Plan Review Details - Permit 17120453
| Plan Review Stops For Permit 17120453 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-01-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-23 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-09 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2018-01-10 12:49:34 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-01-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-21 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2017-12-22 09:28:14 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-12 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2017-12-13 14:07:08 | REVISION ROUTED TO CCOLE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-01-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-23 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-23 |
Time |
14:40 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-01-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-03 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-03 |
Time |
15:39 |
Sent To |
I |
|
| Notes |
| 2018-01-03 17:14:45 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120453 | | | 1/3/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: PLEASE CLARIFY HOW AIR IS BEING RETURNED | | | FROM BEDROOMS 1 & 2. | | | | | | 2) M-1: PLEASE CLARIFY IF THE DUCT SHAFTS BY THE | | | ELEVATOR ARE FIRE-RATED SHAFTS. PLEASE NOTE FIRE | | | DAMPERS MAY BE REQUIRED FOR DUCT PENETRATIONS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-19 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-19 |
Time |
09:50 |
Sent To |
I |
|
| Notes |
| 2017-12-19 09:55:48 | 1ST REVIEW FBC-2014 MECHANICAL , WEST PALM BEACH | | | AMENDMENTS TO THE FBC | | | PERMIT #17120453 | | | 12/19/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MINIMUM 1/8"=1'0" SCALE REQUIRED FOR PLANS- SECTION | | | 107.2.1.4 WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|