Plan Review Details - Permit 17120337
Plan Review Stops For Permit 17120337
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-12-20 Cont ID  
Sent By jgomez Date 2017-12-20 Time 16:44 Rev Time 0.00
Received By jgomez Date 2017-12-20 Time 16:12 Sent To  
Notes
2017-12-20 16:13:34 
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 NOTE: PROVIDE INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS
  
 1- PROPOSED CABANA: SHOW COMPLIANCE WITH THE HEATING
 REQUIREMENTS OF SEC. R303.9 FBC-RESIDENTIAL. NOTE:
 SHEET E-1 SHOW AN EXISTING A/C UNIT TO BE RELOCATED
 ABOVE THE DOUBLE FRENCH DOORS. PROVIDE DETAIL SHOWING
 HOW THE RELOCATED A/C UNIT IS GOING TO BE INSTALLED
 ABOVE THE NEW FRENCH DOORS. IT DOESN'T SEEM TO BE
 ENOUGH ROOM.
  
 2- THE HANDRAILS WERE REMOVED. HANDRAILS CAN NOT BE
 REMOVED. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS AS
 REQUIRED BY SEC. R311.7.8-RESIDENTIAL.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-12-19 Cont ID  
Sent By fmittner Date 2017-12-19 Time 10:26 Rev Time 0.00
Received By fmittner Date 2017-12-19 Time 10:26 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-20 Cont ID  
Sent By jgomez Date 2017-12-20 Time 16:45 Rev Time 0.00
Received By jgomez Date 2017-12-08 Time 13:08 Sent To I
Notes
2017-12-11 13:08:28REVISION ROUTED TO FMITTNER VIA ZONING INBOX