Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By tklarge Date 2017-12-28 Time 13:50 Rev Time 0.00
Received By tklarge Date 2017-12-28 Time 12:30 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-12-19 Cont ID  
Sent By thunt Date 2017-12-19 Time 06:34 Rev Time 0.00
Received By thunt Date 2017-12-19 Time 06:34 Sent To  
Notes
2017-12-19 06:48:1912/18/2018 1ST GAS REVIEW **DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 3) MISSING .5LB GALV SIZING TABLES. SUBMIT TWO COPIES
 OF THE APPLICABLE SIZING TABLES USED TO SIZE THE GAS
 SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING
 WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER
 STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4,
 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3.
  
 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4.
  
 5) ) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
  
 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD
  
 7) ALL FUTURE ITEMS WILL BE REQUIRED TO HAVE THE LISTED
 VALVE, THREADED NIPPLE, GAS REGULATOR, AND THEN A
 THREADED CAP G404.15
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-28 Cont ID  
Sent By tklarge Date 2017-12-28 Time 13:50 Rev Time 0.00
Received By tklarge Date 2017-12-27 Time 14:26 Sent To I
Notes
2017-12-27 14:26:44THUNT'S DESK AKA TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-19 Cont ID  
Sent By thunt Date 2017-12-19 Time 06:48 Rev Time 0.00
Received By thunt Date 2017-12-11 Time 13:21 Sent To  
Notes
2017-12-12 13:21:44PLUMB <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved