| 2017-12-20 14:43:40 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) PROVIDE THE MANUFACTURE?S SPECIFICATION CUT SHEETS |
| | FOR THIS INSTALLATION ON FIRE FINAL FOR FIRE INSPECTORS |
| | REVIEW. |
| | |
| | PER NFPA 96, |
| | |
| | 11.2 INSPECTION, TESTING, AND MAINTENANCE OF |
| | FIRE-EXTINGUISHING SYSTEMS |
| | |
| | 11.2.2* ALL ACTUATION AND CONTROL COMPONENTS, INCLUDING |
| | REMOTE MANUAL PULL STATIONS, MECHANICAL AND ELECTRICAL |
| | DEVICES, DETECTORS, AND ACTUATORS, SHALL BE TESTED FOR |
| | PROPER OPERATION DURING THE INSPECTION IN ACCORDANCE |
| | WITH THE MANUFACTURER?S |
| | PROCEDURES. |
| | 11.2.3 THE SPECIFIC INSPECTION AND MAINTENANCE |
| | REQUIREMENTS OF THE EXTINGUISHING SYSTEM STANDARDS AS |
| | WELL AS THE APPLICABLE INSTALLATION AND MAINTENANCE |
| | MANUALS FOR THE LISTED SYSTEM AND SERVICE BULLETINS |
| | SHALL BE FOLLOWED. |
| | |
| | PER NFPA 17A |
| | |
| | 6.4 APPROVAL OF INSTALLATIONS. THE COMPLETED SYSTEM |
| | SHALL BE TESTED BY TRAINED PERSONNEL AS REQUIRED BY THE |
| | MANUFACTURER?S LISTED INSTALLATION AND MAINTENANCE |
| | MANUAL. |
| | 6.4.1 THE TESTS SHALL DETERMINE THAT THE SYSTEM HAS |
| | BEEN PROPERLY INSTALLED AND WILL FUNCTION AS INTENDED. |
| | 6.4.2* WHERE REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION, THE APPROVAL TESTS SHALL INCLUDE A |
| | DISCHARGE TEST, IN ACCORDANCE WITH THE MANUFACTURER?S |
| | LISTED INSTALLATION MANUAL, TO VERIFY THAT THE SYSTEM |
| | IS PROPERLY INSTALLED AND FUNCTIONAL. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |