 0.00
Received By aclange Date 2018-03-06 Time 12:49 Sent To  
Notes
2018-03-07 07:58:14****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 SECOND REVIEW:
  
 1. FLOOD ZONE
  
 ADDRESSED. I CAN PROVISO THE ELEVATION CERTIFICATE
 REQUIREMENTS.
  
 2. PERMIT VALUATION
  
 ADDRESSED. THE CHANGE FROM IIB TO VB HAS REDUCED
 CONSTRUCTION COSTS.
  
 3. ADDRESSED. NO LONGER CONSIDERED A SUBSTANTIAL
 IMPROVEMENT.
  
 4. STAIR DETAIL 4/A301.
  
 ADDRESSED.
  
 5. ADDRESSED
  
 6. VAPOR BARRIER.
  
 ADDRESSED.
  
 7. ADA PARKING DETAIL
  
 ADDRESSED
  
 8. PROVIDE AN ACCESSIBLE RAMP.
  
 ADDRESSED
  
 9. ARCHITECT SHALL APPROVE SUPPORTING DOCUMENTS
 INCLUDING, PRODUCT APPROVALS AND GEOTECHNICAL REPORT.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NOT COMPLETELY ADDRESSED. PLEASE REVIEW AND PROVIDE A
 REVIEWED STAMP ON ALL PRODUCT APPROVALS AND
 GEOTECHNICAL REPORT.
  
 A. NEW COMMENT: SELECT THE ROOFING ASSEMBLY TO BE USED
 ON THE PRODUCT APPROVAL AND CHECK TO SEE IF GENERAL
 LIMITATION NUMBER 7 IS APPLICABLE FOR THAT PRODUCT. IF
 IT IS PROVIDE THE ADDITIONAL CALCULATIONS AS SHOWN. SEE
 PAGE 14.
  
 10. NEW COMMENT. SEE PAGE G.001 IT SHOWS FIRE SPRINKLER
 SYSTEM NOTES FOR FORT PIERCE. A FIRE SPRINKLER PERMIT
 HAS BEEN APPLIED FOR AT THE CITY OF WEST PALM BEACH.
 PLEASE UPDATE NOTES AND APPLY SEPARATELY FOR THE FIRE
 SPRINKLER PERMIT.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By aclange Date 2017-12-28 Time 11:19 Rev Time 0.00
Received By aclange Date 2017-12-27 Time 15:40 Sent To  
Notes
2017-12-28 11:08:33****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. FLOOD ZONE
  
 THIS PROPERTY IS IN FLOOD ZONE A.
  
 FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
  
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION IS ON OR AFTER SEPT. 12,2016, AFTER
 OCT. 11, 2017 AN ADDITIONAL ONE FOOT OF FREE BOARD WILL
 BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 FBC 1612.1 GENERAL.
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 AFTER OCTOBER 5TH 2017 THE NGVD HAS BEEN UPDATED TO
 NAVD88. PLEASE UPDATE THE PLANS TO REFLECT THIS AS WELL
 AS THE NEW FREE BOARD.
  
 FBC 1612.4 DESIGN AND CONSTRUCTION.
  
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  
 ELEVATION CERTIFICATES
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 2. PERMIT VALUATION
  
 THE PERMIT VALUE OF $480,000 IS LOW. IT HAS BEEN
 ADJUSTED ACCORDING TO ICC BVD (ICC BUILDING VALUATION
 DATA). CONSTRUCTION TYPE IIB, OCCUPANCY CLASS S 2
 STORAGE IS $87.50 PER SQUARE FOOT. THIS MULTIPLIED BY
 8000 SQUARE FEET IS $700,000.
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
  
 3. THIS PROJECT IS CONSIDERED A SUBSTANTIAL IMPROVEMENT
 SINCE THE PERMIT VALUE IS $700,000 AND THE IMPROVED
 VALUE OF THE EXISTING BUILDING IS $1,085,945 FROM PALM
 BEACH COUNTY PROPERTY APPRAISERS (PAPA).
 SEE FBC CHAPTER 2 DEFINITIONS, SUBSTANTIAL IMPROVEMENT.
  
 PROVISIONS FOR FLOOD HAZARD REDUCTION SEC. 94-546 WEST
 PALM BEACH MUNI CODE.
  
 (A) AREAS OF SPECIAL FLOOD HAZARD GENERALLY. IN ALL
 AREAS OF SPECIAL FLOOD HAZARD, THE FOLLOWING PROVISIONS
 ARE REQUIRED:
  
 (1) ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS
 SHALL BE ANCHORED TO PREVENT FLOTATION, COLLAPSE OR
 LATERAL MOVEMENT OF THE STRUCTURE, AND SHALL BE
 CONSTRUCTED WITH MATERIALS AND UTILITY EQUIPMENT
 RESISTANT TO FLOOD DAMAGE BY METHODS AND PRACTICES THAT
 MINIMIZE FLOOD DAMAGE.
  
 (2) ALL NEW AND REPLACEMENT WATER SUPPLY SYSTEMS AND
 SANITARY SEWAGE SYSTEMS SHALL BE DESIGNED TO MINIMIZE
 OR ELIMINATE INFILTRATION OF FLOOD WATERS INTO THE
 SYSTEMS AND DISCHARGES FROM THE SYSTEMS INTO FLOOD
 WATERS; ON-SITE WASTE DISPOSAL SYSTEMS SHALL BE LOCATED
 TO AVOID IMPAIRMENT TO THEM OR CONTAMINATION FROM THEM
 DURING FLOODING.
  
 (3) ANY ALTERATION, REPAIR, RECONSTRUCTION OR
 IMPROVEMENTS TO A PROPERTY FOR WHICH THE CUMULATIVE
 COST FOR ANY FIVE-YEAR PERIOD EQUALS OR EXCEEDS 50
 PERCENT OF THE BUILDING VALUE AT THE COMMENCEMENT OF
 THE FIVE-YEAR PERIOD SHALL MEET THE REQUIREMENTS OF NEW
 CONSTRUCTION AS CONTAINED IN THIS ARTICLE.
  
 (4) ANY ALTERATION, REPAIR, RECONSTRUCTION OR
 IMPROVEMENTS TO A PROPERTY SHALL NOT CREATE ADVERSE
 STORMWATER IMPACTS TO ADJACENT PROPERTIES.
  
 (B) AREAS OF SPECIAL FLOOD HAZARD WITH BASE FLOOD
 ELEVATION PROVIDED. IN ALL AREAS OF SPECIAL FLOOD
 HAZARD WHERE BASE FLOOD ELEVATION DATA HAS BEEN
 PROVIDED AS SET FORTH IN THIS ARTICLE, THE FOLLOWING
 PROVISIONS ARE REQUIRED:
  
 (2) NONRESIDENTIAL CONSTRUCTION . ALL NEW CONSTRUCTION
 OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL,
 INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL
 EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO THE LEVEL OF ONE FOOT ABOVE THE BASE FLOOD
 ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND
 SANITARY FACILITIES, BE FLOOD PROOFED SO THAT BELOW ONE
 FOOT ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS
 WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE
 PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING
 THE CAPABILITY OF RESISTING HYDROSTATIC AND
 HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A
 REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL
 CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE
 SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE
 CITY ENGINEER.
  
 FBC 1612.1 FLOOD LOADS
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 4. STAIR DETAIL 4/A301.
  
 (A) PROVIDE A HANDRAIL ON BOTH SIDES OF STAIRS. FBC
 1009.15 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE AND SHALL
 COMPLY WITH SECTION 1012.
  
 (B) FBC 1013.4 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
 EXCEPTIONS:
  
 1. FROM A HEIGHT OF 36 INCHES (914 MM) TO 42 INCHES
 (1067 MM), GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 43/8 INCHES (111 MM) IN DIAMETER.
  
 (C) LANDING AT DOOR SHALL HAVE A LENGTH MEASURED IN THE
 DIRECTION OF TRAVEL OF NOT LESS THAN 44 INCHES. FBC
 1008.1.6
  
 5. ALL G AND A PAGES HAVE NOT BEEN SIGNED AND SEALED ON
 BOTH SETS OF PLANS SUBMITTED.
  
 61G1-16.004 TITLE BLOCK. ARCHITECT.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
  
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
  
 6. VAPOR BARRIER USED UNDER SLAB IS SHOWN AS 15 MIL ON
 A-301, 6 MIL ON A-302. THE GEOTECHNICAL REPORT
 RECOMMENDS 10 MIL. PLEASE UPDATE THIS TO THE
 GEOTECHNICAL REPORT RECOMMENDATIONS.
  
 7. ADA PARKING DETAIL ON 4/A-100 SHOWS PARKING SIGN AT
 84 INCHES. THE STATUTE HAS CHANGED AND THE MINIMUM IS
 NOW 60 INCHES FS 553.5041 (6). NO ACTION IS REQUIRED.
  
 8. PROVIDE AN ACCESSIBLE RAMP AT REAR DOOR. RAMP SHALL
 BE IN COMPLIANCE WITH THE FLORIDA ACCESSIBILITY CODE
 405.
  
 9. ARCHITECT SHALL APPROVE SUPPORTING DOCUMENTS
 INCLUDING, PRODUCT APPROVALS AND GEOTECHNICAL REPORT.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-13 Cont ID  
Sent By jpearson Date 2018-03-13 Time 17:07 Rev Time 0.00
Received By jpearson Date 2018-03-13 Time 16:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By jpearson Date 2018-01-30 Time 11:16 Rev Time 0.00
Received By jpearson Date 2018-01-30 Time 09:11 Sent To  
Notes
2018-01-30 11:08:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL CODE REFERENCED ON SHEET G-001 IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 ABOVE)
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
 5. PER FBC EC: . LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS. PROVIDE DETAIL OF COMPLIANCE. FBC EC
 405.2.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2018-03-27 Cont ID  
Sent By Mgonzale Date 2018-03-27 Time   Rev Time 1.00
Received By mgonzale Date 2018-03-27 Time   Sent To I
Notes
2018-03-27 10:57:49NO OBJECTIO TO BUILDING PERMITS BEING ISSUE.
  
 SITE DEVELOPMENT APPROVAL WILL COME THRU ENGINEERING.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 10:40 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 10:40 Sent To  
Notes
2018-03-23 10:40:31***ENGINEERING APPROVAL IS REQUIRED PRIOR TO PERMIT
 ISSUANCE***
  
 1) CIVIL PLANS ARE UNDER REVIEW THROUGH ENGINEERING
 DEVELOPMENT APPROVAL PERMIT NO. E18010040.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-03-20 Cont ID  
Sent By shill Date 2018-03-20 Time 11:55 Rev Time 0.00
Received By shill Date 2018-03-20 Time 11:55 Sent To  
Notes
2018-03-20 11:56:19***ENGINEERING APPROVAL IS REQUIRED PRIOR TO PERMIT
 ISSUANCE***
  
 1) CIVIL PLANS ARE UNDER REVIEW THROUGH ENGINEERING
 DEVELOPMENT APPROVAL PERMIT NO. E18010040.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-02-05 Cont ID  
Sent By squinone Date 2018-02-05 Time   Rev Time 0.00
Received By squinone Date 2018-02-05 Time   Sent To I
Notes
2018-02-05 16:46:081) CIVIL PLANS ARE UNDER REVIEW THROUGH ENGINEERING
 DEVELOPMENT APPROVAL PERMIT NO. E18010040.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-21 Cont ID  
Sent By pleduc Date 2018-02-21 Time   Rev Time 0.00
Received By pleduc Date 2018-02-20 Time 16:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-21 Cont ID  
Sent By wjolin Date 2017-12-21 Time 11:48 Rev Time 0.00
Received By wjolin Date 2017-12-21 Time 10:58 Sent To  
Notes
2017-12-21 11:47:231880 OLD OKEECHOBEE ROAD - WAREHOUSE ADDITION
 PERMIT #17120731
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE TAMPER SWITCHES FOR SUPERVISING THE BACKFLOW
 PREVENTER IN THE OPEN POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 NOTE: SEPARATE SUB PERMITS WILL BE NEEDED FOR THE
 UNDERGROUND FIRE LINE, FIRE SPRINKLER SYSTEM AND
 DEDICATED FUNCTION FIRE ALARM (SPRINKLER MONITORING)
 SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 10:46 Rev Time 0.00
Received By aclange Date 2018-03-21 Time 15:47 Sent To  
Notes
2018-03-22 15:48:05RESUB ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-20 Cont ID  
Sent By shill Date 2018-03-20 Time 11:56 Rev Time 0.00
Received By shill Date 2018-02-16 Time 15:43 Sent To  
Notes
2018-02-20 15:43:58C19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-06 Cont ID  
Sent By cpuell Date 2018-02-06 Time 14:58 Rev Time 0.00
Received By cpuell Date 2017-12-19 Time 13:56 Sent To  
Notes
2017-12-20 13:57:07C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-03-29 Cont ID  
Sent By shill Date 2018-03-29 Time 13:07 Rev Time 0.00
Received By shill Date 2018-03-29 Time 13:07 Sent To  
Notes
2018-03-29 13:08:31MU 18-10446
 $12767.12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 09:52 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 09:52 Sent To  
Notes
2018-03-23 09:53:02 
 IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-502

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-07 Cont ID  
Sent By aclange Date 2018-03-07 Time 07:23 Rev Time 0.00
Received By aclange Date 2018-03-07 Time 07:23 Sent To  
Notes
2018-03-07 07:23:53 
 IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By aclange Date 2017-12-27 Time 15:40 Rev Time 0.00
Received By aclange Date 2017-12-27 Time 15:40 Sent To  
Notes
2017-12-27 15:41:39 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
  
 IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-07 Cont ID  
Sent By ccole Date 2018-03-07 Time 17:17 Rev Time 0.00
Received By ccole Date 2018-03-07 Time 16:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-17 Cont ID  
Sent By ccole Date 2018-01-17 Time 11:11 Rev Time 0.00
Received By ccole Date 2018-01-17 Time 11:10 Sent To  
Notes
2018-01-17 11:19:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120731
 1/17/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: PROVIDE A SEQUENCE OF OPERATION FOR THE ROOF
 FANS.
  
 2) M-1: PROVIDE THE MIAMI-DADE NOA # FOR THE RSF FANS
 ON THE PLAN AND PROVIDE A SHOP DRAWING STAMP ON THE
 NOA.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2018-03-23 Cont ID  
Sent By aclange Date 2018-03-23 Time 10:32 Rev Time 0.00
Received By aclange Date 2018-03-23 Time 10:32 Sent To  
Notes
2018-03-23 10:35:18NOT A SUBSTANTIAL IMPROVEMENT. CONSTRUCTION TYPE VB.
 PROJECT CALCULATED BASED ON THAT CONSTUCTION TYPE.
 RECEIVED ELEVATION CERTIFICATE AE ZONE BFE 12.7. FINISH
 FLOOR OK TO MATCH EXISTING.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By gjohnson Date 2018-03-16 Time 16:17 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By gjohnson Date 2018-01-26 Time 14:52 Rev Time 0.00
Received By gjohnson Date 2018-01-26 Time 10:22 Sent To  
Notes
2018-01-26 15:00:421ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE 4" ROOF DRAIN DRAINING 4253 SQFT SHALL BE A MIN
 OF 5" PER FBC PL TABLE 1106.2(1)
  
 2. PROVIDE DETAIL FOR EMERGENCY SCUPPPER SHALL COMPLY
 WITH FBC 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-01-02 Cont ID  
Sent By rmcdouga Date 2019-01-02 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2019-01-02 Time 13:37 Sent To  
Notes
2019-01-02 13:50:55ROOFING PRODUCT APPROVAL NOA NO. 14-0827.19 FOR TAMKO
 MODIFIED BITUMEN ROOF SYSTEM OVER CONCRETE DECKS WAS
 SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-03-02 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-28 Time 15:45 Sent To  
Notes
2018-03-02 11:01:021.) PRIOR TO THE ISSUANCE OF FINAL CERTIFICATE OF
 OCCUPANCY, A FINAL PLAT FOR THE SUBJECT PROPERTY SHALL
 BE RECORDED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-24 Cont ID  
Sent By PG Date 2018-01-24 Time 14:58 Rev Time 0.00
Received By pgreilic Date 2018-01-19 Time 15:31 Sent To  
Notes
2018-01-24 14:59:101.) PRIOR TO THE ISSUANCE OF FINAL CERTIFICATE OF
 OCCUPANCY, A FINAL PLAT FOR THE SUBJECT PROPERTY SHALL
 BE RECORDED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]