Plan Review Details - Permit 17120495
Plan Review Stops For Permit 17120495
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-02 Cont ID  
Sent By jwitmer Date 2018-04-02 Time 11:50 Rev Time 0.00
Received By jwitmer Date 2018-04-02 Time 07:37 Sent To  
Notes
2018-04-02 11:50:33OCCUPANCY: A-2
 BUILDING TYPE: II-B
 SPRINKLERED
 3520 SQ. FT.
 145 OCCUPANT LOAD
 FLOOD ZONE-NO
 2 RESTROOMS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-23 Cont ID  
Sent By jwitmer Date 2018-02-23 Time 15:32 Rev Time 0.00
Received By jwitmer Date 2018-02-23 Time 11:52 Sent To  
Notes
2018-02-23 15:32:322014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120495
 W. P. B. PERMIT: 17060769 (SHELL)
 ADD: 1560 PALM BEACH LAKES BLVD. SUITE # 08
 CONT: U.S. CONSTRUCTION
 TEL: 407-399-4630
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI. FEB. 23/ 2018
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SEMI-COMPLIED. SHEET A1.0. THE ACCESSIBLE SEATING AT
 THE COUNTER SHOWING A DROPPED SECTION WITH PIANO HINGE
 IS NOT EQUIVALENT FACILITATION AS REQUIRED BY THE
 FLORIDA ACCESSIBILITY CODE SECTION 103.
 A PORTION OF THE COUNTER WILL NEED TO BE DROPPED TO
 SHOW COMPLIANCE WITH THE ACCESSIBILITY CODE SECTION:
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, BUT
 ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND
 BOOTHS.
 PLEASE ALSO SHOW AT LEAST ONE ACCESSIBLE BOOTH AND
 COMPLIANCE WITH 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES..
  
 2)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1ST ROUND COMMENTS. SHEET A1.0 SHOWS APPROXIMATELY 130
 SEATS ON BOTH THE INTERIOR AND EXTERIOR OF THE A2
 OCCUPANCY AND OF THESE SEATS 7 SEATS ARE ACCESSIBLE
 MEETING THE 5% ACCESSIBLE SEATING. WHAT THE FLOOR PLAN
 DOES NOT SHOW IS DISPERSION BETWEEN TYPE OF DINING,
 SUCH AS BANQUETS AND STOOLS; NONE OF THESE ELEMENTS
 SHOW ACCESSIBLE SEATING.
 2014 FBC-ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 3-4) COMPLIED.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 10:52 Sent To  
Notes
2017-12-19 15:50:312014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120495
 W. P. B. PERMIT: 17060769 (SHELL)
 ADD: 1560 PALM BEACH LAKES BLVD. SUITE # 08
 CONT: U.S. CONSTRUCTION
 TEL: 407-399-4630
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. DEC. 19/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET CS1 INDICATES THIS BUILDING IS
 DESIGNED UNDER THE 2014 FBC-EXISTING BUILDING CODE AND
 AS AN ALTERATION LEVEL II. PLEASE REVIEW BUILDINGS THAT
 WERE NEVER PREVIOUSLY OCCUPIED ARE TO BE DESIGNED &
 REVIEW UNDER THE:
 2014 FBC-BUILDING. 101.4.1 BUILDINGS NOT PREVIOUSLY
 OCCUPIED. A BUILDING OR PORTION OF A BUILDING THAT HAS
 NOT BEEN PREVIOUSLY OCCUPIED OR USED FOR ITS INTENDED
 PURPOSE IN ACCORDANCE WITH THE LAWS IN EXISTENCE AT THE
 TIME OF ITS COMPLETION SHALL COMPLY WITH THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING OR FLORIDA
 BUILDING CODE, RESIDENTIAL, AS APPLICABLE, FOR NEW
 CONSTRUCTION OR WITH ANY CURRENT PERMIT FOR SUCH
 OCCUPANCY.
 PLEASE DELETE THE REFERENCE TO THE EXISTING BUILDING
 CODE AND LEVEL II ALTERATION.
  
 2) SHEET A1.0 SHOWS APPROXIMATELY 130 SEATS ON BOTH THE
 INTERIOR AND EXTERIOR OF THE A2 OCCUPANCY AND OF THESE
 SEATS 7 SEATS ARE ACCESSIBLE MEETING THE 5% ACCESSIBLE
 SEATING. WHAT THE FLOOR PLAN DOES NOT SHOW IS
 DISPERSION BETWEEN TYPE OF DINING, SUCH AS BANQUETS AND
 STOOLS; NONE OF THESE ELEMENTS SHOW ACCESSIBLE SEATING.
 2014 FBC-ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 3) SHEET A2.1 AND A2.2 SHOWS AWNINGS AND SIGNAGE, BOTH
 OF THESE ITEMS REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.1 PERMITS REQUIRED.
  
 4A) SHEET A4.2 DETAIL 2 AND SHEET M3.1 SHOW THE
 INSTALLATION OF A ROOF TOP CONDENSING STAND PLEASE SHOW
 COMPLIANCE WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4C) THE ROOF TOP A/C STAND PRODUCT APPROVALS. PLEASE
 IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE
 AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-05 Cont ID  
Sent By jpearson Date 2018-03-05 Time 09:41 Rev Time 0.00
Received By jpearson Date 2018-03-05 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By jpearson Date 2018-01-02 Time 15:49 Rev Time 0.00
Received By jpearson Date 2018-01-02 Time 15:49 Sent To  
Notes
2018-01-02 15:49:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET EO.1, NOTE 10 REFERENCES NEC 250.95 FOR
 EQUIPMENT GROUNDING CONDUCTOR SIZE. THIS CODE SECTION
 DOES NOT EXIST IN THE 2011 NEC. PROVIDE CORRECTION. NEC
 250.122; FBC 107.2.1
 2. RISER SHOWS AN EXISTING SERVICE, BUT THE PROPERTY
 APPRAISER'S SITE SHOWS THIS AS A VACANT LOT. WHAT IS
 EXISTING ON SITE? IF THIS IS FED FROM AN EXISTING
 SERVICE, PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE.
 PROVIDE CLARIFICATION. NEC 220, FBC 107.2.1
 3. PROVIDE GROUNDING ELECTRODE SYSTEM AND CONDUCTORS
 PER CODE. PROVIDE DETAIL ON PLAN. NEC 250.50, 250.66;
 FBC 107.2.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. IT APPEARS THAT THE PANEL SCHEDULES HAVE NOT BEEN
 COMPLETELY FILLED OUT. DOES PANEL A HAVE A MAIN
 BREAKER, OR WILL THERE BE A DISCONNECT OUTSIDE? PROVIDE
 CLARIFICATION. FBC 107.2.1; NEC 230.71
 8. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 9. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE
 IN RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
 10. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2,
 405.2.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-03-30 Cont ID  
Sent By scaldero Date 2018-03-30 Time 11:42 Rev Time 0.00
Received By scaldero Date 2018-03-30 Time 11:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-15 Cont ID  
Sent By scaldero Date 2018-02-15 Time 12:05 Rev Time 0.00
Received By scaldero Date 2018-02-15 Time 12:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-20 Cont ID  
Sent By wjolin Date 2017-12-20 Time 14:52 Rev Time 0.00
Received By wjolin Date 2017-12-20 Time 14:31 Sent To  
Notes
2017-12-20 14:51:581560 PALM BEACH LAKES BOULEVARD - SUITE #8
 PERMIT #17120495
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED,
 THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2018-04-09 Time 17:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By gjohnson Date 2018-03-08 Time 12:24 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2018-03-08 12:35:562ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BTU LOAD FOR THE FRYER DOES NOT MATCH , ON THE
 COMBUSTION AIR CALCS IT LIST 330 MBTU ON THE RISER IT
 LIST 360 MBTU.PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1
  
 2. THE RISER AND EQUIPMENT SCHEDULE LIST THE CONVECTION
 OVEN AT 100 MBTU THE MANUFACTURE SPECS LIST 88 MBTU.
 PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 3. THE RISER AND EQUIPMENT SCHEDULE LIST THE1 FRYER AT
 360 MBTU THE MANUFACTURE SPECS LIST MODEL SG14 AT110
 MBTU.PLEASE CLARIFY PER WPB AMEND TO FBC 107.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By gjohnson Date 2018-01-08 Time 15:18 Rev Time 0.00
Received By gjohnson Date 2018-01-08 Time 15:18 Sent To  
Notes
2018-01-08 15:22:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. PER FBC FG
 408.4
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-10 Cont ID  
Sent By hmoser Date 2018-04-10 Time 08:22 Rev Time 0.00
Received By hmoser Date 2018-03-28 Time 13:32 Sent To  
Notes
2018-03-29 13:32:14B32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-13 Cont ID  
Sent By cpuell Date 2018-03-13 Time 17:52 Rev Time 0.00
Received By cpuell Date 2018-02-13 Time 13:44 Sent To  
Notes
2018-02-14 13:46:09C06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By cpuell Date 2018-01-22 Time 15:22 Rev Time 0.00
Received By cpuell Date 2017-12-13 Time 14:45 Sent To  
Notes
2017-12-14 14:45:26C18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-04-02 Cont ID  
Sent By jwitmer Date 2018-04-02 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2018-04-02 Time 10:42 Sent To  
Notes
2018-04-02 10:59:52PALM BEACH COUNTY IMPACT FEE OFFICE
 DATE RECEIVED: 03/28/2018
 RECEIPT NUMBER: 2018-0328-274
 TRACKING NUMBER: MU-2018-003337-0000
 TOTAL AMOUNT: $4,954.99
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-02-23 Cont ID  
Sent By jwitmer Date 2018-02-23 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2018-02-23 Time 15:13 Sent To  
Notes
2018-02-23 15:13:56IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 15:51 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 13:17 Sent To  
Notes
2017-12-19 15:51:091) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-10 Cont ID  
Sent By hmoser Date 2018-04-10 Time 08:22 Rev Time 0.00
Received By hmoser Date 2018-04-10 Time 07:56 Sent To  
Notes
2018-04-10 08:22:04PASS PROVISO
 SEPARATE APPLICATION, PLANS, AND PERMITS REQUIRED
 FOR HOODS, AND COOLERS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 516-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 09:38 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 08:59 Sent To  
Notes
2018-02-28 10:22:582ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120495
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1 COMBUSTION AIR CALCULATION: PLEASE REFER
 TO SHEETS CS1 AND A1.3. BASED ON THE 3520 SQ. FT. AREA
 AND AN AVERAGE CEILING HEIGHT OF 9'6" THE MAXIMUM
 VOLUME OF THE SPACE IN CUBIC FEET WOULD BE 33,440. THAT
 TOTAL WOULD ALSO BE CUT DRASTICALLY WHEN DEDUCTING
 CLOSED OFF SPACES SUCH AS THE RESTROOMS, STORAGE, AND
 OFFICE ROOMS ETC. HOW ARE YOU CALCULATING THE
  
 INDOOR VOLUME AT 46.392 FT3. IT DOES NOT SEEM
 PHYSICALLY POSSIBLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By ccole Date 2017-12-27 Time 12:30 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 11:49 Sent To  
Notes
2017-12-27 12:57:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120495
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DUE TO THE LOW WALLS SEPARATING THE KITCHEN AND THE
 DINING ROOMS, IT APPEARS THAT SOME OF THE AIR SUPPLIED
 TO THE KIITCHEN WILL BE RECIRCULATED INTO THE DINING
 ROOM WHICH IS PROHIBITED- TABLE 403.3 FOOTNOTE B.
  
 2) PROVIDE COMBUSTION FOR THE COOKING APPLIANCES AND
 SHOW HOW THE AIR WILL BE PROVIDED- SEE SECTION 304
 FBC-14 FUEL GAS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS,
 THE FIRE SUPPRESSION SYSTEMS, AND THE WALK-IN COOLER
 AND FREEZER. PLEASE PLACE A NOTE ON THE PLAN.
  
 ADVISORY- KITCHEN HOOD PLANS: COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE WILL BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 17:07 Rev Time 0.00
Received By gjohnson Date 2018-04-09 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By gjohnson Date 2018-03-08 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2018-03-08 Time 11:47 Sent To  
Notes
2018-03-08 12:23:46 
 2ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GREASE INTERCEPTOR SIZING CALCULATIONS SHALL
 INCLUDE ALL THE FLOOR DRAINS, FLOOR SINKS, TROUGH
 DRAINS AND HUBDRAINS RECEIVING DISCHARGE OF GREASY
 WASTE SUCH AS THE KETTLE.AND HOT WELLS OR USE THE
 SIZING METHOD FOR RESTAURANT USING THE NUMBER OF SEATS
 X GALLONS PER SEAT X HR OF OPERATION X LOAD FACTOR. PER
 FBC PL 1003.2, 1003.3.1
  
 2. ON THE WATER RISER SHUT OFF VALVES ARE REQUIRED ON
 ALL DROPS A NOTE ON THE PLAN SHALL COMPLY. PER FBC PL
 606.1(5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By gjohnson Date 2018-01-08 Time 14:53 Rev Time 0.00
Received By gjohnson Date 2018-01-08 Time 07:35 Sent To  
Notes
2018-01-08 15:12:061ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE IF MEASURED TO CENTERLINE OF BAR TO
 THE MAX OF 36" BARS WILL BE INSTALLED TO HIGH. PER FBC
 ACC 609.4
  
 2. SHT. A7.1-7.2 DETAILS SHOWS HORIZONTAL GRAB BARS PER
 FBC ACC 909.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION,
  
 3. SHT. P1.1 SHOWS 3 GREASE INTERCEPTORS THE APPROVED
 PLANS FOR BUILDING SHELL SHOW FOUR GREASE INTERCEPTORS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. THE SANITARY ISOMETRIC IS TO COMPACT TO DETERMINE
 CODE COMPLIANCE PLEASE EXPAND AND SEPARATE THE SANITARY
 AND GREASE ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC
 107.2.1
  
 5. PROVIDE WATER ISOMETRIC SHOWING PIPE SIZE, ALL
 VALVES, HAMMER ARESTORS AND BACK FLOWS. PER WPB AMEND
 TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-13 Cont ID  
Sent By jroach Date 2018-03-13 Time 15:48 Rev Time 0.00
Received By jroach Date 2018-03-13 Time 15:48 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By JR Date 2018-01-22 Time 14:14 Rev Time 0.00
Received By jroach Date 2018-01-16 Time 14:51 Sent To PC
Notes
2018-01-22 14:15:04ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.22.2018
 PERMIT NO.: 17120495
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. STAFF IS CONCERNED WITH REGARD TO THE ?BLACKOUT? AND
 ?NEW WALL? THAT IS PROPOSED TO BE CONSTRUCTED BEHIND
 NEARLY EVERY ONE OF THE STOREFRONT WINDOWS THAT WERE
 APPROVED THROUGH THE MAJOR PLANNED DEVELOPMENT
 AMENDMENT PROCESS. THESE STOREFRONTS WERE SPECIFICALLY
 ADDED DURING APPROVAL PROCESS FOR THE SITE PLAN AND IT
 IS COUNTERINTUITIVE TO HAVE EACH OF THEM BLOCKED OFF.
 STAFF WOULD LIKE TO DISCUSS THIS MATTER TO SEE IF THERE
 ARE ALTERNATIVES THAT WOULD MAINTAIN TRANSPARENCY INTO
 THE SPACE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved