Plan Review Details - Permit 17120496
Plan Review Stops For Permit 17120496
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-17 Cont ID  
Sent By eschneid Date 2018-03-17 Time 16:27 Rev Time 0.00
Received By cthroop Date 2018-03-17 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-01-06 Cont ID  
Sent By cthroop Date 2018-01-06 Time 12:59 Rev Time 0.00
Received By cthroop Date 2018-01-06 Time 12:56 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-17 Cont ID  
Sent By cthroop Date 2018-03-17 Time 10:11 Rev Time 0.00
Received By cthroop Date 2018-03-01 Time 11:38 Sent To I
Notes
2018-03-02 11:39:09RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-22 Cont ID  
Sent By cpuell Date 2018-02-22 Time 15:19 Rev Time 0.00
Received By cpuell Date 2018-02-09 Time 09:43 Sent To  
Notes
2018-02-12 09:43:27RESUB ROUTED TO ESCHNEID VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-19 Cont ID  
Sent By eschneid Date 2018-01-19 Time 10:04 Rev Time 0.00
Received By eschneid Date 2017-12-13 Time 11:28 Sent To  
Notes
2017-12-14 11:28:52ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2018-03-14 Cont ID  
Sent By eschneid Date 2018-03-14 Time 16:13 Rev Time 0.25
Received By eschneid Date 2018-03-14 Time 16:13 Sent To B
Notes
2018-03-14 16:13:41THE SHED NEEDS TO BE A MINIMUM OF SIX (6) FEET FROM THE
 COLUMNS FOR THE NEW SCREEN ENCLOSURE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By ES Date 2018-02-22 Time 14:04 Rev Time 0.75
Received By eschneid Date 2018-02-13 Time 11:44 Sent To PC
Notes
2018-02-22 14:23:34FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE PROPOSED SCREEN ENCLOSURE NEEDS
 TO BE SHOWN, WITH ACCURATE SETBACKS, ON THE SURVEY.
  
 2) THE PROPOSED SCREEN ENCLOSURE WITH A SOLID ROOF IS
 CONSIDERED AN EXTENSION OF THE PRIMARY STRUCTURE
 (HOUSE) ON THE PROPERTY. THE SETBACKS ARE MEASURED FROM
 THE SUPPORT COLUMNS. USING A SCALE, THE SOLID ROOF
 SCREEN ENCLOSURE COMPLIES WITH SETBACKS
  
 3) THE CITY PERMITS ACCESSORY STRUCTURES TO HAVE A FIVE
 (5) FOOT SIDE AND REAR SETBACK IF THEY ARE LOCATED MORE
 THAN SIX (6) FEET FROM THE PRIMARY STRUCTURE. THE
 EXISTING SHED CURRENTLY MEETS THAT STANDARD; HOWEVER,
 THE PROPOSED SOLID ROOF SCREEN ENCLOSURE COLUMNS WILL
 BE LESS THEN FIVE (5) FEET FROM THE EXISTING SHED. THIS
 IS ONLY PERMITTED IF THE SHED IS LOCATED AT LEAST 10.8
 FEET FROM THE REAR (WEST) PROPERTY LINE. THE SHED IS
 LOCATED LESS THEN NINE (9) FEET FROM THE REAR PROPERTY
 LINE. THE SHED EITHER NEEDS TO BE REMOVED OR RELOCATED
 TO A LOCATION THAT COMPLIES WITH THE ACCESSORY
 STRUCTURE SETBACKS. A PERMIT WILL BE REQUIRED FOR THE
 REMOVAL OR RELOCATION OF THE SHED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-19 Cont ID  
Sent By ES Date 2018-01-19 Time 09:43 Rev Time 0.50
Received By eschneid Date 2018-01-19 Time 09:43 Sent To  
Notes
2018-01-19 10:00:04FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR
 OLD, SHOWING THE CURRENT IMPROVEMENTS TO THE PROPERTY.
 THE SUBMITTED SURVEY IS FROM 1954 AND DOES NOT SHOW THE
 CURRENT LAYOUT OF THE HOUSE AND THE OTHER FEATURES ON
 THE LOT.
  
 2) THE PROPOSED SCREEN ENCLOSURE NEEDS TO BE SHOWN,
 WITH ACCURATE DIMENSIONS AND SETBACKS, ON THE SURVEY.
  
 3) THE AERIAL SHOWS A TREE IN THE VICINITY OF THE
 PROPOSED SCREEN ENCLOSURE. ARE YOU PLANNING TO REMOVE A
 TREE(S) OR SHRUBS AS PART OF THE ADDITION?
  
 4) MORE COMMENTS MAY BE GENERATED WITH THE SUBMITTAL OF
 THE CURRENT SURVEY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]