Plan Review Details - Permit 17120629
Plan Review Stops For Permit 17120629
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By dharvey Date 2018-01-18 Time 08:19 Rev Time 0.00
Received By dharvey Date 2018-01-18 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-22 Cont ID  
Sent By aclange Date 2017-12-22 Time 16:08 Rev Time 0.00
Received By aclange Date 2017-12-22 Time 15:49 Sent To  
Notes
2017-12-22 16:08:49****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 1. CHANGE WORK DESCRIPTION ON APPLICATION TO INCLUDE
 THE SCOPE OF WORK THAT IS SHOWN IN JUAN CONTIN?S
 LETTER.
  
 2. REVISE PERMIT VALUE TO INCLUDE ALL PROPOSED AND
 EXISTING WORK THAT IS INCLUDED IN THIS PERMIT.
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 3. PROVIDE DOOR SIZE AND PRODUCT APPROVAL. SUBMIT
 EVALUATION REPORT FOR THIS PRODUCT.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. PROVIDE BATHROOM REMODEL DETAILS. WHAT IS THE SCOPE
 OF THIS REMODEL.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 FBC107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
 5. SEE ELECTRICAL AND PLUMBING REVIEWS FOR ADDITIONAL
 INFORMATION TO INCLUDE WITH YOUR RESUBMITTAL.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-16 Cont ID  
Sent By jpearson Date 2018-01-16 Time 12:11 Rev Time 0.00
Received By jpearson Date 2018-01-16 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By jpearson Date 2017-12-21 Time 12:31 Rev Time 0.00
Received By jpearson Date 2017-12-21 Time 12:31 Sent To B
Notes
2017-12-21 12:31:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 4. PROVIDE FLOOR PLAN SHOWING SMOKE ALARMS IN EACH
 LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-18 Cont ID  
Sent By dharvey Date 2018-01-18 Time 08:19 Rev Time 0.00
Received By dharvey Date 2018-01-12 Time 11:18 Sent To  
Notes
2018-01-16 11:19:11RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-22 Cont ID  
Sent By aclange Date 2017-12-22 Time 16:09 Rev Time 0.00
Received By aclange Date 2017-12-15 Time 12:44 Sent To  
Notes
2017-12-19 12:46:03ROUTED TO PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By tklarge Date 2018-01-18 Time 07:28 Rev Time 0.00
Received By tklarge Date 2018-01-18 Time 07:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By tklarge Date 2017-12-21 Time 10:56 Rev Time 0.00
Received By tklarge Date 2017-12-21 Time 10:43 Sent To E
Notes
2017-12-21 10:44:221) SUBMIT A SANITARY RISER AND WATER RISER DIAGRAM FOR
 REVIEW FOR THE ADDED SHOWER AND FOR THE ADDED WASHING
 MACHINE.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE NEW SHOWER
 VALVE. THE SHOWER VALVE SHALL CCOMPLY WITH 2014 FBCR
 SEC.P2708.3.
 3) SUBMIT INFORMATION AS TO THE TYPE OF SHOWER RECEPTOR
 THAT WAS INSTALLED. COMPLY WITH 2014 FBCR SEC.P2709.
 4) SHOWER WALLS SHALL BE FINISHED IN ACCORDANCE WITH
 2014 FBCR-SECS.P2710.1, R307.2.
 5) SUBMIT MANUF. SPECIFICATIONS FOR THE NEW WATER
 HEATER. WATER HEATERS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 INSTALLATION MANUAL SHALL BE ON THE JOBSITE FOR
 INSPECTION. 2014 FBCR SEC.M2005.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved