Plan Review Details - Permit 17120442
| Plan Review Stops For Permit 17120442 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-02-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-01-26 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2018-01-29 13:15:50 | RESUB OF REVISION ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-01-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-01-09 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2018-01-10 10:50:00 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-19 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2017-12-20 11:34:57 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-12 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2017-12-13 13:50:08 | REVISION ROUTED TO CCOLE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-02-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-02-02 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-02-02 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-01-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-16 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-16 |
Time |
12:22 |
Sent To |
I |
|
| Notes |
| 2018-01-16 12:28:37 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120442 | | | 1/16/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC SYSTEM HAS BEEN CHANGED FROM A 2.5 TON TO A | | | 3.0 SYSTEM, HOWEVER THE PLAN IS INDICATING 1000 CFMS OF | | | SUPPLY AIR AND NOT 1200 CFMS AS THE NEW SCHEDULE SHOWS. | | | | | | 2) REVISE THE ENERGY COMPLIANCE FORM TO SHOW THE NEW | | | SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-12-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-27 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-27 |
Time |
15:32 |
Sent To |
I |
|
| Notes |
| 2017-12-27 15:37:09 | 2ND REVIEW FBC-2014 MECHANICAL | | | REVISION #17120442 | | | MASTER #16080345 | | | 12/27/17 | | | | | | 1) THE REVISED M-1 SHEET IS MISSING ALL OF THE DETAILS | | | AND NOTES THAT WERE PROVIDED ON THE APPROVED SHEET. | | | PLEASE PROVIDE A COMPLETE REVISED PLAN SHEET. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-12-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-18 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-18 |
Time |
07:45 |
Sent To |
I |
|
| Notes |
| 2017-12-18 09:25:42 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #17120442 | | | MASTER #16080345 | | | 12/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMTTED PLANS ARE FOR A POMPANO BEACH PROJECT. | | | PLEAE PROVIDE REVISED PLANS FOR 801 BRADLEY, WPB. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|