Plan Review Details - Permit 17120353
Plan Review Stops For Permit 17120353
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-03-27 Cont ID  
Sent By aclange Date 2018-03-27 Time 08:56 Rev Time 0.00
Received By aclange Date 2018-03-27 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-02-23 Cont ID  
Sent By aclange Date 2018-02-23 Time 12:45 Rev Time 0.00
Received By aclange Date 2018-02-23 Time 10:48 Sent To  
Notes
2018-02-23 12:45:17****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 THIRD PLAN REVIEW:
  
  
 NOT UPDATED ON ALL AREAS ON A-1
  
 PARTIALLY ADDRESSED. NOT UPDATED UNDER OCCUPANY
 CLASSIFICATION.
 (B) UPDATE SQUARE FOOTAGE IT IS SHOWN AS 600 SQ. FT.
 BUT IS ACTUALLY 586.4 SQ. FT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
 5. ACCESSIBILITY:
  
  
 TABLE HEIGHT TOO HIGH. MAXIMUM HEIGHT IS 34"
  
 PARTIALLY ADDRESSED. TABLE HEIGHT NOT SHOWN.
 (C) SHOW HOW THE DINING AREA WILL COMPLY WITH 902.1
 GENERAL.
 DINING SURFACES AND WORK SURFACES SHALL COMPLY WITH
 902.2 AND 902.3.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
  
 NEW WALLS SHOWN ON EXISTING FLOOR PLAN
 NOT ADDRESSED.
 (B ) LABEL ALL WALLS ON PLANS SHOW NEW AND EXISTING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 FBC107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-01-18 Cont ID  
Sent By aclange Date 2018-01-18 Time 13:36 Rev Time 0.00
Received By aclange Date 2018-01-18 Time 13:16 Sent To  
Notes
2018-01-18 13:35:54****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 SECOND PLAN REVIEW:
  
 OCCUPANY CLASSIFICATION OK.
 1. OCCUPANCY SHOWN ON PLANS IS SHOWN AS B2. IF THIS WAS
 RETAIL PREVIOUSLY THIS WAS A B OCCUPANCY. NOW AS A
 RESTAURANT THE CURRENT OCCUPANCY CLASSIFICATION IS A-2
 RESTAURANT.
 FBC 303.3 ASSEMBLY GROUP A-2.
  
 ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK
 CONSUMPTION INCLUDING, BUT NOT LIMITED TO:
  
 RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES
 (INCLUDING ASSOCIATED COMMERCIAL KITCHENS).
  
 NOT ADDRESSED.
 A) SHOW COMPLIANCE FOR CHANGE OF USE WITH THE EXISTING
 BUILDING CODE [A] 101.2 SCOPE.
 THE PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING
 BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION AND RELOCATION OF EXISTING
 BUILDINGS.
  
 NOT ADDRESSED.
 B) CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
 C101.4.8 EXEMPT BUILDINGS.
  
 BUILDINGS EXEMPT FROM THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, ENERGY CONSERVATION, INCLUDE EXISTING
 BUILDINGS EXCEPT THOSE CONSIDERED RENOVATED BUILDINGS,
 CHANGES OF OCCUPANCY TYPE, OR PREVIOUSLY UNCONDITIONED
 BUILDINGS TO WHICH COMFORT CONDITIONING IS ADDED.
 EXEMPT BUILDINGS INCLUDE THOSE SPECIFIED IN SECTIONS
 C101.4.8.1 THROUGH C101.4.8.4.
  
 NOT ADDRESSED.
 2. SHOW IN YOUR PROJECT DATA THE LEVEL OF ALTERATION
 THAT IS SELECTED. FBC EXISTING BUILDING CODE 407 AND
 501.
  
 A) SHOW ALSO THE COMPLIANCE WITH FBC EXISTING BUILDING
 1001 CHANGE OF OCCUPANCY.
  
 OK. ADDRESSED.
 3. (A) UPDATE TRAVEL DISTANCE ON PLANS. IT IS SHOWN AS
 46 FEET BUT MEASURES APPROXIMATELY 53 FEET.
  
 PARTIALLY ADDRESSED. NOT UPDATED UNDER OCCUPANY
 CLASSIFICATION.
 (B) UPDATE SQUARE FOOTAGE IT IS SHOWN AS 600 SQ. FT.
 BUT IS ACTUALLY 586.4 SQ. FT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 OK. ADDRESSED.
 4. UPDATE CODE DATA TO REFLECT 2014 FLORIDA PLUMBING
 CODE 5TH EDITION AND NFPA 2014 5TH EDITION.
  
  
 5. ACCESSIBILITY:
  
 NOT ADDRESSED.
 (A) DOOR AT THE BATHROOM SHALL HAVE MANEUVERING
 CLEARANCES IN COMPLIANCE WITH FLORIDA ACCESSIBILITY
 CODE 5TH EDITION.
 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 PARTIALLY ADDRESSED. THE 12" AT THE LATCH SIDE IS
 SHOWN. SEE 404.2.4.1 DETAILS (A) AND (D) FOR 60 INCHES
 CLEAR.
 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1. DETAIL (A)
 AND (C).
  
 NOT ADDRESSED.
 (B) PROVIDE SCALED ELEVATIONS FOR WORK AREA AND
 CUSTOMER SERVICE COUNTER AREAS. SHOW COMPLIANCE WITH
 203.9 EMPLOYEE WORK AREAS AND 904.4.
 904 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS
 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF 904.
  
 PARTIALLY ADDRESSED. TABLE HEIGHT NOT SHOWN.
 (C) SHOW HOW THE DINING AREA WILL COMPLY WITH 902.1
 GENERAL.
 DINING SURFACES AND WORK SURFACES SHALL COMPLY WITH
 902.2 AND 902.3.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 NOT ADDRESSED.
 6. (A) CLARIFY THE SCOPE OF WORK ON THE PLANS AND
 PERMIT APPLICATION. IT IS SHOWN AS EXISTING RETAIL
 SPACE BUT THE 1 HOUR WALL DETAIL IS SHOWING THE TENANT
 SEPARATION WALLS AS NEW.
  
 NOT ADDRESSED.
 (B ) LABEL ALL WALLS ON PLANS SHOW NEW AND EXISTING.
  
 NOT ADDRESSED.
 (C) BATHROOM IS SHOWN AS AN UPGRADE BUT INCLUDES NEW
 WALLS AND A COMPLETE RECONFIGURATION OF PLUMBING
 FIXTURES.
  
 OK SHOWN ON PLANS.
 (D) SHOW ADJACENT TENANT SPACE USE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 FBC107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By aclange Date 2018-02-22 Time 15:24 Rev Time 0.00
Received By aclange Date 2018-01-18 Time 11:22 Sent To  
Notes
2018-02-22 15:24:40STOP LOCKED SEE OTHER REVIEW FROM 1/18/18.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By aclange Date 2017-12-14 Time 10:49 Rev Time 0.00
Received By aclange Date 2017-12-13 Time 13:56 Sent To  
Notes
2017-12-14 10:47:06****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. OCCUPANCY SHOWN ON PLANS IS SHOWN AS B2. IF THIS WAS
 RETAIL PREVIOUSLY THIS WAS A B OCCUPANCY. NOW AS A
 RESTAURANT THE CURRENT OCCUPANCY CLASSIFICATION IS A-2
 RESTAURANT.
 FBC 303.3 ASSEMBLY GROUP A-2.
  
 ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK
 CONSUMPTION INCLUDING, BUT NOT LIMITED TO:
  
 RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES
 (INCLUDING ASSOCIATED COMMERCIAL KITCHENS).
  
 A) SHOW COMPLIANCE FOR CHANGE OF USE WITH THE EXISTING
 BUILDING CODE [A] 101.2 SCOPE.
 THE PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING
 BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION AND RELOCATION OF EXISTING
 BUILDINGS.
  
 B) CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
 C101.4.8 EXEMPT BUILDINGS.
  
 BUILDINGS EXEMPT FROM THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, ENERGY CONSERVATION, INCLUDE EXISTING
 BUILDINGS EXCEPT THOSE CONSIDERED RENOVATED BUILDINGS,
 CHANGES OF OCCUPANCY TYPE, OR PREVIOUSLY UNCONDITIONED
 BUILDINGS TO WHICH COMFORT CONDITIONING IS ADDED.
 EXEMPT BUILDINGS INCLUDE THOSE SPECIFIED IN SECTIONS
 C101.4.8.1 THROUGH C101.4.8.4.
  
 2. SHOW IN YOUR PROJECT DATA THE LEVEL OF ALTERATION
 THAT IS SELECTED. FBC EXISTING BUILDING CODE 407 AND
 501.
  
 A) SHOW ALSO THE COMPLIANCE WITH FBC EXISTING BUILDING
 1001 CHANGE OF OCCUPANCY.
  
 3. (A) UPDATE TRAVEL DISTANCE ON PLANS. IT IS SHOWN AS
 46 FEET BUT MEASURES APPROXIMATELY 53 FEET.
  
 (B) UPDATE SQUARE FOOTAGE IT IS SHOWN AS 600 SQ. FT.
 BUT IS ACTUALLY 586.4 SQ. FT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4. UPDATE CODE DATA TO REFLECT 2014 FLORIDA PLUMBING
 CODE 5TH EDITION AND NFPA 2014 5TH EDITION.
  
 5. ACCESSIBILITY:
  
 (A) DOOR AT THE BATHROOM SHALL HAVE MANEUVERING
 CLEARANCES IN COMPLIANCE WITH FLORIDA ACCESSIBILITY
 CODE 5TH EDITION.
 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1. DETAIL (A)
 AND (C).
  
 (B) PROVIDE SCALED ELEVATIONS FOR WORK AREA AND
 CUSTOMER SERVICE COUNTER AREAS. SHOW COMPLIANCE WITH
 203.9 EMPLOYEE WORK AREAS AND 904.4.
 904 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS
 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF 904.
  
 (C) SHOW HOW THE DINING AREA WILL COMPLY WITH 902.1
 GENERAL.
 DINING SURFACES AND WORK SURFACES SHALL COMPLY WITH
 902.2 AND 902.3.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 6. (A) CLARIFY THE SCOPE OF WORK ON THE PLANS AND
 PERMIT APPLICATION. IT IS SHOWN AS EXISTING RETAIL
 SPACE BUT THE 1 HOUR WALL DETAIL IS SHOWING THE TENANT
 SEPARATION WALLS AS NEW.
  
 (B ) LABEL ALL WALLS ON PLANS SHOW NEW AND EXISTING.
  
 (C) BATHROOM IS SHOWN AS AN UPGRADE BUT INCLUDES NEW
 WALLS AND A COMPLETE RECONFIGURATION OF PLUMBING
 FIXTURES.
  
 (D) SHOW ADJACENT TENANT SPACE USE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 FBC107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-05 Cont ID  
Sent By jpearson Date 2018-03-05 Time 14:04 Rev Time 0.00
Received By jpearson Date 2018-03-05 Time 14:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-30 Cont ID  
Sent By jpearson Date 2018-01-30 Time 14:09 Rev Time 0.00
Received By jpearson Date 2018-01-30 Time 14:09 Sent To  
Notes
2018-01-30 14:02:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5.2 (NEED TO SHOW THE ALLOWED WATTAGE
 FOR THIS SPACE)
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. PLAN NEEDS TO SHOW
 LOCATION AND DESIGN OF CONTROL. FBC EC 405.2.2,
 405.2.2.2 (I DO NOT SEE ANY AUTOMATIC CONTROL FOR THE
 MAIN AREA, PROVIDE CONTROL FOR ALL LIGHTING.)
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By jpearson Date 2017-12-27 Time 16:10 Rev Time 0.00
Received By jpearson Date 2017-12-27 Time 16:10 Sent To  
Notes
2017-12-27 16:10:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5.2
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. PLAN NEEDS TO SHOW
 LOCATION AND DESIGN OF CONTROL. FBC EC 405.2.2,
 405.2.2.2
 3. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER CODE. NEC
 210.62
 4. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN KITCHEN /
 PREP AREAS. NEC 210.8
 5. PROVIDE LIGHTING CONTROLS FOR SIGN CIRCUIT AND SHOW
 WINDOW CIRCUIT. PER CODE: "LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS.' FBC EC 405.2.4
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-03-26 Cont ID  
Sent By scaldero Date 2018-03-26 Time 10:59 Rev Time 0.00
Received By scaldero Date 2018-03-26 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-25 Cont ID  
Sent By scaldero Date 2018-01-25 Time 11:14 Rev Time 0.00
Received By scaldero Date 2018-01-25 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-12 Cont ID  
Sent By scaldero Date 2017-12-12 Time 12:11 Rev Time 0.00
Received By scaldero Date 2017-12-12 Time 12:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2018-04-16 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-11 Time 12:28 Sent To  
Notes
2018-04-12 12:28:39RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-04-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-22 Time 13:50 Sent To  
Notes
2018-03-23 13:50:50B07

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-12 Cont ID  
Sent By gjohnson Date 2018-03-12 Time 16:41 Rev Time 0.00
Received By gjohnson Date 2018-02-16 Time 11:47 Sent To  
Notes
2018-02-20 11:47:17B11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-12 Cont ID  
Sent By cpuell Date 2018-02-12 Time 12:41 Rev Time 0.00
Received By cpuell Date 2018-01-16 Time 13:58 Sent To  
Notes
2018-01-17 13:58:12B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-02 Cont ID  
Sent By gjohnson Date 2018-01-02 Time 18:51 Rev Time 0.00
Received By gjohnson Date 2017-12-08 Time 14:22 Sent To  
Notes
2017-12-11 14:22:13B12

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-04-16 Cont ID  
Sent By ccole Date 2018-04-16 Time 10:56 Rev Time 0.00
Received By ccole Date 2018-04-16 Time 10:56 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-04-03 Cont ID  
Sent By ccole Date 2018-04-03 Time 10:46 Rev Time 0.00
Received By ccole Date 2018-04-03 Time 10:46 Sent To I
Notes
2018-04-03 10:50:484TH REVIEW FBC-2017 MECHANICAL
 PERMIT #17120353
 4/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL INDICATES A 15
 SEER 48,000 BTUH (4-TON) SYSTEM, HOWEVER THE EQUIPMENT
 SCHEDULE ON THE PLAN INDICATES A 13 SEER 36,000 BTUH
 (3-TON) SYSTEM. IT APPEARS THAT THE ENERGY SUBMITTAL
 NEEDS TO BE CORRECTED.
  
 IF YOU HAVE ANYU QUESTIONS PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 11:57 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 11:57 Sent To  
Notes
2018-02-28 12:08:253RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17120353
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A REVISED OR CORRECTED AC EQUIPMENT SCHEDULE
 ON THE PLAN TO CORRELATE WITH THE COMPLIANCE DATA FOR
 THE SYSTEM SHOWN IN THE ENERGYGAUGE FORM. THE CURRENT
 SCHEDULE ON THE PLAN HAS BEEN CROSSED OUT.
  
 2) COMMENT #3 FROM THE PREVIOUS REVIEW STILL EXISTS. I
 HAVE REPRINTED IT BELOW- PLEASE COMPLY.
  
 3) M-1: THE AC LAYOUT PLAN IS INCOMPLETE: THE SIZE OF
 THE MAIN TRUNK IS NOT SHOWN, AND ONLY 3- 200 CFM SUPPLY
 DIFFUSERS ARE SHOWN WHICH INDICATES THE TOTAL SUPPLY
 AIR IN THE SPACE AT 600 CFMS FOR THE 3-TON SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-25 Cont ID  
Sent By ccole Date 2018-01-25 Time 07:46 Rev Time 0.00
Received By ccole Date 2018-01-24 Time 17:55 Sent To  
Notes
2018-01-25 08:05:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120353
 1/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE 180 CFMS OF OUTSIDE AIR WAS NOT
 CALCULATED IN ACCORDANCE WITH TABLE 403.3, HOWEVER IT
 EXCEEDS THE AMOUNT OF AIR REQUIRED BY CODE SO IT IS
 ACCEPTED.
  
 2) M-1: THE AC SCHEDULED IS INCORRECTLY INDCICATING
 2000 CFMS OF SUPPLY AIR FOR A 3-TON SYSTEM. A TYPICAL
 3-TON SYSTEM WILL PRODUCE 1200 CFMS +/-. PLEASE
 CORRECT.
  
 3) M-1: THE AC LAYOUT PLAN IS INCOMPLETE: THE SIZE OF
 THE MAIN TRUNK IS NOT SHOWN, AND ONLY 3- 200 CFM SUPPLY
 DIFFUSERS ARE SHOWN WHICH INDICATES THE TOTAL SUPPLY
 AIR IN THE SPACE AT 600 CFMS FOR THE 3-TON SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-21 Cont ID  
Sent By ccole Date 2017-12-21 Time 14:31 Rev Time 0.00
Received By ccole Date 2017-12-21 Time 14:31 Sent To  
Notes
2017-12-21 14:42:271ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120353
 12/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED CFMS OF
 OUTDOOR AIR AND THE AMOUNT OF CFMS PROVIDED BY THE
 EXISTING SYSTEM.
  
 2) NO MECHANICAL PLANS WERE SUBMITTED. PLEASE PROVIDE
 PLANS SHOWING ALL CHANGES TO BE MADE TO THE EXISTING
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-12 Cont ID  
Sent By gjohnson Date 2018-03-12 Time 16:41 Rev Time 0.00
Received By gjohnson Date 2018-03-12 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-01-29 Time   Rev Time 0.00
Received By gjohnson Date 2018-01-29 Time 09:59 Sent To  
Notes
2018-01-29 13:51:211ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 4.HOW WILL THIS BE COMPLIED WITH 110DEG SHOWN ON THE
 ISOMETRIC DRAWING IS NOT SUFFICIENT PROVIDE MANUFACTURE
 AND MODEL NUMBER INDICATE WITH NOTE ON PLAN. TEMPERED
 WATER SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH
 FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED
 FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER
 SHALL BE DELIVERED THEOUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 5. PLEASE PROVIDE MANUFACTURE SPECS AND INSTALLATION
 GUIDE FOR GREASE TRAP MANUFACTURE SPECIFICATIONS THAT
 WAS PROVIDED DID NOT SHOW THE PDI CERTIFICATION OR ANY
 OTHER STANDARD NUMBER THAT IT COMPLIES WITH. IT WAS NOT
 A INSTALLATION GUIDE . PER WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. THE LOCATION OF THE GREASE INTERCEPTOR UNDER THR
 THREE COMPARTMENT SINK WILL NOT ALLOW IT TO BE SERVICED
 IT SHOULD BE IN AN OPEN FLOOR AREA WERE THE LID CAN BE
 REMOVED AND INTERCEPTOR BE CLEANED OUT FROM ABOVE. PER
 FBC PL 1003.2
  
 2. PLEASE SHOE CLEAR FLOOR SPACE FOR TOILET AND
 LAVATORY. PER FBC ACC
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By gjohnson Date 2018-01-02 Time 18:41 Rev Time 0.00
Received By gjohnson Date 2018-01-02 Time 14:50 Sent To  
Notes
2018-01-02 18:51:231ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE THREE COMP SINK SHALL BE INDIRECT WASTE. PER FBC
 PL 802.1
  
 2. PROVIDE SIZING CALCULATIONS FOR GREASE TRAP.PER WPB
 AMEND TO FBC 107.2.1
  
 3. THE SIZE OF THE GREASE TRAP IS UNCLEAR ONE NUMBER
 WAS MARKED OUT AND ANOTHER WRITTEN IN IN PEN PLEASE
 CLARIFY ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 5. PLEASE PROVIDE MANUFACTURE SPECS AND INSTALLATION
 GUIDE FOR GREASE TRAP AND ICE CREAM MACHINES. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2018-03-27 Cont ID  
Sent By aclange Date 2018-03-27 Time 08:55 Rev Time 0.00
Received By aclange Date 2018-03-27 Time 08:55 Sent To  
Notes
2018-03-27 08:56:08PREVIOUSLY REVIEWED.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-24 Cont ID  
Sent By LL Date 2018-01-24 Time   Rev Time 0.00
Received By llouie Date 2018-01-24 Time   Sent To  
Notes
2018-01-24 16:20:59CHANGE OF OCCUPANCY (ICE CREAM PARLOR PERMITTED IN GC);
 INTERIOR MODIFICATIONS ONLY.