Plan Review Details - Permit 17120442
Plan Review Stops For Permit 17120442
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-02-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-26 Time 13:15 Sent To  
Notes
2018-01-29 13:15:50RESUB OF REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-01-16 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-09 Time 10:49 Sent To  
Notes
2018-01-10 10:50:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-12-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-19 Time 11:34 Sent To  
Notes
2017-12-20 11:34:57RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-12-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-12 Time 13:49 Sent To  
Notes
2017-12-13 13:50:08REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-02-02 Cont ID  
Sent By ccole Date 2018-02-02 Time 15:17 Rev Time 0.00
Received By ccole Date 2018-02-02 Time 15:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-01-16 Cont ID  
Sent By ccole Date 2018-01-16 Time 12:22 Rev Time 0.00
Received By ccole Date 2018-01-16 Time 12:22 Sent To I
Notes
2018-01-16 12:28:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120442
 1/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC SYSTEM HAS BEEN CHANGED FROM A 2.5 TON TO A
 3.0 SYSTEM, HOWEVER THE PLAN IS INDICATING 1000 CFMS OF
 SUPPLY AIR AND NOT 1200 CFMS AS THE NEW SCHEDULE SHOWS.
  
 2) REVISE THE ENERGY COMPLIANCE FORM TO SHOW THE NEW
 SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By ccole Date 2017-12-27 Time 15:32 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 15:32 Sent To I
Notes
2017-12-27 15:37:092ND REVIEW FBC-2014 MECHANICAL
 REVISION #17120442
 MASTER #16080345
 12/27/17
  
 1) THE REVISED M-1 SHEET IS MISSING ALL OF THE DETAILS
 AND NOTES THAT WERE PROVIDED ON THE APPROVED SHEET.
 PLEASE PROVIDE A COMPLETE REVISED PLAN SHEET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By ccole Date 2017-12-18 Time 09:22 Rev Time 0.00
Received By ccole Date 2017-12-18 Time 07:45 Sent To I
Notes
2017-12-18 09:25:421ST REVIEW FBC-2014 MECHANICAL
 REVISION #17120442
 MASTER #16080345
 12/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMTTED PLANS ARE FOR A POMPANO BEACH PROJECT.
 PLEAE PROVIDE REVISED PLANS FOR 801 BRADLEY, WPB.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  