Plan Review Details - Permit 17120261
| Plan Review Stops For Permit 17120261 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-07 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-06 |
Time |
17:51 |
Sent To |
|
|
| Notes |
| 2018-09-07 18:28:42 | BUILDING PROVISO | | | 1) THE PROJECT IS LOCATED IN AN AE FLOOD ZONE. THE | | | MINIMUM FINISH FLOOR ELEVATION IS 14.77 NAVD 88 | | | (INCLUDES 2 FT FREEBOARD). ELEVATION CERTIFICATES ARE | | | REQUIRED. FBC1612 & CITY OF WPB ORDINANCE 94-546. | | | 2) SUBMIT ALTERNATE METHOD AND MATERIAL NETTING FALL | | | PROTECTION ENGINEERING CALCULATIONS WITH THE ENGINEER'S | | | SEAL AND ORIGINAL HANDWRITTEN SIGNATURE. FAC | | | 61G15-23.001 | | | 3) AUDITING OF JOBSITE INSPECTIONS IS REQUIRED. THE | | | SCHEDULING OF INSPECTIONS IS REQUIRED TO PREVENT THE | | | PERMIT FROM EXPIRING. FBC 110.3.7 FOR INFORMATION | | | CONTACT KEN CONRAD AT 561-601-6982. | | | 4) SUBMIT DEFERRED SUBMITTALS FOR REVIEW AND APPROVAL | | | BY THE BUILDING OFFICIAL, AFTER THEY HAVE BEEN REVIEWED | | | BY THE DESIGNER OF RECORD AND PRIOR TO THEIR | | | INSTALLATION. FBC 107.3.4.2 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-27 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-19 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2018-07-19 18:59:55 | 3RD REVIEW / 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17120261 | | | ADD: 1600 BELVEDERE RD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: NOT GIVEN ON PERMIT APPLICATION | | | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT | | | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR | | | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER | | | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY | | | WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE | | | DEVELOPMENT. | | | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND | | | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL | | | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS | | | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED | | | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES | | | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED | | | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF | | | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW | | | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 2) 2ND ROUND COMMENT. WE HAVE CALCULATED THE VALUE OF | | | THE BUILDING USING THE ICC TABLES FROM AUGUST 01/2017. | | | THERE IS NO A5 CLASS IN THE TABLES; THE CLOSEST USE IS | | | A4 ARENAS. | | | 63,885.0 SQ. FT. X $190.84 BUILDING TYPE II-B = | | | $12,191,813.00 (CALCULATED VALUE) | | | PLEASE PROVIDE AN ITEMIZED LIST OF THE SUB-PERMITS NOT | | | COVERED UNDER THE MAIN PERMIT AND DEDUCT THERE VALUE | | | FROM THE OVERALL CALCULATED VALUE OF THE BUILDING. THIS | | | WILL BECOME THE NEW ADJUSTED VALUE OF THE BUILDING | | | PERMIT. | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK | | | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME PERMIT | | | | | | 3) COMPLIED. | | | | | | 3A) COMPLIED. | | | | | | 3B) COMPLIED. | | | | | | 3C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 . 633 | | | FLORIDA STATUTE. | | | | | | 3D)COMPLIED. | | | | | | 3E) COMPLIED. | | | | | | 3F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 3G) PROVISO/ NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND | | | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE | | | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. | | | EACH SHORING AND RESHORING INSTALLATION SHALL BE | | | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE | | | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. | | | | | | 3H) PROVISO/ NOTICE ONLY. PLEASE CALL THE CITY OF WEST | | | PALM BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 3I) PROVISO/ NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, | | | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. | | | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) PROVISO. THIS PROPERTY IS LOCATED IN A AE FLOOD | | | ZONE. THE BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS | | | 2 FEET OR A FINISH FLOOR ELEVATION MINIMUM OF 14.77 | | | NAVD 88. | | | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & | | | CONTROL | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE | | | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | 4) (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF | | | THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH | | | FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 | | | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, | | | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. | | | | | | 4) (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. | | | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 | | | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON | | | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND | | | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION | | | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL. | | | | | | 4) (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD | | | ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL | | | EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR | | | GENERATORS. | | | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS | | | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS | | | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR | | | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL | | | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR | | | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING | | | JURISDICTION. | | | FEMA NEW FORM AVAILABLE JUNE 13/2016. | | | OMB NO. 1660-0008 | | | EXPIRATION DATE: NOV. 30/2018 | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5) COMPLIED. | | | 5A) COMPLIED. | | | 5B) COMPLIED. | | | 5C) COMPLIED. | | | 5D) COMPLIED. | | | 5E) NOTICE ONLY. THE SOILS REPORT INDICATES THERE ARE | | | TO BE 160 FOOT TALL POLES WITH NETTING TO CATCH THE | | | GOLF BALLS. THE POLES AND NETTING ARE NOT PART OF THIS | | | PERMIT AND WILL REQUIRE A SEPARATE PERMIT REVIEW AND | | | ASSOCIATED FEES. IN THE ANALYSIS FOR THE POLES IT WILL | | | NEED TO BE MADE CLEAR IF THE NETTING IS TO BE DROPPED | | | WHEN A HIGH WIND EVENT WILL OCCUR. NOTE THIS ALSO NEEDS | | | TO BE INCORPORATED INTO THE O & M MANUAL. | | | 1ST REVIEW. THIS REVIEW NO SOILS REPORTS WERE FOUND IN | | | THE FILE FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY | | | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 6A-D) COMPLIED. | | | | | | 7A-G) COMPLIED. | | | | | | 8A-H) COMPLIED. 004- LS-01 LIFE SAFETY PLAN. | | | NEW COMMENTS. | | | 1) FBC 1014.3 SHOW THE COMMON PATHS OF EGRESS TRAVEL | | | AND THEIR DISTANCES ON THE LIFE SAFETY PLANS. | | | 2) ON SHEET 004-LS-01, CLARIFY THE 68" CLEAR DOOR | | | LISTED IN THE EXIT CAPACITY SUMMARY AT LEVEL 2 FOR | | | STAIR #3. FBC 107.2.1 | | | 3) REVISE THE NOTES FOR THE DOORS ON THE HOLD OPEN | | | DEVICES AT STAIR #3. THESE DOORS SHOULD BE OPENABLE | | | FROM THE PANTRY SIDE AND SHOULD BE USED AS EXIT EGRESS | | | DOORS FROM THOSE AREAS. THE ONLY OPENINGS INTO EXIT | | | ACCESS STAIRWAYS ENCLOSURE ARE THOSE NECESSARY FOR THE | | | PURPOSE OF THE STAIRWAY. FBC 1009.3.1.4.1 THE FIRE | | | DEPARTMENT DOES NOT WANT THESE DOORS TO BE OPENABLE | | | FROM THE STAIRWAY SIDE. | | | 4) THE EXIT SIGN ON THE GROUND FLOOR DIRECTING THE | | | GROUND FLOOR OCCUPANTS INTO STAIR #4 SHOULD BE REMOVED. | | | THE OCCUPANTS OF THE FIRST FLOOR WILL USE THE EXIT DOOR | | | THAT OPENS TO THE EXTERIOR OF THE BUILDING. THE | | | OCCUPANTS FROM THE SECOND AND THIRD LEVELS USING STAIR | | | #3 WILL USE THIS SAME DOOR TO EXIT THE BUILDING. | | | OTHERWISE, THE OCCUPANTS OF THE UPPER LEVELS MAY | | | ATTEMPT TO EXIT THROUGH STAIR #4 AND CONVERGE WITH THE | | | OCCUPANTS USING THIS STAIR. | | | 5) THE LIFE SAFETY PLAN ON SHEET 004-LS-01 DOES NOT | | | SHOW THE FIRE RATED WALLS ON ALL SIDES OF STAIR #S 1 | | | AND 4, AS THEY ARE ON SHEETS 206-A2-01-A AND | | | 206-A2-01-B. CLARIFY. | | | | | | 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS. | | | NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE | | | ACCESSIBILITY CODE: | | | NEW COMMENTS. THE ADA BAR AREA IS NOT IDENTIFIED AT THE | | | UPPER LEVEL BAR ONT SHEET 210-A2-01-B. PROVIDE | | | DIMENSIONS ON THE BAR ELEVATION DRAWINGS TO SHOW THAT | | | ADA PORTIONS OF THE BARS ARE IN COMPLIANCE AND SHOW THE | | | CLEAR FLOOR SPACE AT THE BARS AND ANY FIXED SEATING. | | | | | | 9A) 2ND REQUEST. 226.1 WHERE DINING SURFACES ARE | | | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST | | | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. | | | | | | 9B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND | | | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE | | | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING | | | DINING SURFACES AND WORK SURFACES. | | | | | | 9C) 2ND REQUEST. SEMI-COMPLIED. THE PLANS DO SHOW A | | | DROPPED PORTION OF THE BARS FOR ACCESSIBLE DRINKING | | | AREA. | | | NEW COMMENTS. PROVIDE DIMENSIONS ON THE BAR ELEVATION | | | DRAWINGS TO SHOW THAT ADA PORTIONS OF THE BARS ARE IN | | | COMPLIANCE AND SHOW THE CLEAR FLOOR SPACE AT THE BARS | | | AND ANY FIXED SEATING. | | | | | | 1ST ROUND COMMENT. 902.1 .DINING SURFACES AND WORK | | | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY | | | 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT | | | LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. | | | 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 10A-E) COMPLIED. | | | | | | 10E) COMPLIED. 206.2.15 GOLF FACILITIES. | | | | | | 11A-C)COMPLIED. EMERGENCY OVER FLOW SCUPPERS & | | | SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. | | | | | | 12-23) BUILDING PROVISO: THE DESIGNER OF RECORD WISHES | | | TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT | | | ISSUANCE. SEE THE COVERSHEET 003-CS-1. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE | | | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY | | | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS | | | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE | | | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE | | | CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-29 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-03-28 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2018-04-06 15:12:28 | E-MAIL SENT TO MR. FRED HENDERSON 04/06/2018 03:11 PM | | | 630 K ATTACHMENT | | | APRIL 06/2018 | | | W. P. B. DRIVE SHACK | | | ADDRESS 1600 BELVEDERE RD. | | | PERMIT: 17120261 | | | | | | TO: MR. FRED HENDERSON, | | | | | | THE CITY IS IN RECEIPT OF THE SUBMITTED THRESHOLD | | | INSPECTION PLAN. THE CITY HAS REVIEWED YOUR THRESHOLD | | | INSPECTION PLAN AND FOUND EVERYTHING IN THE THRESHOLD | | | INSPECTION PLAN AS WELL AS IN THE STRUCTURAL PLANS | | | REFERS BACK TO SECTIONS 1704 AND OR 1705 OF THE IBC. | | | PLEASE NOTE UNDER THE 2014 OR THE 2017 FBC-B THESE | | | SECTIONS ARE RESERVED. FLORIDA STATUTE 553.79(5) STATES | | | THE STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO AND | | | APPROVED BY THE ENFORCING AGENCY BEFORE THE ISSUANCE OF | | | A BUILDING PERMIT FOR THE CONSTRUCTION OF A THRESHOLD | | | BUILDING. WE HAVE HAD THE BUILDING OFFICIAL AND ONE OF | | | OUR ASSISTANT BUILDING OFFICIALS LOOK AT THE SUBMITTED | | | DOCUMENT AND FOUND IT LACKING. THE PURPOSE OF THE | | | STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC | | | INSPECTION PROCEDURES AND SCHEDULES SO THAT THE | | | BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | PLEASE REFER TO THE THRESHOLD INSPECTION PLAN THAT HAS | | | BEEN SUBMITTED TO THE CITY AND APPROVED. THE ONLY THING | | | THAT WE WOULD RECOMMEND IN REGARDS TO A THRESHOLD | | | INSPECTION PLAN WE WOULD PREFER TO ALSO HAVE THE | | | BUILDING TYPE, OCCUPANCY AND USE, STORIES OF BUILDING | | | AND IF FIRE SPRINKLERED. | | | | | | SEE THE NEXT SHEET FOR A SAMPLE OF A THRESHOLD | | | INSPECTION PLAN. | | | | | | THRESHOLD INSPECTION . PDF | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | 2018-03-29 16:57:14 | 2ND REVIEW / 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17120261 | | | ADD: 1600 BELVEDERE RD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: NOT GIVEN ON PERMIT APPLICATION | | | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: WED.-THURS. MARCH 28-29/2018 | | | ACTION: DENIED | | | | | | 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT | | | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR | | | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER | | | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY | | | WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE | | | DEVELOPMENT. | | | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND | | | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL | | | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS | | | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED | | | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES | | | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED | | | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF | | | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW | | | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 2) 2ND ROUND COMMENT. WE HAVE CALCULATED THE VALUE OF | | | THE BUILDING USING THE ICC TABLES FROM AUGUST 01/2017. | | | THERE IS NO A5 CLASS IN THE TABLES; THE CLOSEST USE IS | | | A4 ARENAS. | | | 68,885.0 SQ. FT. | | | X 190.84 BUILDING TYPE II-B | | | $13,146,013.00 IN VALUE CALCULATED VALUE | | | PLEASE PROVIDE AN ITEMIZED LIST OF THE SUB-PERMITS NOT | | | COVERED UNDER THE MAIN PERMIT AND DEDUCT THERE VALUE | | | FROM THE OVERALL CALCULATED VALUE OF THE BUILDING. THIS | | | WILL BECOME THE NEW ADJUSTED VALUE OF THE BUILDING | | | PERMIT. | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK | | | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME PERMIT | | | | | | 1ST ROUND OF COMMENTS. 108.3* BUILDING PERMIT | | | VALUATION. PLEASE NOTE THE BUILDING VALUATION SEEMS A | | | LITTLE LOW. THE CODE SUMMARY SHEET CS-1 UNDER THE | | | HEADING BUILDING DATA LIST THE SQUARE FOOTAGE PER FLOOR | | | BUT NOT THE SQUARE FOOTAGE PER OCCUPANCY TYPE. THE ICC | | | EVALUATION TABLES USES BUILDING TYPE, OCCUPANCY TYPE | | | AND SQUARE FOOTAGE TO DETERMINE THE VALUATION OF THE | | | BUILDING. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK | | | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME PERMIT | | | | | | 3) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | | BUILDING BY DEFINITION. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 3A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 3B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | | | | FORMS WERE E-MAILED TO: [email protected] 1/24/2018 | | | 2:30PM. | | | | | | | | | 3C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 . 633 | | | FLORIDA STATUTE. | | | | | | 3D)SEMI-COMPLIED. IN THE DOCUMENT FILE DOCUMENTS HAD | | | BEEN UPLOADED FOR DONALD G BELLAMY, JR. P. E. , S. I. | | | FOR LICENSING AND RESUME (UNIVERSAL ENGINEERING | | | SERVICES, INC.). WHAT WE DID NOT SEE WERE HIS DESIGNEES | | | LICENSED UNDER PART XII OF CHAPTER 468, FLORIDA | | | STATUTES AND THEIR RESUMES. 110.3.7.6 THE BUILDING | | | DEPARTMENT MAY ALLOW A SPECIAL INSPECTOR TO CONDUCT THE | | | MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS | | | REQUIRED BY THIS CODE, SECTION 553.73, FLORIDA | | | STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE | | | BUILDING DEPARTMENT. THE BUILDING | | | OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON | | | CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING | | | INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA | | | STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER | | | CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF | | | THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5), | | | FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM | | | INSPECTIONS REQUIRED BY THIS CODE. | | | | | | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | | | | 3E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 3F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 3G) PROVISO/ NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND | | | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE | | | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. | | | EACH SHORING AND RESHORING INSTALLATION SHALL BE | | | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE | | | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. | | | | | | 3H) PROVISO/ NOTICE ONLY. PLEASE CALL THE CITY OF WEST | | | PALM BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 3I) PROVISO/ NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, | | | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. | | | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) 2ND REQUEST. THIS PROPERTY IS LOCATED IN A AE FLOOD | | | ZONE. THE BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS | | | 2 FEET OR A FINISH FLOOR ELEVATION MINIMUM OF 14.77 | | | NAVD 88. | | | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & | | | CONTROL | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE | | | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | 4) (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF | | | THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH | | | FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 | | | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, | | | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. | | | | | | 4) (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. | | | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 | | | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON | | | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND | | | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION | | | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL. | | | | | | 4) (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD | | | ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL | | | EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR | | | GENERATORS. | | | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS | | | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS | | | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR | | | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL | | | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR | | | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING | | | JURISDICTION. | | | FEMA NEW FORM AVAILABLE JUNE 13/2016. | | | OMB NO. 1660-0008 | | | EXPIRATION DATE: NOV. 30/2018 | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5) 2ND REVIEW. SOILS REPORT BY ESC FLORIDA, LLC. JOSE | | | N. GOMEZ P. E. D.GE SEAL AND COPIED SIGNATURE AND DATE | | | ARE ON PAGE 2 OF THE REPORT. WILL NEED TO SEND (1) | | | ORIGINAL PAPER SOILS REPORT, IT WILL BE KEPT WITH OTHER | | | PAPER DOCUMENTS FOR SEAL AND SIGNATURE PURPOSES OR SHOW | | | COMPLIANCE WITH: | | | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A | | | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE | | | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON | | | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH | | | LISTED PAGES OR INDEX SHEET FOR ENGINEERING | | | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE | | | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & | | | PREPARATION OF EACH SECTION OF THE ENGINEERING | | | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER | | | SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER | | | THE COVER SHEET OR INDEX SHEET. | | | | | | 5A) WITHIN THE SOILS REPORT ON PAGE 11 TABLE 5.1.1.1 | | | FOUNDATION DESIGN THE TABLE LIST A NET ALLOWABLE | | | BEARING PRESSURE OF 3,000 PSF FOR BOTH COLUMN AND WALL | | | FOOTINGS. THE TABLE ALSO LIST A MINIMUM FOOTING | | | EMBEDMENT DEPTH (BELOW SLAB OR FINISH GRADE) OF 48 | | | INCHES FOR BOTH COLUMN AND WALL FOOTINGS. THE QUESTION | | | IS HAS THE STRUCTURAL ENGINEER OF RECORD REVIEWED THESE | | | RECOMMENDATIONS? OR IS THERE OTHER REASONS THEY ARE NOT | | | OF CONCERN AS OF FROST LINE PER 2014 FBC-B 1809.5 FROST | | | PROTECTION? 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | SHEET 309-S2-01A NOTE 3 2 INDICATES THE TOP OF | | | FOUNDATION ELEVATION IS (-) 2 FEET UNLESS OTHERWISE | | | NOTED. | | | SHEET 320-S4-11 UNDER THE FOOTING SCHEDULE LIST | | | FOOTINGS F1-F7. FOOTINGS F4,F5, & F6 WILL ALWAYS COMPLY | | | WITH THE 4 FOOT FOOTING DEPTH. FOOTINGS F1, F2, F3, & | | | F7 WILL ALL BE ABOVE THE REQUIRED 4 FOOT DEPTH. | | | | | | 5B) IN REVIEWING FOR THE FOOTING DEPTHS ON SHEET | | | 309-S2-01A NOTE # 1 INDICATES THE CIVIL DRAWINGS | | | ELEVATION OF 182.00 FEET. PLEASE CORRECT THE ELEVATION, | | | THIS PROJECT IS IN AN A FLOOD ZONE. | | | | | | 5C) IN REVIEWING FOR THE FOOTING DEPTHS ON SHEET | | | 309-S2-01A THERE IS A NOTE BY GRID LINES 22/C.8 FOR | | | VERTICAL REBAR MISSING THE SIZE AND SPACING OF THE | | | REBAR. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 5D) THE SOILS REPORT ON PAGES 10 & 11 HIGHLY RECOMMENDS | | | CONDUCTING TEST PITS, AND OR OTHER GEOPHYSICAL | | | TECHNIQUES TO DETERMINE THE PRESENCE OF AND DELINEATE | | | THE EXTENTS OF BURIED CONCRETE, METALS, PLASTICS AND | | | GLASS DEBRIS AT THE EASTERN PORTION OF THE SITE, AS | | | THESE DELETERIOUS MATERIALS WILL NEED TO BE ADDRESSED | | | DURING THE EARTHWORK OPERATIONS PRIOR TO START OF | | | CONSTRUCTION. 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED, PLEASE PROVIDE A RESPONSE. | | | | | | 5E) NOTICE ONLY. THE SOILS REPORT INDICATES THERE ARE | | | TO BE 160 FOOT TALL POLES WITH NETTING TO CATCH THE | | | GOLF BALLS. THE POLES AND NETTING ARE NOT PART OF THIS | | | PERMIT AND WILL REQUIRE A SEPARATE PERMIT REVIEW AND | | | ASSOCIATED FEES. IN THE ANALYSIS FOR THE POLES IT WILL | | | NEED TO BE MADE CLEAR IF THE NETTING IS TO BE DROPPED | | | WHEN A HIGH WIND EVENT WILL OCCUR. NOTE THIS ALSO NEEDS | | | TO BE INCORPORATED INTO THE O & M MANUAL. | | | 1ST REVIEW. THIS REVIEW NO SOILS REPORTS WERE FOUND IN | | | THE FILE FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY | | | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 6A) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR | | | ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION | | | HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING | | | OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS | | | NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH | | | 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF | | | CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH | | | FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT | | | DOCS PROGRAM INFORMATION FOLDER. | | | | | | 1ST ROUND OF COMMENTS. FALL PROTECTION PDF. ATTACHMENT | | | 1 HITTING BAY. UNDER THE 2014 FBC-B, THE CODE DOES NOT | | | INCLUDE RAISED GOLFING PLATFORMS AS EXEMPT LOCATIONS TO | | | THE REQUIREMENT FOR GUARDS AND OR GUARDRAILS SEE FBC-B | | | 1013.2 WHERE REQUIRED. I WOULD RECOMMEND THAT YOU | | | SHOULD MAKE A WRITTEN REQUEST TO THE BUILDING OFFICIAL | | | ROBERT BROWN REQUESTING THE FALL PROTECTION PDF TO BE | | | CONSIDERED UNDER THE: | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION SECTION 104.11 ALTERNATIVE MATERIALS, | | | DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT. THE | | | PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT THE | | | INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN | | | OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED | | | BY THIS CODE, PROVIDED THAT | | | ANY SUCH ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE | | | MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE | | | APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE | | | PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE | | | INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE | | | MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE | | | INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN | | | THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE | | | RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE | | | SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE | | | TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND | | | DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE | | | BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL | | | SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE | | | SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE | | | ALTERNATIVE. | | | | | | 6B) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR | | | ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION | | | HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING | | | OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS | | | NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH | | | 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF | | | CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH | | | FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT | | | DOCS PROGRAM INFORMATION FOLDER. | | | 1ST ROUND OF COMMENTS. 104.11.1 RESEARCH REPORTS. | | | SUPPORTING DATA, WHERE NECESSARY TO ASSIST IN THE | | | APPROVAL OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY | | | PROVIDED FOR IN THIS CODE, SHALL CONSIST OF VALID | | | RESEARCH REPORTS FROM APPROVED SOURCES. | | | | | | 6C) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR | | | ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION | | | HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING | | | OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS | | | NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH | | | 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF | | | CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH | | | FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT | | | DOCS PROGRAM INFORMATION FOLDER. | | | | | | 1ST ROUND OF COMMENTS. 104.11.2 TESTS. WHENEVER THERE | | | IS INSUFFICIENT EVIDENCE OF COMPLIANCE WITH THE | | | PROVISIONS OF THIS CODE, OR EVIDENCE THAT A MATERIAL OR | | | METHOD DOES NOT CONFORM TO THE REQUIREMENTS OF THIS | | | CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR | | | ALTERNATIVE MATERIALS OR METHODS, THE BUILDING | | | OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS | | | EVIDENCE OF COMPLIANCE TO BE MADE AT NO | | | EXPENSE TO THE JURISDICTION. TEST METHODS SHALL BE AS | | | SPECIFIED IN THIS CODE OR BY OTHER | | | RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED | | | AND ACCEPTED TEST METHODS, THE | | | BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES. | | | TESTS SHALL BE PERFORMED BY AN APPROVED | | | AGENCY. REPORTS OF SUCH TESTS SHALL BE RETAINED BY THE | | | BUILDING OFFICIAL FOR THE PERIOD REQUIRED | | | FOR RETENTION OF PUBLIC RECORDS. | | | | | | 6D) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR | | | ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION | | | HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING | | | OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS | | | NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH | | | 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF | | | CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH | | | FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT | | | DOCS PROGRAM INFORMATION FOLDER. | | | 1ST ROUND OF COMMENTS. 104.11.3 ACCESSIBILITY. | | | ALTERNATIVE DESIGNS AND TECHNOLOGIES FOR PROVIDING | | | ACCESS TO AND USABILITY OF A FACILITY FOR PERSONS WITH | | | DISABILITIES SHALL BE IN ACCORDANCE WITH PROVISIONS OF | | | THE FLORIDA BUILDING CODE, ACCESSIBILITY. | | | | | | 7) SHEET 003 CS-1 CODE SUMMARY: | | | | | | 7A-C) COMPLIED. | | | | | | 7D)SEMI- COMPLIED. HEADING: ACCESSIBLE PARKING | | | REQUIREMENTS CHART. SIGNAGE IS REQUIRED FOR THE VAN | | | ACCESSIBLE PARKING, EVEN THOUGH IT IS NOT IN A PARKING | | | GARAGE, FOR EVERY 6 OR FRACTION THERE OF A VAN | | | ACCESSIBLE SPACE NEEDS TO BE DECLARED WITH SIGNAGE. | | | | | | FBC-ACCESSIBILITY CODE: ADVISORY 208.2 MINIMUM NUMBER. | | | THE TERM ?PARKING FACILITY? IS USED SECTION 208.2 | | | INSTEAD OF THE TERM ?PARKING LOT? SO THAT IT IS CLEAR | | | THAT BOTH PARKING LOTS AND PARKING STRUCTURES ARE | | | REQUIRED TO COMPLY WITH THIS SECTION. | | | 2014 FBC-ACCESSIBILITY CODE 502.6 IDENTIFICATION. | | | PARKING SPACE IDENTIFICATION SIGNS SHALL INCLUDE THE | | | INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH | | | 703.7.2.1. SIGNS IDENTIFYING VAN PARKING SPACES WHEN | | | REQUIRED BY 502.2 SHALL CONTAIN THE DESIGNATION ?VAN | | | ACCESSIBLE.? | | | | | | | | | | | | 7E) COMPLIED. 9:30 AM. 3/30/3018. PRESSURES OK. PLEASE | | | PROVIDE ALSO IN VASD SINCE THE PRODUCT APPROVALS ARE | | | ALL IN VASD. THANK YOU WITH YOUR ANTICIPATED | | | COOPERATION. | | | | | | 7F-G) COMPLIED. | | | | | | 8A-H) COMPLIED. 004- LS-01 LIFE SAFETY PLAN. | | | | | | | | | 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS. | | | NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE | | | ACCESSIBILITY CODE: | | | 9A) 2ND REQUEST. 226.1 WHERE DINING SURFACES ARE | | | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST | | | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT | | | THE DINING SURFACES SHALL COMPLY WITH 902. | | | | | | 9B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND | | | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE | | | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING | | | DINING SURFACES AND WORK SURFACES. | | | | | | 9C)2ND REQUEST. SEMI-COMPLIED. THE PLANS DO SHOW A | | | DROPPED PORTION OF THE BARS FOR ACCESSIBLE DRINKING | | | AREA. | | | 1ST ROUND COMMENT. 902.1 .DINING SURFACES AND WORK | | | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY | | | 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT | | | LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. | | | 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 10)COMPLIED. | | | 10A-C) COMPLIED. | | | | | | 10D) SEE COMMENT 7D). 208.2.4 VAN PARKING SPACES. WHERE | | | VAN PARKING IS PROVIDED PURSUANT TO SECTION 502.2, FOR | | | EVERY SIX OR FRACTION OF SIX PARKING SPACES REQUIRED BY | | | 208.2 TO COMPLY WITH 502, AT LEAST ONE SHALL BE A VAN | | | PARKING SPACE COMPLYING WITH 502. | | | | | | 10E) COMPLIED. 206.2.15 GOLF FACILITIES. | | | | | | 11A-C)COMPLIED. EMERGENCY OVER FLOW SCUPPERS & | | | SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. | | | | | | 12-23) BUILDING PROVISO: THE DESIGNER OF RECORD WISHES | | | TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT | | | ISSUANCE. SEE THE COVERSHEET 003-CS-1. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE | | | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY | | | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS | | | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE | | | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE | | | CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-24 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-12-21 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2018-01-24 14:18:41 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17120261 | | | ADD: 1600 BELVEDERE RD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: NOT GIVEN ON PERMIT APPLICATION | | | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: WED. JAN. 24/2018 | | | ACTION: DENIED | | | | | | ART IN PUBLIC PLACES | | | 1) THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE | | | DEVELOPMENT. | | | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND | | | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL | | | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS | | | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED | | | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES | | | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED | | | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF | | | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW | | | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 2) 108.3* BUILDING PERMIT VALUATION. PLEASE NOTE THE | | | BUILDING VALUATION SEEMS A LITTLE LOW. THE CODE SUMMARY | | | SHEET CS-1 UNDER THE HEADING BUILDING DATA LIST THE | | | SQUARE FOOTAGE PER FLOOR BUT NOT THE SQUARE FOOTAGE PER | | | OCCUPANCY TYPE. THE ICC EVALUATION TABLES USES BUILDING | | | TYPE, OCCUPANCY TYPE AND SQUARE FOOTAGE TO DETERMINE | | | THE VALUATION OF THE BUILDING. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK | | | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME PERMIT | | | | | | 3) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | | BUILDING BY DEFINITION. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. | | | | | | FORMS WERE E-MAILED TO: [email protected] 1/24/2018 | | | 2:30PM. | | | | | | | | | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 3F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE | | | E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, | | | THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED | | | AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, | | | TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) | | | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK | | | & WHITE.. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 3G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 3H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 3I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | 4) THIS PROPERTY IS LOCATED IN A AE FLOOD ZONE. THE | | | BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS 2 FEET OR | | | A FINISH FLOOR ELEVATION MINIMUM OF 14.77 NAVD 88. | | | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & | | | CONTROL | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE | | | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 | | | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, | | | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. | | | | | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. | | | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 | | | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON | | | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND | | | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION | | | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL. | | | | | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. | | | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS | | | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS | | | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR | | | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL | | | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR | | | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING | | | JURISDICTION. | | | FEMA NEW FORM AVAILABLE JUNE 13/2016. | | | OMB NO. 1660-0008 | | | EXPIRATION DATE: NOV. 30/2018 | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5) THIS REVIEW NO SOILS REPORTS WERE FOUND IN THE FILE | | | FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY | | | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 6A) FALL PROTECTION PDF. ATTACHMENT 1 HITTING BAY. | | | UNDER THE 2014 FBC-B, THE CODE DOES NOT INCLUDE RAISED | | | GOLFING PLATFORMS AS EXEMPT LOCATIONS TO THE | | | REQUIREMENT FOR GUARDS AND OR GUARDRAILS SEE FBC-B | | | 1013.2 WHERE REQUIRED. I WOULD RECOMMEND THAT YOU | | | SHOULD MAKE A WRITTEN REQUEST TO THE BUILDING OFFICIAL | | | ROBERT BROWN REQUESTING THE FALL PROTECTION PDF TO BE | | | CONSIDERED UNDER THE: | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION SECTION 104.11 ALTERNATIVE MATERIALS, | | | DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT. THE | | | PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT THE | | | INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN | | | OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED | | | BY THIS CODE, PROVIDED THAT | | | ANY SUCH ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE | | | MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE | | | APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE | | | PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE | | | INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE | | | MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE | | | INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN | | | THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE | | | RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE | | | SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE | | | TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND | | | DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE | | | BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL | | | SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE | | | SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE | | | ALTERNATIVE. | | | | | | 6B) 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE | | | NECESSARY TO ASSIST IN THE APPROVAL OF | | | MATERIALS OR ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR | | | IN THIS CODE, SHALL CONSIST OF VALID | | | RESEARCH REPORTS FROM APPROVED SOURCES. | | | | | | 6C) 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT | | | EVIDENCE OF COMPLIANCE WITH THE PROVISIONS OF | | | THIS CODE, OR EVIDENCE THAT A MATERIAL OR METHOD DOES | | | NOT CONFORM TO THE REQUIREMENTS OF THIS | | | CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR | | | ALTERNATIVE MATERIALS OR METHODS, THE BUILDING | | | OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS | | | EVIDENCE OF COMPLIANCE TO BE MADE AT NO | | | EXPENSE TO THE JURISDICTION. TEST METHODS SHALL BE AS | | | SPECIFIED IN THIS CODE OR BY OTHER | | | RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED | | | AND ACCEPTED TEST METHODS, THE | | | BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES. | | | TESTS SHALL BE PERFORMED BY AN APPROVED | | | AGENCY. REPORTS OF SUCH TESTS SHALL BE RETAINED BY THE | | | BUILDING OFFICIAL FOR THE PERIOD REQUIRED | | | FOR RETENTION OF PUBLIC RECORDS. | | | | | | 6D) 104.11.3 ACCESSIBILITY. ALTERNATIVE DESIGNS AND | | | TECHNOLOGIES FOR PROVIDING ACCESS TO AND | | | USABILITY OF A FACILITY FOR PERSONS WITH DISABILITIES | | | SHALL BE IN ACCORDANCE WITH PROVISIONS OF | | | THE FLORIDA BUILDING CODE, ACCESSIBILITY. | | | | | | 7) SHEET 003 CS-1 CODE SUMMARY: | | | | | | 7A) SEPARATED USE CALCULATIONS SHOWS THE FORMULA AND | | | CHART BUT NEITHER IS FILLED OUT. PLEASE PROVIDE THE | | | DOCUMENTATION SEE THE 2014 FBC-B SECTION 506.5.2. | | | | | | 7B) UNDER THE HEADING FIRE RESISTANCE RATINGS THERE IS | | | NO ROW FOR FIRE BARRIER ASSEMBLIES OR HORIZONTAL | | | ASSEMBLIES BETWEEN FIRE AREAS, SEE TABLE 707.3.10. | | | | | | 7C) HEADING: EXIT REQUIREMENTS LIST 50 FT. MAXIMUM DEAD | | | END. PLEASE LIST THE OCCUPANCIES WHERE THIS IS TRUE. | | | FBC-B 1018.4 SEE EXCEPTION 2. | | | | | | 7D) HEADING: ACCESSIBLE PARKING REQUIREMENTS CHART IS | | | LEFT BLANK. WILL NEED TO COMPLY WITH THE 2014 | | | ACCESSIBILITY CODE 208.2, TABLE 208.2 AND 208.2.4. VAN | | | PARKING SPACES. | | | | | | 7E) HEADING: STRUCTURAL INDICATES WIND LOAD 170 MPH | | | VULT. PLEASE REFER TO THE 2014 FBC-B TABLE 1604.5 FOR | | | RISK CATEGORY OF BUILDINGS . RISK CATEGORY III INCLUDES | | | BUILDINGS AND OTHER STRUCTURES WHOSE PRIMARY OCCUPANCY | | | IS PUBLIC ASSEMBLY WITH AN OCCUPANT LOAD GREATER THAN | | | 300. THIS BUILDING QUALIFIES WITH AN OCCUPANT LOAD OF | | | 1708 PLUS. | | | PLEASE ALSO REVIEW FIGURE 1609B THE V ULTIMATE DESIGN | | | SPEEDS FOR RISK CATEGORY III BUILDINGS AND OTHER | | | STRUCTURES. THE CITY OF WEST PALM BEACH IS LOCATED IN A | | | 180 MPH (VULT) WIND ZONE. IMPORTANCE FACTOR SHOULD ALSO | | | CHANGE FOR WIND. | | | | | | PLEASE ALSO CORRECT THE WIND DESIGN CRITERIA FOUND ON | | | SHEET 3001 S0-01 GENERAL NOTE E WIND LOADS, THE PLANS | | | STATE BUILDING CATEGORY II AND 170 MPH, VULT. | | | | | | 7F) OCCUPANCY CATEGORY (TABLE 1604.5) WILL ALSO CHANGE | | | TO III. | | | | | | 7G) SOIL BEARING CAPACITY OF 3,000 PSF ASSUMED, NO | | | SOILS REPORT SUBMITTED TO SEE WHAT VALUES ARE IN THE | | | NATURAL SOILS. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | | | | 8) 004- LS-01 LIFE SAFETY PLAN: | | | | | | 8A) FOR ALL 3 LEVELS PLEASE PROVIDE THE OCCUPANT LOAD | | | FOR EACH ROOM IN THAT ROOM. WHEN TRAVELING THROUGH | | | ADJACENT ROOMS COMBINE THE OCCUPANT LOADS FOR THE ROOMS | | | AND WHEN YOU GET TO EITHER AN AISLE OR CORRIDOR PROVIDE | | | THE OCCUPANT LOAD FOR THAT AREA BEING SERVED AND ADD | | | THE ADDITIONAL OCCUPANTS BEING ADDED ALONG THE EGRESS | | | PATH FROM THE INTERIOR OF THE BUILDING AS WELL AS THE | | | HITTING AND SEATING BAYS, THIS SHOULD ADD UP TO THE | | | AMOUNT GOING THROUGH THE VERTICAL EXITS AND STAIRS. | | | | | | 2014 FBC-B 1004.1.1.1 INTERVENING SPACES. WHERE | | | OCCUPANTS EGRESS FROM ONE ROOM, AREA OR SPACE THROUGH | | | ANOTHER, THE DESIGN OCCUPANT LOAD SHALL BE BASED ON THE | | | CUMULATIVE OCCUPANT LOADS OF ALL ROOMS, AREAS OR SPACES | | | TO THAT POINT ALONG THE PATH OF EGRESS TRAVEL. | | | | | | 8B) LOWER LEVEL. THE EXTERIOR TERRACE01.20.02 HAS 2338 | | | SQ. FT. OF AREA WITH NO FURNITURE LAYOUT. 2338/ 07= 334 | | | OCCUPANT LOAD. THERE IS ONLY ONE EXIT FROM THIS AREA. | | | THE FBC-B TABLE 1015.1 ONLY ALLOWS FOR 49 OCCUPANTS | | | WHEN THERE IS ONE EXIT. DOOR # 7 IS ALSO ADDING | | | ADDITIONAL OCCUPANTS FROM THE INTERIOR OF THE BUILDING. | | | FBC-B 1027.1. THE EXIT DISCHARGE SHALL NOT REENTER THE | | | BUILDING. A SECOND MEANS OF EXITING WILL BE REQUIRED | | | FOR THIS AREA. | | | | | | 8C) LOWER LEVEL, STAIR # 3 SHOWS A DOOR OPENING INTO | | | THE ENCLOSURE FROM THE CASH VESTIBULE. EXIT ACCESS | | | CORRIDORS ARE TO SEND OCCUPANTS INTO VERTICAL EXITS. | | | THE LIFE SAFETY PLAN INDICATES THE VERTICAL EXIT WITH | | | FIRE RATED WALLS, FIRE BARRIERS. | | | PLEASE REVIEW 2014 FBC-B 1022.5 PENETRATIONS. | | | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT | | | STAIRWAYS ARE PROHIBITED EXCEPT FOR REQUIRED EXIT | | | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT | | | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT | | | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING | | | THE INTERIOR EXIT STAIRWAY TERMINATING AT A STEEL BOX | | | NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | | PENETRATIONS SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL | | | BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT | | | STAIRWAYS AND RAMPS. | | | | | | 8D) LOWER LEVEL. STAIR # 4 SHOWS AT DOOR # 1 A MAXIMUM | | | OF 227 OCCUPANTS ARE ALLOWED TO TRAVEL THROUGH A 34 | | | INCH WIDE CLEAR DOOR OPENING. THE EXTERIOR DOOR IN THE | | | SAME STAIRWELL IS NOT IDENTIFIED AS TO WIDTH BUT | | | DEPICTED AS A SINGLE 3 FOOT WIDE DOOR WITH AN OCCUPANT | | | LOAD OF 575 OCCUPANTS? PLEASE EXPLAIN? | | | IT APPEARS YOU WERE USING THE 0.15 EGRESS FACTOR ON | | | DOOR #1 OF THE STAIRWELL? | | | FBC-B 1005.3.2 OTHER EGRESS COMPONENTS. EXCEPTION, | | | OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF | | | EGRESS CAPACITY FACTOR OF 0.15 INCH (3.8 MM) PER | | | OCCUPANT IN BUILDINGS EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH | | | SECTION 903.3.1.1 OR 903.3.1.2 AND AN EMERGENCY | | | VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH | | | SECTION 907.5.2.2. | | | | | | 8E) PLEASE BE AWARE THAT THE OCCUPANT LOADS TAKEN FOR | | | DOORS IS OFF. EXAMPLE 34 / 0.15= 226.66 YOU ROUNDED UP | | | TO 227. THIS HAPPENS AT ALL SINGLE 34 INCH DOORS. WHEN | | | YOU HAVE A PORTION OF AN OCCUPANT YOU ALWAYS ROUND | | | DOWN, THERE ARE NOT PARTS OF AN OCCUPANT. FLORIDA | | | BUILDING CODE INFORMAL INTERPRETATION REPORT 5479, | | | DATED 12/18/2007. THE FLORIDA BUILDING OFFICIALS | | | ASSOCIATION OF FLORIDA, IN COOPERATION WITH THE FLORIDA | | | BUILDING COMMISSION, THE FLORIDA DEPARTMENT OF | | | COMMUNITY AFFAIRS. | | | | | | 8F) MAIN LEVEL. STAIR 3 HAS AN ENTRY DOOR FROM THE | | | PANTRY/ SERVER STATION OPENING DIRECTLY INTO THE | | | STAIRWELL. PLEASE REVIEW 2014 FBC-B 1022.5 | | | PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH | | | INTERIOR EXIT STAIRWAYS ARE PROHIBITED EXCEPT FOR | | | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY | | | FOR INDEPENDENT VENTILATION OR PRESSURIZATION, | | | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR | | | FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL | | | RACEWAY SERVING THE INTERIOR EXIT STAIRWAY TERMINATING | | | AT A STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 | | | M2). SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE | | | WITH SECTION 714. THERE SHALL BE NO PENETRATIONS OR | | | COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, | | | BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS. | | | | | | 8G) STAIR # 2 IS CONSIDERED AN EXIT ACCESS STAIRWAY AND | | | HAVING TO MEET THE REQUIREMENTS FOUND UNDER 2014 FBC-B | | | 1009.3 EXCEPTION 4. THE LIFE SAFETY PLAN SHOWS ON THE | | | UPPER FLOOR AND MAIN FLOOR THE STAIR IS PROTECTED BY A | | | DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS IN | | | ACCORDANCE WITH NFPA BUT THIS NOTE IS NOT FOUND ON THE | | | LOWER FLOOR. PLEASE ADD NOTE TO THE LOWER FLOOR FOR | | | CODE COMPLIANCE WITH: 2014 FBC-B 1009.3 EXCEPTION 4. | | | | | | 8H) STAIR # 2 IS CONSIDERED AN EXIT ACCESS STAIRWAY | | | PLEASE PROVIDE HOW COMPLIANCE WITH SECTION 1016.3.1 IS | | | ACHIEVED. INDICATE THE FURTHEST DISTANCE ON THE UPPER | | | LEVEL TO THE 1ST FLOOR EXIT IS ACHIEVED. | | | | | | 2014 FBC-B 1016.3.1 EXIT ACCESS STAIRWAYS AND RAMPS. | | | TRAVEL DISTANCE ON EXIT ACCESS STAIRWAYS OR RAMPS SHALL | | | BE INCLUDED IN THE EXIT ACCESS TRAVEL DISTANCE | | | MEASUREMENT. THE MEASUREMENT ALONG STAIRWAYS SHALL BE | | | MADE ON A PLANE PARALLEL AND TANGENT TO THE STAIR TREAD | | | NOSINGS IN THE CENTER OF THE STAIR AND LANDINGS. THE | | | MEASUREMENT ALONG RAMPS SHALL BE MADE ON THE WALKING | | | SURFACE IN THE CENTER OF THE RAMP AND LANDINGS. | | | | | | 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS. | | | NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE | | | ACCESSIBILITY CODE: | | | 9A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE | | | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE | | | SEATING SPACES AND STANDING SPACES AT THE DINING | | | SURFACES SHALL COMPLY WITH 902. | | | | | | 9B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES | | | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | | SURFACES AND WORK SURFACES. | | | | | | 9C) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK | | | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, | | | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER | | | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON | | | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING | | | PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | ADVISORY 226.1. IN FACILITIES COVERED BY THE ADA, THIS | | | REQUIREMENT DOES NOT APPLY TO WORK SURFACES USED ONLY | | | BY EMPLOYEES. HOWEVER, THE ADA AND, WHERE APPLICABLE, | | | SECTION 504 OF THE REHABILITATION ACT OF 1973, AS | | | AMENDED, PROVIDE THAT EMPLOYEES ARE ENTITLED TO | | | ?REASONABLE ACCOMMODATIONS.? WITH RESPECT TO WORK | | | SURFACES, THIS MEANS THAT EMPLOYERS MAY NEED TO PROCURE | | | OR ADJUST WORK STATIONS SUCH AS DESKS, LABORATORY AND | | | WORK BENCHES, FUME HOODS, RECEPTION COUNTERS, TELLER | | | WINDOWS, STUDY CARRELS, COMMERCIAL KITCHEN COUNTERS, | | | AND CONFERENCE TABLES TO ACCOMMODATE THE INDIVIDUAL | | | NEEDS OF EMPLOYEES WITH DISABILITIES ON AN ?AS NEEDED? | | | BASIS. CONSIDER WORK SURFACES THAT ARE FLEXIBLE AND | | | PERMIT INSTALLATION AT VARIABLE HEIGHTS AND CLEARANCES. | | | | | | 10) NONE OF THE CIVIL PLANS WERE UPLOADED AS PART OF | | | THIS REVIEW. COMPLIANCE WITH THE 2014 ACCESSIBILITY | | | REQUIREMENTS CANNOT BE VERIFIED, NEED PLANS UPLOADED | | | FOR THE NEXT REVIEW: | | | | | | 10A) 206.2.1. SITE ARRIVAL POINTS. AT LEAST ONE | | | ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN THE SITE FROM | | | ACCESSIBLE PARKING SPACES AND ACCESSIBLE PASSENGER | | | LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; AND PUBLIC | | | TRANSPORTATION STOPS TO THE ACCESSIBLE BUILDING OR | | | FACILITY ENTRANCE THEY SERVE. | | | | | | 10B) 206.2.2. WITHIN A SITE. AT LEAST ONE ACCESSIBLE | | | ROUTE SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE | | | FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES | | | THAT ARE ON THE SAME SITE. | | | | | | 10C) 208.2 MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES. | | | PARKING SPACES COMPLYING WITH 502 SHALL BE PROVIDED IN | | | ACCORDANCE WITH TABLE 208.2 EXCEPT AS REQUIRED BY | | | 208.2.1, 208.2.2, AND 208.2.3. WHERE MORE THAN ONE | | | PARKING FACILITY IS PROVIDED ON A SITE, THE NUMBER OF | | | ACCESSIBLE SPACES PROVIDED ON THE SITE SHALL BE | | | CALCULATED ACCORDING TO THE NUMBER OF SPACES REQUIRED | | | FOR EACH PARKING FACILITY. | | | | | | 10D) 208.2.4 VAN PARKING SPACES. WHERE VAN PARKING IS | | | PROVIDED PURSUANT TO SECTION 502.2, FOR EVERY SIX OR | | | FRACTION OF SIX PARKING SPACES REQUIRED BY 208.2 TO | | | COMPLY WITH 502, AT LEAST ONE SHALL BE A VAN PARKING | | | SPACE COMPLYING WITH 502. | | | | | | 10E) 206.2.15 GOLF FACILITIES. AT LEAST ONE ACCESSIBLE | | | ROUTE SHALL CONNECT ACCESSIBLE ELEMENTS AND SPACES | | | WITHIN THE BOUNDARY OF THE GOLF COURSE. IN ADDITION, | | | ACCESSIBLE ROUTES SERVING GOLF CAR RENTAL AREAS; BAG | | | DROP AREAS; COURSE WEATHER SHELTERS COMPLYING WITH | | | 238.2.3; COURSE TOILET ROOMS; AND PRACTICE PUTTING | | | GREENS, PRACTICE TEEING GROUNDS, AND TEEING STATIONS AT | | | DRIVING RANGES COMPLYING WITH 238.3 SHALL COMPLY WITH | | | CHAPTER 4 EXCEPT AS MODIFIED BY 1006.2. | | | 11) 212-ROOF PLAN A2-04A- AREA A & 213 ROOF PLAN | | | A2-04-B AREA B: | | | | | | 11A) BOTH ROOF PLANS SHOW THE USE OF EMERGENCY OVER | | | FLOW SCUPPERS. THERE ARE 2 DETAILS FOR EMERGENCY | | | OVERFLOW SCUPPERS DETAIL 8 & 9 OF SHEET 243- A8-09. | | | PLEASE PROVIDE THE SQ. FT. AREA TO BE DRAINED BY BOTH | | | EMERGENCY OVERFLOW SCUPPERS INCLUDING ? OF THE HEIGHT | | | OF THE PARAPET. WHY IS DETAIL 8 SHOWING THE SIZE OF THE | | | SCUPPER 4X16 WHEREAS DETAIL 9 SHOW A SIZE OF 8X16 TWICE | | | AS LARGE FOR CLOSE TO THE SAME AREA? | | | | | | 2014 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW) | | | DRAINS OR SCUPPERS. | | | WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY | | | OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED | | | WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE | | | ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF | | | THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. THE | | | INSTALLATION AND SIZING OF SECONDARY EMERGENCY OVERFLOW | | | DRAINS, LEADERS AND CONDUCTORS SHALL COMPLY WITH | | | SECTIONS 1106 AND 1107, AS APPLICABLE, OF CHAPTER 11 OF | | | THE FLORIDA BUILDING CODE, PLUMBING. | | | | | | 11B) SHEET 213-A2-04B. ON BOTH ROOF DRAINAGE SHEETS THE | | | PLANS SHOW A DETAIL # 5 WITH 2 ROOF DRAINS 4 FEET APART | | | CENTER TO CENTER BUT AT THE SAME ELEVATION. DOES IT | | | TAKE 2 DRAINS TO TAKE THE WATER OFF THE ROOF OR IS IT | | | THE INTENT FOR ONE OF THE ROOF DRAINS TO BE CONSIDERED | | | THE SECONDARY EMERGENCY OVERFLOW DRAIN? | | | IF THE ONE DRAIN IS TO BE CONSIDER A SECONDARY | | | EMERGENCY OVERFLOW DRAIN A SEPARATE SYSTEM IS REQUIRED. | | | SHEET 616-P4-2 SHOWS A 6 INCH ROOF DRAIN AND A 6 INCH | | | OVERFLOW DRAIN EMPTYING INTO THE SAME RISER (1555). SEE | | | FBC-P 1108.2. | | | | | | 10C) SHEET 611P2-3-B PLEASE SEE STAIRWELL # 3. A 6 INCH | | | ROOF DRAIN IS IN STAIRWELL # 3. | | | PLEASE REVIEW 2014 FBC-B 1022.5 PENETRATIONS. | | | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT | | | STAIRWAYS ARE PROHIBITED EXCEPT FOR REQUIRED EXIT | | | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT | | | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT | | | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING | | | THE INTERIOR EXIT STAIRWAY TERMINATING AT A STEEL BOX | | | NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | | PENETRATIONS SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL | | | BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT | | | STAIRWAYS AND RAMPS. | | | | | | 11) PLEASE NOTE THAT THE SUBMITTED PRODUCT APPROVALS | | | CANNOT BE REVIEWED FOR POSITIVE AND NEGATIVE PRESSURES | | | UNTIL THE CORRECT WIND DESIGN CRITERIA AND PRESSURES | | | ARE PROVIDE. SEE COMMENTS 7E AND 7F. | | | | | | 12) PLEASE SHOW COMPLIANCE WITH: | | | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 13) KAWNEER COMPANY CURTAIN WALL 1600 SYSTEM PLEASE | | | SUBMIT EITHER A MIAMI-DADE OR FLORIDA APPROVAL WITH | | | THIS TEST REPORT. , 1609.6.4.4.1 COMPONENTS & CLADDING. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE | | | CODE 61G20-3.005, | | | | | | 14A) CENTRIA INTERCEPT ENTYRE PANEL SYSTEM, PLEASE | | | PROVIDE WHERE THIS SYSTEM IS TO BE INSTALLED ON THE | | | BUILDING, AND WHAT TYPE OF BACKING IS REQUIRED. | | | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 14B) CENTRIA INTERCEPT ENTYRE PANEL SYSTEM PLEASE | | | SUBMIT EITHER A MIAMI-DADE OR FLORIDA APPROVAL WITH | | | THIS TEST REPORT. , 1609.6.4.4.1 COMPONENTS & CLADDING. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE | | | CODE 61G20-3.005, | | | | | | 15) CECO DOOR IT APPEARS HAS A FLORIDA APPROVAL, SUBMIT | | | THE COVERSHEETS FOR FL 16355.1-R1. , 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | | | | 16) OVERHEAD DOORS SERIES521 & 610/620 ROLLING STEEL | | | DOORS, PLEASE SUBMIT THE FLORIDA APPROVAL COVERSHEETS. | | | , 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA | | | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE | | | 61G20-3.005, | | | | | | 17A) ROOFING REPORT CARLISLE SUBMIT THE FLORIDA | | | APPROVAL COVERSHEET FOR FL 16440-R10. | | | | | | 17B) PLEASE NOTE NONE OF THE SUB-SYSTEMS HAVE BEEN | | | IDENTIFIED WITH ASSOCIATED PRESSURES. REVIEW | | | LIMITATIONS AS TO IF ENHANCED FASTENING CAN OCCUR. | | | 107.2.1.3. ADDITIONAL INFORMATION REQUIRED. | | | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING | | | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF | | | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF | | | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. | | | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION | | | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. | | | 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 18) EURO-LS100 LIFT AND SLIDING GLASS DOORS PLEASE | | | PROVIDE EITHER A FLORIDA APPROVAL OR MIAMI-DADE NOA. | | | , 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA | | | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE | | | 61G20-3.005, | | | | | | 19) KAWNEER IR501 LMI ALUMINUM STORE FRONT SYSTEMS, | | | PLEASE SUBMIT EITHER A MIAMI-DADE OR FLORIDA APPROVAL | | | WITH THIS TEST REPORT. , 1609.6.4.4.1 COMPONENTS & | | | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, | | | ADMINISTRATIVE CODE 61G20-3.005, | | | | | | 20) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 21) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. | | | | | | 22) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL | | | FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE | | | MANUFACTURERS INSTALLATION BROCHURE PROVIDING | | | COMPLIANCE WITH 2014 FBC-B SECTIONS; | | | 1408.2 PERFORMANCE CHARACTERISTICS. | | | 1408.2 PERFORMANCE CHARACTERISTICS. | | | 1408.3 STRUCTURAL DESIGN. | | | 1408.4 WEATHER RESISTANCE. | | | 1408.4.1 EIFS WITH DRAINAGE. | | | 408.4.1.1 WATER-RESISTIVE BARRIER. | | | 1408.5 INSTALLATION. | | | | | | 23) LATERAL FORCE-RESISTING SYSTEM FOR ALL ROOF TOP | | | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE | | | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY | | | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS | | | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE | | | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE | | | CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-06 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-06 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-10 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-10 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2018-08-10 07:32:39 | NO CHANGES TO PREVIOUSLY APPROVED PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-04-04 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-04-04 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-04-04 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-01-11 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-11 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-09 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2018-01-11 10:36:07 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. PLANS FOR | | | ANY OF THESE SYSTEMS WILL NEED TO BE SUBMITTED AT TIME | | | OF APPLICATION FOR PERMIT. FBC 105.1, 107.2.1 | | | 2. FEEDER SCHEDULES SHOW A # 2 EQUIPMENT GROUNDING | | | CONDUCTOR (EGC) FOR THE 450 AMP FEEDER. PARALLEL | | | FEEDERS ARE REQUIRED TO HAVE THE EGC SIZED FOR THE | | | CIRCUIT IN EACH CONDUIT, WHICH WOULD BE A 1/0 AL | | | CONDUCTOR. PROVIDE CORRECTION. NEC 250.122(F) | | | 3. LOAD CALCULATION SHOWS SEVERAL LOADS WITH DEMAND | | | FACTORS NOT TO CODE. THIS MAY BE A FUNCTION OF THE | | | PROGRAM USED. EXAMPLE: HVAC LOAD IS SHOWN WITH 90% | | | DEMAND, KITCHEN IS SHOWN WITH 90% DEMAND, MISCELLANEOUS | | | IS SHOWS AT 70% DEMAND. HOWEVER, IT IS REQUIRED TO SHOW | | | A LOAD CALCULATION FOR FEEDERS AND SERVICE THAT WILL | | | HANDLE 125% OF THE CONTINUOUS LOAD PLUS 100% OF THE NON | | | CONTINUOUS LOAD. PROVIDE LOAD CALCULATIONS WITH THESE | | | DETAILS. NEC 220.40, 215.2 | | | 4. SHOW COMPLIANCE WITH NEC 240.87 | | | 5. AN ESTIMATED FAULT CURRENT FROM POWER COMPANY IS NOT | | | ACCEPTABLE. PROVIDE LETTER FROM FPL WITH FAULT CURRENT | | | AT SOURCE AND USE THIS INFORMATION IN CALCULATION. FBC | | | 107.2.1, NEC 110.10 | | | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 7. FOOD SERVICE/KITCHEN AREAS REQUIRE THAT ALL | | | RECEPTACLE OUTLETS BE GFCI PROTECTED, NOT JUST THOSE | | | THAT SERVE THE COUNTERTOP. PROVIDE CORRECTION. NEC | | | 210.8(B)(2),(6) | | | 8. SHEET E8-1, SERVICE GROUNDING DETAIL, SHOWS THE | | | "MAIN BONDING JUMPER" SIZED AT 3/0. THIS SHOULD BE | | | SIZED AT 12.5% OF THE AREA OF THE PHASE CONDUCTORS. | | | BASED ON CURRENTLY SHOWN FEEDERS THIS WOULD EQUAL: 600 | | | KCMIL X 5 RUNS= 3000000 X 12.5% = 375000. THIS MAIN | | | BONDING JUMPER WOULD NEED TO BE SIZED A MINIMUM OF 375 | | | KCMIL, WHICH THE NEXT SIZE AVAILABLE IS 400 KCMIL. | | | PROVIDE CORRECTION. NEC 250.28(D)(1) | | | 9. PANEL 1GR2 IS SHOWN AS A 100 AMP MAIN LUG ONLY PANEL | | | WITH 111 AMPS ON A PHASE, 101 AMPS ON B PHASE, AND 106 | | | AMPS ON C PHASE. PANEL MUST BE SIZED TO HANDLE THE | | | LOAD. PROVIDE CORRECTION. NEC 408.30 | | | 10. PANEL 2CR2 IS SHOWN AS A 200 AMP MAIN LUG ONLY | | | PANEL WITH 208 AMPS ON A PHASE, 186 AMPS ON B PHASE, | | | AND 222 AMPS ON C PHASE. PANEL MUST BE SIZED TO HANDLE | | | THE LOAD. PROVIDE CORRECTION. NEC 408.30 | | | 11. PANEL 2CR3 IS SHOWN AS A 150 AMP MAIN LUG ONLY | | | PANEL WITH 184 AMPS ON A PHASE, 161 AMPS ON B PHASE, | | | AND 175 AMPS ON C PHASE. PANEL MUST BE SIZED TO HANDLE | | | THE LOAD. PROVIDE CORRECTION. NEC 408.30 | | | 12. IT APPEARS THERE WOULD BE A SUBSTANTIAL AMOUNT OF | | | NONLINEAR LOADS WITH THIS INSTALLATION. BASED ON THIS, | | | THE NEUTRAL CONDUCTOR WOULD BE COUNTED AS A CURRENT | | | CARRYING CONDUCTOR FOR FEEDERS PER NEC 310.15(B)(5)(C). | | | BASED ON THIS REASONING, WHEN APPLYING THE 80% DEMAND | | | FACTOR IN TABLE 310.15(B)(3), SEVERAL FEEDER SIZES ARE | | | INADEQUATE FOR THE LOADS SERVED. THIS WOULD INCLUDE THE | | | WIRE SIZES FOR 125, 150, 175, 200, 225, 250, 300, 450, | | | 500, 600, 800, AND 1600 AMP FEEDERS. PROVIDE | | | CORRECTION. NEC310.15(B)(3), 240.4(C) | | | 13. REVIEWER DID NOT SEE ANY CIRCUITS FOR DRINKING | | | FOUNTAINS. PROVIDE GFCI PROTECTION FOR DRINKING | | | FOUNTAIN IF INSTALLED. NEC 422.52 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2018-04-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-24 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-24 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2018-04-24 16:13:13 | BOND RECEIVED, OK TO PASS ENGINEERING PER MG | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2018-04-12 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2018-04-12 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2018-04-12 |
Time |
|
Sent To |
I |
|
| Notes |
| 2018-04-12 11:13:53 | CITY OF WPB ENG HAS NOT RECEIVED SURETY INSTRUMENT. | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2018-01-17 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
2018-01-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
2018-01-17 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-17 08:20:23 | 1) WILL REVIEW DURING NEXT REVISION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-08-31 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-12 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-03-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-03-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-03-13 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-12-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-12 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2017-12-21 15:21:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET LS 01 - THERE ARE STAIRS INDICATED TOWARDS THE | | | CENTER ON THE BUILDING.STAIR # 2. THERE IS NO | | | INDICATION OF THE TYPE OF OPENING THESE STAIRS | | | REPRESENT. PER THE FFPC, NFPA 101, CHAPTER 12 & 8 THESE | | | STAIRS SHALL CONFORM TO ONE OF THE FOLLOWING. | | | | | | 12.3 PROTECTION. | | | 12.3.1 PROTECTION OF VERTICAL OPENINGS. ANY VERTICAL | | | OPENING SHALL BE ENCLOSED OR PROTECTED IN ACCORDANCE | | | WITH SECTION 8.6, UNLESS OTHERWISE PERMITTED BY ONE OF | | | THE FOLLOWING: | | | (1)* STAIRS OR RAMPS SHALL BE PERMITTED TO BE | | | UNENCLOSED BETWEEN BALCONIES OR MEZZANINES AND MAIN | | | ASSEMBLY AREAS LOCATED BELOW, PROVIDED THAT THE BALCONY | | | OR MEZZANINE IS OPEN TO THE MAIN ASSEMBLY AREA. | | | (2) EXIT ACCESS STAIRS FROM LIGHTING AND ACCESS | | | CATWALKS, GALLERIES, AND GRIDIRONS SHALL NOT BE | | | REQUIRED TO BE ENCLOSED. | | | (3) ASSEMBLY OCCUPANCIES PROTECTED BY AN APPROVED, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH SECTION 9.7 SHALL BE PERMITTED TO HAVE UNPROTECTED | | | VERTICAL OPENINGS BETWEEN ANY TWO ADJACENT FLOORS, | | | PROVIDED THAT SUCH OPENINGS ARE SEPARATED FROM | | | UNPROTECTED VERTICAL OPENINGS SERVING OTHER FLOORS BY A | | | BARRIER COMPLYING WITH 8.6.5. | | | (4) ASSEMBLY OCCUPANCIES PROTECTED BY AN APPROVED, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITHSECTION 9.7 SHALL BE PERMITTED TO HAVE CONVENIENCE | | | STAIR OPENINGS IN ACCORDANCE WITH 8.6.9.2. | | | | | | 8.6.6 COMMUNICATING SPACE. | | | 8.6.7* ATRIUMS | | | 8.6.9 CONVENIENCE OPENINGS. | | | | | | PLEASE INDICATE WHICH ONE REPRESENTS THE PROPOSED AND | | | PROVIDE SPECIFIC DETAILS HOW IT COMPLIES WITH EACH OF | | | THE CONDITIONS. | | | | | | | | | | | | | | | 2) SHEET FP 00 - THERE ARE NO INDICATIONS OR DRAWINGS | | | RELATING THE CURTAIN WALL AND CLOSELY SPACED SPRINKLERS | | | NOTED IN # 1 ABOVE. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS OF THIS DESIGN ARA | | | REQIUREMENTS. | | | | | | | | | | | | | | | 3) SHEET LS 01 - THERE IS AN INDICATION INVOLVING STAIR | | | # 2 OF A "DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS". | | | THERE ARE NO DETAILS INDICATED OR SPECIFIC FIRE CODE | | | REFERENCES THAT PERMIT THIS TYPE OF LIFE SAFETY | | | FEATURE. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | | | | 4) SHEET LS 01 - IN THE CLACULATION OF THE EGRESS | | | CAPACITY OF THE STAIRS A 0.2 FIGURE IS BEING USED. PER | | | NFPA 101, CHAPTER 7, MEANS OF EGRESS 0.3 SHALL BE USED. | | | THE EXCEPTION IN THE BUILDING CODE DOES NOT APPLY TO | | | THE FIRE CODE. | | | | | | 7.3.3* EGRESS CAPACITY. | | | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF | | | MEANS OF EGRESS SHALL BE BASED ON THE CAPACITY FACTORS | | | SHOWN IN TABLE | | | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 . | | | THE TABLE INDICATES "ALL OTHERS 0.3" | | | | | | PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATIONS. | | | | | | | | | | | | 5) SHEET LS 01 - IN THE CALCULATION OF THE EGRESS | | | CAPACITY FO THE EXIT DOOR A .15 IS BEING USED, PER NFPA | | | 101, CHAPTER 7, MEANS OF EGRESS 0.2 SHALL BE USED. THE | | | EXCEPTION IN THE BUILDING CODE DOES NOT APPLY TO THE | | | FIRE CODE. | | | | | | 7.3.3* EGRESS CAPACITY. | | | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF | | | MEANS OF EGRESS SHALL BE BASED ON THE CAPACITY FACTORS | | | SHOWN IN TABLE | | | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 . | | | THE TABLE INDICATES "ALL OTHERS 0.2" | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | 6) SHEETS FP & FP 01 - THERE ARE NO INDICATIONS | | | RELATING TO THE CURTAIN WALL AND CLOSELY SPACED | | | SPRINKLERS. THE EOR SHALL MAKE REFERENCE AND ACCEPT THE | | | DESIGN AND FUNCTION OF THE PROPOSED OF # 1 ABOVE. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-04-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-03 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-03 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-25 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-25 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2018-01-25 09:53:21 | | | | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. CLEARLY SHOW ALL CUT SECTIONS OF PIPE AND | | | CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS. | | | 402.4.1, 402.4.2. | | | | | | 2. ON THE RISER SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, AND PRESURE. WPB AMENDMENTS TO FBC SEC. | | | 107.2.1. | | | | | | | | | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | | | | 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 6. PLEASE PROVIDE SIZING TABLES USED FROM FBC FG 402 | | | | | | 7. SHT. FS-12 SHOWS A ROOF TOP EQUIPMENT R6 WITH A MBH | | | LOAD OF 288 IT IS NOT SHOWN ON THE GAS RISER PLEASE | | | CLARIFY PER WPB AMEND TO FBC 107.2.1 | | | | | | 8. SHT. FS-07 SHOWS EQUIPMENT #5-10 WITH A QUANITY OF 1 | | | AND A MBH LOAD OF (3) 40 THE GAS RISER SHOWS IT AS 40 | | | MBTU PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 9. SHT. P7-1 THE TOTAL MBH ON THE KITCHEN COOKING | | | ISOMETRIC ADDS UO TP 1391 MBH THE MAIN RISER SHOWS AN | | | 11/2? PIPE TO THE KITCHEN WITH 1471 MBH PLEASE CLARIFY. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 10. LABEL THE GAS RISER TO MATCH THE FLOOR PLAN. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 11. PLEASE PROVIDE AN EXPANDED ISOMETRIC FOR THE AREA | | | OF THE KITCEN AND WATER HEATERS COMBINED THE AREA IS TO | | | CONJESTED ON THE MAIN RISER. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-11 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-27 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-17 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-10 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-04-23 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-04-23 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-18 |
Time |
15:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-04-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-12 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-12 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2018-04-12 10:17:04 | SENT EMAIL REQUEST FOR ENGINEERING TO DO REVIEW | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-26 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-11 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-06 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-06 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2018-09-06 19:02:50 | MU-2018-014951-0000 | | | $56,524.64 | | | | | | PAID WITH REVISION 18071337 EXPAND FOUNDATION TO | | | VERTICAL SHELL | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-19 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-19 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2018-07-19 18:49:08 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-03-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-03-30 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-03-30 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2018-03-30 07:16:03 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-09 |
Time |
07:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-12-21 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2018-01-09 07:04:38 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-09-06 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-09-05 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2018-09-06 14:06:22 | MECHANICAL PROVISOS: | | | CCOLE- 9/6/18 | | | | | | THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS AS | | | REQUESTED. PLEASE NOTE THAT ALL SUBMITTALS, AND ALL | | | DELEGATED ENGINEERING, SHOP DRAWINGS ETC. SHALL BEAR | | | APPROVAL STAMPS BY THE ENGINEER OF RECORD. | | | | | | 1) WIND LOAD ENGINEERING FOR ALL ROOFTOP AND EXTERIOR | | | MECHANICAL EQUIPMENT INCLUDING THE RTU'S, RTU CURBS, | | | CONDENSERS AND STANDS, DUCTWORK AND SUPPORTS, FANS AND | | | FAN CURBS, PIPE STANDS AND BRACKETS, INFRARED HEATERS, | | | DESTRATIFICATION FANS, ETC. | | | | | | 2) MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR | | | LOUVERS AND ROOF STANDS, INCLUDING PRODUCT DATA SHEETS | | | FOR THE LOUVERS FROM THE MANUFACTURER. | | | | | | 3) WATER HEATER AND WATER HEATER VENT PIPING. | | | | | | 4) FIRE DAMPERS, AND FIRE/SMOKE DAMPERS. | | | | | | 5) DUCT SMOKE DETECTORS. | | | | | | 6) MOTORIZED DAMPERS. | | | | | | 7) REFRIGERANT RISER DIAGRAM FOR THE AAON FAN COIL | | | SYSTEMS. | | | | | | 8) KITCHEN COOKING APPLIANCES | | | | | | 9) FIRESTOPPING | | | | | | 10) PIPE AND DUCT INSULATIONS. | | | | | | 11) GREASE DUCT ENCLOSURE WRAPPING. | | | | | | 12) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL | | | LIGHTING SYSTEMS. | | | | | | ADVISORY: PLEASE NOTE THAT THE FINAL COMMISSIONING | | | REPORT MUST BE SUBMITTED TO BOTH THE OWNERSHIP OF THE | | | BUILDING AND THE BUILDING DEPARTMENT PRIOR TO RECEIVING | | | THE CERTIFICATE OF OCCUPANCY. | | | | | | ADVISORY: SEPATRATE PERMITS ARE REQUIRED FOR THE | | | KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, FIRE | | | SPRINKLERS, FIRE ALARM, AND WALK-IN COOLER AND FREEZER. | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-08-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-10 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-09 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2018-08-10 08:16:57 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | | FUEL GAS CODES, AND WEST PALM BEACH AMENDMENTS TO THE | | | FBC-14 | | | PERMIT #17120261 | | | 8/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE UPDATED COMCHECK ENERGY CERTIFICATE IS NOT | | | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER OF | | | RECORD- SECTION 61G15-23.005 FAC. | | | | | | 2) SHEETS M2-2-B & M2-3-B: PLEASE ADD NOTES TO THE | | | DRAWING TO INDICATE THE GREASE EXHAUST DUCT WILL BE | | | ENCLOSED BY A FIELD-APPLIED GREASE DUCT ENCLOSURE THAT | | | IS A LISTED AND LABELED WRAPPING MATERIAL OR PRODUCT | | | THAT HAS BEEN SPECIFICALLY EVALUATED FOR SUCH PURPOSE | | | IN ACCORDANCE WITH ASTM E 2336. PLEASE PROVIDE THE NAME | | | OF THE PRODUCT ON THE PLAN AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS. | | | | | | 3) MEPO-2: PLEASE CLARIFY WHY NO HEAT RECOVERY COOLING | | | OR HEATING DATA FOR RTU-3 IS SHOWN IN THE SCHEDULE. | | | | | | 4) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS AS | | | REQUESTED. PLEASE NOTE THAT ALL SUBMITTALS, AND ALL | | | DELEGATED ENGINEERING, SHOP DRAWINGS ETC. SHALL BEAR | | | APPROVAL STAMPS BY THE ENGINEER OF RECORD. | | | | | | A) WIND LOAD ENGINEERING FOR ALL ROOFTOP AND EXTERIOR | | | MECHANICAL EQUIPMENT INCLUDING THE RTU'S, RTU CURBS, | | | CONDENSERS AND STANDS, DUCTWORK AND SUPPORTS, FANS AND | | | FAN CURBS, PIPE STANDS AND BRACKETS, INFRARED HEATERS, | | | DESTRATIFICATION FANS, ETC. | | | | | | B) MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR | | | LOUVERS AND ROOF STANDS, INCLUDING PRODUCT DATA SHEETS | | | FOR THE LOUVERS FROM THE MANUFACTURER. | | | | | | C) WATER HEATER AND WATER HEATER VENT PIPING. | | | | | | D) FIRE DAMPERS. | | | | | | E) DUCT SMOKE DETECTORS. | | | | | | F) MOTORIZED DAMPERS. | | | | | | G) REFRIGERANT RISER DIAGRAM FOR THE AAON FAN COIL | | | SYSTEMS. | | | | | | H) KITCHEN COOKING APPLIANCES | | | | | | I) FIRESTOPPING | | | | | | J) PIPE AND DUCT INSULATIONS. | | | | | | K) GREASE DUCT ENCLOSURE WRAPPING. | | | | | | L) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL | | | LIGHTING SYSTEMS. | | | | | | ADVISORY: PLEASE NOTE THAT THE FINAL COMMISSIONING | | | REPORT MUST BE SUBMITTED TO BOTH THE OWNERSHIP OF THE | | | BUILDING AND THE BUILDING DEPARTMENT PRIOR TO RECEIVING | | | THE CERTIFICATE OF OCCUPANCY. | | | | | | ADVISORY: SEPATRATE PERMITS ARE REQUIRED FOR THE | | | KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, FIRE | | | SPRINKLERS, FIRE ALARM, AND WALK-IN COOLER AND FREEZER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-04-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-04-05 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-03 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2018-04-05 07:30:49 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | | FUEL GAS CODES, AND WEST PALM BEACH AMENDMENTS TO THE | | | FBC-14 | | | PERMIT #17120261 | | | 1/12/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC CALCULATIONS FOR RTU-1, 2, & 3 MUST BE | | | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO | | | PREPARED THE CALCULATIONS- SECTION 105.3.1.2(3) WPB | | | AMENDMENTS TO THE FBC, AND SECTIONS 61G15-23.001 AND | | | 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. | | | | | | 2) SHEET MEPO-2: A) AC SYSTEMS FCU-103, FCU-104, | | | AC-101, AC-102, AND AC-302 ARE OVERSIZED PER THE | | | SUBMITTED AC CALCULATIONS- SECTION C403.2.2 FBC-14 | | | ENERGY CONSERVATION. B) THE SCHEDULE SHOWS A DEFICIENT | | | AMOUNT OF 1100 CFMS OF SUPPLY AIR FOR FC-104 WHICH IS A | | | 4-TON SYSTEM. | | | | | | 3) COMCHECK COMPLIANCE AND SHEETS MEPO-2 & MEPO-3: A) | | | THE RTU CAPACITIES AND EER'S AS LISTED IN THE COMCHECK | | | REPORT DO NOT MATCH THE CAPACITIES AND EER'S IN THE | | | SCHEDULES. B) NO EER IS LISTED IN THE SCHEDULE FOR | | | MAU-1. C) NO EER'S OR SEER'S FOR THE FAN COIL UNITS AND | | | SPLIT SYSTEMS HAVE BEEN PROVIDED IN THE SCHEDULES TO | | | COMPARE WITH THE RATINGS SHOWN IN THE CALCULATIONS. | | | | | | 4) THE SUBMITTED CUT SHEETS FOR THE SPACE-RAY OUTDOOR | | | INFRARED HEATERS DO NOT PROVIDE EVIDENCE OF COMPLIANCE | | | WITH ANSI Z83.19 OR Z83.20- SECTION 630.1 FBC-14 FUEL | | | GAS. | | | | | | 5) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PLEASE | | | PROVIDE A COMMISSIONING PLAN AS OUTLINED IN SECTION | | | C408.2.1 FBC-14 ENERGY CONSERVATION. ACCORDING TO THE | | | RESPONSE NARRATIVE TO THE 1ST REVIEW COMMENTS, THERE | | | ARE NOTES ON SHEET M0-1 CLARIFYING THE COMMISSIONING | | | PLAN. I WAS NOT ABLE TO LOCATE ANY NOTES ON THIS SHEET. | | | | | | 6) SHEET M2-1B: EXHAUST SYSTEMS ARE REQUIRED FOR THE | | | FITTING ROOMS- TABLE 403.3. | | | | | | 7) SHEETS M2-2-B & M2-3-B: THE MAU-1 DUCT, AND THE | | | RTU-3 SUPPLY AND RETURN DUCT CANNOT BE LOCATED IN THE | | | SAME SHAFT OR CHASE WITH THE GREASE EXHAUST DUCT IN | | | ACCORDANCE WITH SECTION 506.3.11. CLARIFY IS THE GREASE | | | EXHAUST DUCT IS TO BE ENCLOSED IN A SEPARATE SHAFT, OR | | | HAVE A FIELD-APPLIED ENCLOSURE SUCH AS FIREWRAPPING | | | THAT IS COMPLIANT WITH ASTM E 2336. | | | | | | 8) PLEASE PLACE THE COMBUSTION AIR CALCULATION FOR THE | | | GAS-FIRED COOKING APPLIANCES ONTO THE PLAN. | | | | | | 9) WIND LOAD ENGINEERING FOR THE ROOFTOP MECHANICAL | | | EQUIPMENT, THE DESTRATIFICATION FANS, AND INFRARED | | | HEATERS IS ACKNOWLEDGED TO BE DEFERRED SUBMITTALS. | | | ADDITIONAL REQUIRED SUBMITTALS TO BE PROVIDED AT THE | | | PRESENT TIME OR AS DEFERRED SUBMITTALS INCLUDE: AC | | | STANDS, RTU AND FAN CURBS, DUCT AND PIPE STANDS AND | | | BRACKETS FOR ROOFTOP ATTACHMENT, FIRE DAMPERS, SMOKE | | | DETECTORS, MOTORIZED DAMPERS, EXHAUST AND O/A LOUVERS, | | | WATER HEATER AND WATER HEATER VENT PIPING. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-16 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-16 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2018-01-16 16:51:35 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #17120261 | | | 1/12/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC | | | SYSTEMS INCLUDING THE RTU'S, THE SPLIT SYSTEMS, THE FAN | | | COIL UNITS, THE INFRARED HEATERS, THE ECUH'S, AND | | | EUH'S. - SECTION C403.2.1 FBC-14 ENERGY CONSERVATION | | | AND SECTION 312.1 FBC-14 MECHANICAL. | | | | | | 2) THE COMCHECK ENERGY COMPLIANCE SUBMITTAL DOES NOT | | | PROVIDE COMPLIANCE DATA FOR ANY OF THE PROPOSED HVAC | | | SYSTEMS INCLUDING THE RTU'S, THE SPLIT SYSTEMS, THE FAN | | | COIL UNITS, THE INFRARED HEATERS, THE ECUH'S, AND | | | EUH'S- TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. | | | | | | 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED | | | PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A | | | COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND | | | DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE | | | THAT A COPY OF THE COMMISSIONING REPORT SHALL BE | | | SUBMITTED FOR REVIEW AT FINAL INSPECTION. | | | | | | 4) SHEET MEPO-3: PROVIDE EXHAUST VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES BEING EXHAUSTED | | | THROUGH RTU'S 1 & 2. REFER TO TABLE 403.3 FOOTNOTE G | | | AND VERIFY NO MORE THAN 10% OF AIR EXHAUSTED FROM THE | | | BATHROOMS AND LOCKERS ROOMS IS BEING RECIRCULATED. | | | | | | 5) MEPO-3: THE AIR BALANCE SCHEDULE FOR RTU-1 & 2 SHOWS | | | MORE AIR BEING RETURN THAN IS BEING SUPPLIED- PLEASE | | | CLARIFY. | | | | | | 6) SHEETS M2-1A, M2-1B, M2-2A, M2-2B, M2.3-A, M2.3-B, | | | M2.4-A, M2-4B: IN ORDER TO HELP EXPEDITE THE REVIEW | | | PLEASE IDENTIFY ALL ROOMS AND SPACES SHOWN ON THE | | | LAYOUT PLANS. | | | | | | 7) SHEETS M2-1A & M2-1B: PLEASE CLARIFY HOW AIR | | | SUPPLIED TO THE ROOMS AND SPACES SHOWN ON THE PLANS IS | | | BEING RETURNED TO RTU-1. | | | | | | 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | | SYSTEMS OF: A) RTU'S 1- 4. B) FCU'S 103 & 104. C) AC | | | 101- SECTION 606.2.1. PLEASE SHOW THE LOCATIONS OF THE | | | DEVICES ON THE PLANS. PLEASE NOTE SMOKE DETECTORS ARE | | | ALSO REQUIRED FOR COMMON RETURN AIR PLENUMS WITH | | | DESIGNE CAPACITIES GREATER THAN 200 CFMS- SECTION | | | 606.2.2. | | | | | | 9) DUCT SMOKE DETECTORS ARE REQUIRED FOR THE RETURN AIR | | | RISER SERVING RTU-2. THE SMOKE DETECTORS SHALL BE | | | PLACED AT EACH STORY- SECTION 606.2.3 | | | | | | 10) WIND LOAD ENGINEERING IS REQUIRED FOR ALL EXTERIOR | | | MECHANICAL EQUIPMENT AND APPLIANCE INSTALLATIONS PER | | | SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609 | | | FBC-14 BUILDING. PLEASE CORRECT THE NOTES ON SHEET M8-1 | | | SPECIFYING 140 MPH WIND SPEED AND RISK CATEGORY III. | | | REFER TO SECTION 1609.1.1 AND PROVIDE THE CORRECT | | | DESIGN CRITERIA. SUBMIT VALID FLORIDA PRODUCT | | | | | | APPROVALS AND/OR MIAMI-DADE NOA'S FOR ANY RTU CURBS, | | | ROOF STANDS, CONDENSER CLIPS, FANS, FAN CURBS, AND O/A | | | AND EXHAUST LOUVERS TO BE USED ON THE PROJECT- RULE | | | 9N-3 FAC. ALL SUBMITTALS SHALL HAVE SHOP DRAWING STAMPS | | | BY THE EOR. | | | | | | 11) M8-1 & M8-2: PROVIDE COMPLETE ANCHORING AND | | | ATTACHMENT DETAILS: RTU CURBS TO STRUCTURE, RTU TO | | | CURB, AC STAND TO STRUCTURE, AC CONDENSER TO STAND, FAN | | | CURBS TO STRUCTURE, FANS TO CURBS, AND ROOF TOP | | | DUCTWORK TO STRUCTURE. | | | | | | 12) PROVIDE WIND LOAD DESIGN CRITERIA AND INSTALLATION | | | DETAILS FOR THE INFRARED HEATERS AND THE | | | DESTRATIFICATION FANS- SECTION 301.15. | | | | | | 13) M7-1: PROVIDE CONTROLS OPERATION DETAILS AND | | | DIAGRAMS FOR THE INFRARED HEATERS AND DESTRATIFICATION | | | FANS | | | | | | 14) M8-1: PROVIDE A HORIZONTAL FIRE DAMPER DETAIL. | | | | | | 15) SUBMIT SPECS FOR THE WATER HEATERS AND VENT FLUES | | | AND PROVIDE EQUIPMENT SCHEDULES ON THE PLAN. | | | | | | 16) THE CONDENSATE IS NOTED IN MANY LOCATIONS ON THE | | | PLAN TO BE DRAINED ONTO SPLASH BLOCKS ON THE ROOF WHICH | | | IS NOT AN APPROVED PLACE OF DISPOSAL. REFER TO SECTION | | | 307 AND SHOW ALL PIPING RUNS, PIPING DETAILS AND | | | DISCHARGE LOCATIONS. | | | | | | 17) REFER TO SECTION 304 FBC-14 FUEL GAS AND PROVIDE | | | COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED COOKING | | | APPLIANCES. | | | | | | 18) ACCESS FOR SERVICE AND REPLACEMENT OF ALL ABOVE | | | CEILING FCU'S , HEATERS, FANS ETC. SHALL BE PROVIDED IN | | | ACCORDANCE WITH SECTION 306.1. PLEASE SHOW ACCESS PANEL | | | LOCATIONS ON THE PLAN AND INCLUDE PANEL DIMENSIONS. | | | | | | 19) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE | | | KITCHEN HOOD AND FIRE SUPPRESSION SYSTEM, AND WALK-IN | | | COOLER AND FREEZERS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
P |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2019-09-17 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2019-09-17 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-17 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-16 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-04-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-03 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-26 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2018-04-03 10:05:52 | | | | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS | | | | | | PARTIALLY COMPLIED 6. PLEASE PROVIDE A LABELING SYSTEM | | | FOR THE SANITARY, WATER AND GAS THAT WILL SHOW A | | | COHESIVE CORRELATION BETWEEN THE RISER?S ISOMETRIC | | | DRAWINGS AND FLOOR PLANS. PER WPB AMEND TO THE FBC | | | 107.2.1 | | | THE ISOMETRIC DRAWINGS ARE STILL EXTREMELY CONFUSING I | | | CANNOT DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC | | | 2017 SEC 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | A) THE TAGS ON THE SANITARY STACKS ON THE FLOOR PLAN | | | ARE ALL LABELLED THE SAME WITH THE KEY NOTE NUMBER | | | PLEASE TAG WITH INDIVIDUAL NUMBERS OR LETTERS THAT CAN | | | BE FOUND ON THE ISOMETRIC DRAWINGS. | | | B) ON THE ENLARGED ISOMETRIC DRAWINGS THE INDIVIDUAL | | | PIPES NEED TO BE LABELED MATCH TO THE PIPE IT IS | | | CONNECTED TO ON OTHER ISOMETRICS THE ONES SHOWN NOW | | | JUST INDICATE OTHER ISOMETRIC NOT INDIVIDUAL PIPES. | | | C) THE OVERALL ISOMETRIC ON SHT P7-3 NEEDS TO BE SPLIT | | | UP AND ENLARGED ALSO THE FIXTURE AND SOIL STACKS NEED | | | TO BE LABELED. | | | D) ON ALL THE ISOMETRIC DRAWING PLEASE REMOVE ALL STRAY | | | PIPING THAT IS NOT SHOWN TO CONNECT ANYWHERE OR LABEL | | | IT. | | | E) THE ENLARGED ISOMETRIC DRAWING ARE STILL TO COMPACT | | | PLEASE ENLARGE. | | | | | | PARTIALLY COMPLIED 8. PROVIDE A COMPLETE SANITARY AND | | | GREASE ISOMETRIC FOR THE SECOND AND THIRD FLOOR SHOWING | | | THE KITCHEN, BATHROOMS AND BAR AREAS, ON THE BRANCHES | | | FOR EACH AREA YOU CAN LABEL IT TO COINCIDE TO THE | | | ENLARGED ISOMETRIC DRAWING INSTEAD OF DRAWING THE AREA | | | TWICE. PER WPB AMEND TO THE FBC 107.2.1 | | | PLEASE LABEL GREASE AND SANITARY SEPARATELY. | | | | | | PARTIALLY COMPLIED 12. PLEASE PROVIDE SIZING | | | CALCULATIONS FOR THE GREASE INTERCEPTORS. . PER WPB | | | AMEND TO THE FBC 107.2.1 | | | THE SIZING CALCULATIONS FOR THE GREASE INTERCEPTOR | | | APPEAR TO BE INCOMPLETE PLEASE PROVIDE THE WASTE WATER | | | FACTOR AND THE LOAD FACTOR. I CANNOT DETERMINE HOW YOUR | | | CALCULATION FIGURES OUT TO 3305 GAL PLEASE CLARIFY. | | | | | | NEW COMMENTS: | | | | | | 1. IS THE ELEVATOR A TRACTION TYPE OR HYDRAULIC IF IT | | | IS HYDRAULIC AN OIL SEPARATOR IS REQUIRED OR AN OIL | | | ALARM SYSTEM. PER FBC PL 1003.4 | | | 2. SHT. P0-1 NOTE #1 THE PLUMBING SHALL BE DESIGNED AND | | | SIZED PER THE 2014 FBC PLUMBING 5TH EDITION THE 2012 IS | | | SHOWN. | | | 3. MAXIMUM SIZE OF THE GREASE INTERCEPTOR PER WPB | | | UTILITIES IS 1250 GAL YOU CAN CONTACT JEFFERY ODOMS PH | | | # 561-822-2172 OR [email protected] | | | 4. SHT. P4-2 THE 6? HORIZONTAL OVERFLOW STORM DRAIN | | | PIPING WITH 5700 + 5740 SQFT IS UNDERSIZED @ 1/8 FT. | | | THE MAX FOR 6? IS 4280SQFT.PER FBC PL TABLE 1106.3 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-25 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-22 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2018-01-25 09:52:30 | | | | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THIS PROJECT SHALL COMPLY WITH FBC PL 403.1.3 POTTY | | | PARITY. IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE | | | OPEN TO THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER | | | CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF | | | WATER CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS | | | THESE ARE TWO OR FEWER SUCH FIXTURES FOR MEN, IN | | | ACCORDANCE WITH SECTION 553.86, FLORIDA STATUTES. | | | | | | 2. PLEASE PROVIDE A BREAKDOWN OF THE FIXTURE COUNT FOR | | | EACH SPACE SUCH AS THE RESTAURANT SPACE AS A2 THE AREA | | | OF THE DRIVING RANGE WOULD BE A4 AREAS SUCH AS STORAGE | | | AND MECHANICAL / MAINTENANCE ROOMS WOULD BE S1. PER FBC | | | PL TABLE 403.1 AND SEC 403.1.1 | | | | | | 3. SHT. A0-03 SHOW THE GRAB BARS MEASURED FROM FINISHED | | | FLOOR TO THE TOP OF THE GRIPPING SURFACE AND MOUNTED IN | | | A HORIZONTAL POSITION VERTICAL GRAB BARS ARE NOT | | | APPROVED PER FBC ACC 609.4 | | | | | | 4. WHAT TYPE OF EQUIPMENT WILL BE IN THE MAINTENANCE / | | | MECHANICAL ROOM 01.07.07IF ANYTHING WITH OIL OR | | | HYDRAULIC FLUID THE FLOOR DRAIN SHALL DISCHARGE THROUGH | | | AN OIL SEPARATOR. PER FBC PL 1003.4 | | | | | | 5. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS | | | SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A | | | HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND | | | EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN | | | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY | | | AFFECTED BY MOISTURE. PER FBC 1210.2.2 | | | | | | 6. PLEASE PROVIDE A LABELING SYSTEM FOR THE SANITARY, | | | WATER AND GAS THAT WILL SHOW A COHESIVE CORRELATION | | | BETWEEN THE RISER?S ISOMETRIC DRAWINGS AND FLOOR PLANS. | | | PER WPB AMEND TO THE FBC 107.2.1 | | | | | | 7. PROVIDE A COLLECTION ISOMETRIC FOR THE SANITARY AND | | | GREASE SYSTEMS PER WPB AMEND TO THE FBC 107.2.1 | | | | | | 8. PROVIDE A COMPLETE SANITARY AND GREASE ISOMETRIC FOR | | | THE SECOND AND THIRD FLOOR SHOWING THE KITCHEN, | | | BATHROOMS AND BAR AREAS, ON THE BRANCHES FOR EACH AREA | | | YOU CAN LABEL IT TO COINCIDE TO THE ENLARGED ISOMETRIC | | | DRAWING INSTEAD OF DRAWING THE AREA TWICE. PER WPB | | | AMEND TO THE FBC 107.2.1 | | | | | | 9. ANY SANITARY VENT TERMINALS ON THE ROOF SHALL BE A | | | MIN OF 10? AWAY FROM ANY AIR INTAKE OPENINGS. PER FBC | | | PL 903.5 | | | | | | 10. WHERE ARE THE ELEVATOR SUMP PUMPS DISCHARGING. . | | | PER WPB AMEND TO THE FBC 107.2.1 | | | | | | 11. PROVIDE CIVIL DRAWINGS SHOWING THE LOCATION OF THE | | | SANITARY, WATER, GREASE AND STORM DRAINS, IT LIST CIVIL | | | DRAWING IN THE INDEX BUT THEY ARE NOT IN THE PLAN SET. | | | . PER WPB AMEND TO THE FBC 107.2.1 | | | | | | 12. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTORS. . PER WPB AMEND TO THE FBC 107.2.1 | | | | | | 13. PLEASE SHOW SQFT ON ALL OF THE PIPING ON THE STORM | | | DRAIN ISOMETRIC. . PER WPB AMEND TO THE FBC 107.2.1 | | | | | | 14. A SEPARATE PERMIT IS REQUIRED FOR ANY BACKFLOW | | | DEVICES ON THE DOMESTIC WATER MAIN AND FIRE LINE AND | | | THE GREASE INTERCEPTOR. PER WPB UTILITIES DEPT. PLEASE | | | PLACE NOTE ON THE PLAN. . PER WPB AMEND TO THE FBC | | | 107.2.1 | | | | | | 15. THE ROOM OR AREA NUMBERS ON THE FOOD SERVICE SHEETS | | | DO NOT MATCH THE ARCHITECTAUL SHEETS. | | | A) SHT. FS-01 SHOWS THE PANTRY HALLWAY/LOCKER ROOM AS | | | 01.05.02 SHT. A2.01.B SHOWS THIS AREA AS 01.07.02 | | | B) SHT. FS-01 SHOWS THE PANTRY AS 1.11.02 AND THE EVENT | | | BAR AS 01.11.03 SHT. A2-01-A SHOWS THE PANTRY AS | | | 0.14.02 AND THE EVENT BAR AS 01.14.03 | | | C) SHT. FS-02 SHOWS THE PANTRY AS 02.05.02 SHT. A2-02-B | | | SHOWS IT AS 02.07.02 | | | D) SHT. FS-03 SHOWS THE PANTRY AS 02.09.02 THE | | | RESTAURANT IS SHOWN AS 02.12.02 SHT. A2-02-A SHOWS THE | | | PANTRY AS 02.12.03 THE RESTAURANT AS 02.14.02 | | | E) SHT. FS-04 SHOWS THE PANTRY AS 03.5.04 SHT. A2-03-B | | | SHOWS THE PANTRY AS 03.07.04 | | | PLEASE CHECK ALL THE FOOD SERVICE SHEETS AND CORRECT. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 16. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS PLEASE | | | SHOW ON ISOMETRIC DRAWING. PER FBC PL 1002.4 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-17 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-17 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-04-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-03 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-03 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2018-04-03 10:07:26 | | | | PARTIALLY COMPLIED 12. PLEASE PROVIDE SIZING | | | CALCULATIONS FOR THE GREASE INTERCEPTORS. . PER WPB | | | AMEND TO THE FBC 107.2.1 | | | THE SIZING CALCULATIONS FOR THE GREASE INTERCEPTOR | | | APPEAR TO BE INCOMPLETE PLEASE PROVIDE THE WASTE WATER | | | FACTOR AND THE LOAD FACTOR. I CANNOT DETERMINE HOW YOUR | | | CALCULATION FIGURES OUT TO 3305 GAL PLEASE CLARIFY. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-03-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-27 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-27 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-11 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-11 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2018-09-11 08:43:43 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PAGES AFTER SHEET # 201 ARE ALL DIGITALLY SIGNED & | | | SEALED, BUT PAGES BEFORE 201 ARE NOT. | | | | | | FS471, 481, DOCUMENTS PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. | | | | | | PROVIDE PAPER ORIGINALS. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-09-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-07 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-30 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2018-09-07 10:59:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PAGES AFTER SHEET # 201 ARE ALL DIGITALLY SIGNED & | | | SEALED, BUT PAGES BEFORE 201 ARE NOT. | | | | | | FS471, 481, DOCUMENTS PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. | | | | | | PLEASE CONTACT ME TO DISCUSS THE BEST WAY TO RESOLVE | | | THIS COMMENT. | | | | | | | | 2018-08-17 15:51:53 | 8/17/18 PLUMB DIG SIG ARE GOOD | | 2018-07-30 12:00:29 | E SHEETS OK | | | S SHEETS OK | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2018-07-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-25 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-25 |
Time |
18:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2018-03-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-03-30 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-03-28 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2018-03-30 07:15:36 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17120261 | | | ADD: 1600 BELVEDERE RD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: NOT GIVEN ON PERMIT APPLICATION | | | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: WED.-THURS. MARCH 28-29/2018 | | | ACTION: DENIED | | | | | | 3) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | | BUILDING BY DEFINITION. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 1A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | | | | FORMS WERE E-MAILED TO: [email protected] 1/24/2018 | | | 2:30PM. | | | | | | | | | 1C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 . 633 | | | FLORIDA STATUTE. | | | | | | 1D)SEMI-COMPLIED. IN THE DOCUMENT FILE DOCUMENTS HAD | | | BEEN UPLOADED FOR DONALD G BELLAMY, JR. P. E. , S. I. | | | FOR LICENSING AND RESUME (UNIVERSAL ENGINEERING | | | SERVICES, INC.). WHAT WE DID NOT SEE WERE HIS DESIGNEES | | | LICENSED UNDER PART XII OF CHAPTER 468, FLORIDA | | | STATUTES AND THEIR RESUMES. 110.3.7.6 THE BUILDING | | | DEPARTMENT MAY ALLOW A SPECIAL INSPECTOR TO CONDUCT THE | | | MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS | | | REQUIRED BY THIS CODE, SECTION 553.73, FLORIDA | | | STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE | | | BUILDING DEPARTMENT. THE BUILDING | | | OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON | | | CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING | | | INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA | | | STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER | | | CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF | | | THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5), | | | FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM | | | INSPECTIONS REQUIRED BY THIS CODE. | | | | | | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | | | | 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 1F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) PROVISO/ NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND | | | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE | | | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. | | | EACH SHORING AND RESHORING INSTALLATION SHALL BE | | | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE | | | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H) PROVISO/ NOTICE ONLY. PLEASE CALL THE CITY OF WEST | | | PALM BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) PROVISO/ NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, | | | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. | | | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2018-01-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-24 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-24 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2018-01-24 14:19:19 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17120261 | | | ADD: 1600 BELVEDERE RD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: NOT GIVEN ON PERMIT APPLICATION | | | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE:WED. JAN. 24/2018 | | | ACTION: DENIED | | | | | | 1) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | | BUILDING BY DEFINITION. THRESHOLD BUILDING / FL S. S. | | | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING | | | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, | | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | | 500 PERSONS. | | | | | | 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. | | | | | | FORMS WERE E-MAILED TO: [email protected] 1/24/2018 | | | 2:30PM. | | | | | | 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 1F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE | | | E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, | | | THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED | | | AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, | | | TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) | | | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK | | | & WHITE.. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
hmtribou |
Date |
2018-09-06 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2018-09-06 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2018-09-06 13:19:03 | PERMIT #17120261 | | | ORD. 4745-17 | | | RESO. 350-17 | | | PROJECT NAME: DRIVE SHACK | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | | | | GENERAL COMMENTS | | | | | | --BUILDING SIZE AND SIDEWALK LOCATIONS DIFFERS FROM | | | APPROVED PLANS AND WILL REQUIRE A MINOR SITE PLAN | | | AMENDMENT BEFORE CERTIFICATE OF OCCUPANCY. | | | | | | --SEPARATE PERMITS ARE REQUIRED FOR FENCE/SITE | | | WALLS/NETTING; DUMPSTER ENCLOSURES; SIGNAGE; LANDSCAPE; | | | PARKING; BIKE RACKS/ HARDSCAPE; AND SITE LIGHTING. | | | | | | --THE DRIVE SHACK PALM BEACH, LLC MUST SUPPLY AN | | | EASEMENT OR OTHER FORM OF ACCEPTABLE AGREEMENT FOR THE | | | ?CITY OF WEST PALM BEACH? SIGNAGE LOCATED ON THE NORTH | | | SIDE OF THE PROPERTY AS INDICATED ON THE SITE PLAN | | | (SP-1) WITH THE LAST REVISION DATED SEPTEMBER 29, 2017. | | | THE EASEMENT WILL BE RECORDED BEFORE ISSUANCE OF | | | CERTIFICATE OF OCCUPANCY. THE CONCEPTUAL DESIGN OF THE | | | NEW SIGN SHALL BE APPROVED BY THE CITY BEFORE | | | INSTALLATION WHICH IS SCHEDULED FOR 5/21/18. | | | | | | -- THE RECONFIGURATION OF DRIVEWAYS AT THE AIRPORT | | | SOUTH OF FLORIDA MANGO ROAD AND THE NEW CIRCULAR DRIVE, | | | INCLUDING ALL ENTRIES TO THE SITE, MUST HAVE COMPLETED | | | CONSTRUCTION BEFORE FINAL INSPECTIONS. | | | | | | -- THIS PROJECT REQUIRES FOR THE PUBLIC ART ASSESSMENT | | | (SEC. 98-129 OF CHAPTER 28 OF THE CITY OF WEST PALM | | | BEACH CODE OF ORDINANCES). IT IS ENCOURAGED THAT THE | | | ART BE INTEGRATED INTO THE SITE PLAN NOW TO ASSIST WITH | | | MITIGATION OF THE FA?ADE ORIENTATION. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2018-07-16 |
|
|
Cont ID |
|
| Sent By |
hmtribou |
Date |
2018-07-16 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2018-07-16 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2018-07-16 12:30:52 | ORD. 4745-17 | | | RESO. 350-17 | | | PROJECT NAME: DRIVE SHACK | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | | | | | | | GENERAL COMMENTS | | | | | | --SEPARATE PERMITS ARE REQUIRED FOR FENCE/SITE | | | WALLS/NETTING; DUMPSTER ENCLOSURES; SIGNAGE; LANDSCAPE; | | | PARKING; BIKE RACKS/ HARDSCAPE; AND SITE LIGHTING. | | | | | | --THE RESPONSE TO COMMENTS INDICATE THAT THE CIVIL | | | CONSULTANTS WILL COORDINATE THIS, BUT THE SITE DEMO | | | PLANS INDICATE THE CURRENT SIGN NOT BEING RELOCATED AND | | | THE SITE LAYOUT PLANS (C4) DO NOT INDICATE REPLACEMENT | | | SIGN. THE DRIVE SHACK PALM BEACH, LLC MUST SUPPLY AN | | | EASEMENT OR OTHER FORM OF ACCEPTABLE AGREEMENT FOR THE | | | ?CITY OF WEST PALM BEACH? SIGNAGE LOCATED ON THE NORTH | | | SIDE OF THE PROPERTY AS INDICATED ON THE SITE PLAN | | | (SP-1) WITH THE LAST REVISION DATED SEPTEMBER 29, 2017. | | | THE EASEMENT WILL BE RECORDED BEFORE ISSUANCE OF | | | CERTIFICATE OF OCCUPANCY. THE CONCEPTUAL DESIGN OF THE | | | NEW SIGN HAS BEEN PROVIDED. | | | | | | -- THE RECONFIGURATION OF DRIVEWAYS AT THE AIRPORT | | | SOUTH OF FLORIDA MANGO ROAD AND THE NEW CIRCULAR DRIVE, | | | INCLUDING ALL ENTRIES TO THE SITE, MUST HAVE COMPLETED | | | CONSTRUCTION BEFORE FINAL INSPECTIONS. | | | | | | -- THIS PROJECT REQUIRES FOR THE PUBLIC ART ASSESSMENT | | | (SEC. 98-129 OF CHAPTER 28 OF THE CITY OF WEST PALM | | | BEACH CODE OF ORDINANCES). IT IS ENCOURAGED THAT THE | | | ART BE INTEGRATED INTO THE SITE PLAN NOW TO ASSIST WITH | | | MITIGATION OF THE FA?ADE ORIENTATION. THE 90 DAY WINDOW | | | FOR COMPLIANCE HAS BEGUN AND A REMINDER EMAIL WAS SENT | | | TO THE PROJECT TEAM ON JULY, 3, 2018. | | | | | | SPECIFIC COMMENTS | | | | | | --WAIVER MUST BE AMENDED AND REGULATING PLAN MUST BE | | | UPDATED TO ENLARGE ANY SIGNAGE BEFORE PERMIT ISSUANCE. | | | | | | --A WAIVER MUST BE REQUESTED BEFORE PERMIT ISSUANCE TO | | | ADDRESS FENCE SUPPORTING STRUCTURES IN SETBACKS. | | | | | | --THE SITE PLAN MUST BE AMENDED BEFORE PERMIT ISSUANCE | | | TO ADD GUYWIRES FOR POLES. | | | | | | --BUILDING SIZE DIFFERS FROM APPROVED PLANS AND WILL | | | REQUIRE A SITE PLAN AMENDMENT BEFORE CERTIFICATE OF | | | OCCUPANCY. | | | | | | --AMENDMENTS TO SIDEWALK LOCATION REQUIRES WILL REQUIRE | | | A SITE PLAN AMENDMENT BEFORE CERTIFICATE OF OCCUPANCY. | | | | | | --ADD PEDESTRIAN CROSSWALKS ON EAST AND SOUTH ENTRIES. | | | | | | --PORTABLES ARE INDICATED O THE ARCHITECTURAL SITE PLAN | | | A2-01-A, NO TEMPORARY OFFICE OR FACILITIES ARE ALLOWED | | | SEVEN DAYS AFTER CONSTRUCTION COMPLETION. PLEASE | | | ADDRESS. | | | | | | -- EQUIPMENT FOR GOLF BALL CONVEYING SYSTEM MUST BE | | | SCREENED. | | | | | | --LIGHTING PLAN (E4-0-S0) MUST COORDINATE WITH EXISTING | | | APPROVED TREE LOCATIONS AND CANOPY REGARDING LOCATIONS | | | AND HEIGHT OF POLES. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-03-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2018-03-23 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-03-23 14:21:53 | ORD. 4745-17 | | | RESO. 350-17 | | | PROJECT NAME: DRIVE SHACK | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | | | | | | | GENERAL COMMENTS | | | | | | --THE RESPONSE TO COMMENTS INDICATE THAT THE CIVIL | | | CONSULTANTS WILL COORDINATE THIS, BUT THE SITE DEMO | | | PLANS INDICATE THE CURRENT SIGN NOT BEING REMOVED AND | | | THE SITE LAYOUT PLANS DO NOT INDICATE REPLACEMENT SIGN. | | | THE DRIVE SHACK PALM BEACH, LLC MUST SUPPLY AN EASEMENT | | | OR OTHER FORM OF ACCEPTABLE AGREEMENT FOR THE ?CITY OF | | | WEST PALM BEACH? SIGNAGE LOCATED ON THE NORTH SIDE OF | | | THE PROPERTY AS INDICATED ON THE SITE PLAN (SP-1) WITH | | | THE LAST REVISION DATED SEPTEMBER 29, 2017. THE | | | EASEMENT WILL BE RECORDED BEFORE ISSUANCE OF | | | CERTIFICATE OF OCCUPANCY. THE FINAL DESIGN OF THE NEW | | | SIGN SHALL BE APPROVED BY THE CITY BEFORE INSTALLATION. | | | | | | --FAA APPROVAL MUST BE PROVIDED BEFORE BUILDING PERMIT | | | ISSUANCE. | | | | | | -- THE RECONFIGURATION OF DRIVEWAYS AT THE AIRPORT | | | SOUTH OF FLORIDA MANGO ROAD AND THE NEW CIRCULAR DRIVE, | | | INCLUDING ALL ENTRIES TO THE SITE, MUST HAVE COMPLETED | | | CONSTRUCTION BEFORE FINAL INSPECTIONS. | | | | | | --PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING | | | TREES, A TREE ALTERATION PERMIT MUST BE ISSUED FROM THE | | | DEVELOPMENT SERVICES DEPARTMENT. | | | | | | -- THIS PROJECT REQUIRES FOR THE PUBLIC ART ASSESSMENT | | | (SEC. 98-129 OF CHAPTER 28 OF THE CITY OF WEST PALM | | | BEACH CODE OF ORDINANCES). IT IS ENCOURAGED THAT THE | | | ART BE INTEGRATED INTO THE SITE PLAN NOW TO ASSIST WITH | | | MITIGATION OF THE FA?ADE ORIENTATION. | | | | | | SPECIFIC COMMENTS | | | | | | --BUILDING SIZE DIFFERS FROM APPROVED PLANS AND WILL | | | REQUIRE A MINOR SITE PLAN AMENDMENT BEFORE CERTIFICATE | | | OF OCCUPANCY. | | | | | | --FRONT ELEVATION DIFFERS FROM APPROVED PLANS, MORE | | | SPECIFICALLY, NOW THE PROMINENT ENTRY DOES NOT EXIST. | | | THE ENTRY HAS GONE FROM A HORIZONTAL VENEER TO A SCORED | | | CONCRETE. PART OF THE MAJOR SITE PLAN APPROVAL, SHOWN | | | AS EXHIBIT F IN THE RESOLUTION, IS MORE DESIRABLE AND | | | ATTRACTIVE DEVELOPMENT (SEC.94-207 (1)) OF THE | | | PROMINENT ENTRY AS DISCUSSED IN PLANNING BOARD AND CITY | | | COMMISSION. MATCH ENTRY ELEVATIONS TO APPROVED DRAWING | | | OR SUBMIT FOR REVISED SITE PLAN APPROVAL BEFORE PERMIT | | | ISSUANCE. | | | | | | --THE STOP BAR ON FLORIDA MANGO NEEDS TO MOVE BACK | | | INTERNAL TO THE SITE AND A PEDESTRIAN CROSSWALK SHOULD | | | BE ADDED FOR PEDESTRIAN SAFETY. | | | | | | --SUPPORTING STRUCTURES FOR FENCE POSTS MAY NOT BE IN | | | SETBACK. APPROVED PLANS DO NOT SHOW GUYWIRES IN | | | SETBACKS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-01-09 |
|
|
Cont ID |
|
| Sent By |
HT |
Date |
2018-01-09 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2018-01-09 |
Time |
13:37 |
Sent To |
I |
|
| Notes |
| 2018-01-09 13:40:38 | PROJECT NAME: DRIVE SHACK | | | ORD. 4745-17 | | | RESO. 350-17 | | | | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | | | | | | | GENERAL COMMENTS | | | | | | --UPDATE ALL SHEETS TO REFLECT ANY CHANGES. | | | | | | --SEPARATE PERMITS ARE REQUIRED FOR FENCE/SITE | | | WALLS/NETTING; DUMPSTER ENCLOSURES; SIGNAGE; LANDSCAPE; | | | PARKING; BIKE RACKS/ HARDSCAPE; AND SITE LIGHTING. | | | | | | --THE DRIVE SHACK PALM BEACH, LLC MUST SUPPLY AN | | | EASEMENT OR OTHER FORM OF ACCEPTABLE AGREEMENT FOR THE | | | ?CITY OF WEST PALM BEACH? SIGNAGE LOCATED ON THE NORTH | | | SIDE OF THE PROPERTY AS INDICATED ON THE SITE PLAN | | | (SP-1) WITH THE LAST REVISION DATED SEPTEMBER 29, 2017. | | | THE EASEMENT WILL BE RECORDED BEFORE ISSUANCE OF | | | CERTIFICATE OF OCCUPANCY. THE FINAL DESIGN OF THE NEW | | | SIGN SHALL BE APPROVED BY THE CITY BEFORE INSTALLATION. | | | | | | --FAA APPROVAL MUST BE PROVIDED BEFORE BUILDING PERMIT | | | ISSUANCE. | | | | | | -- THE RECONFIGURATION OF DRIVEWAYS AT THE AIRPORT | | | SOUTH OF FLORIDA MANGO ROAD AND THE NEW CIRCULAR DRIVE, | | | INCLUDING ALL ENTRIES TO THE SITE, MUST HAVE COMPLETED | | | CONSTRUCTION BEFORE FINAL INSPECTIONS. | | | | | | --PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING | | | TREES, A TREE ALTERATION PERMIT SHALL BE OBTAINED FROM | | | THE DEVELOPMENT SERVICES DEPARTMENT ? PLANNING | | | DIVISION. | | | | | | -- THIS PROJECT REQUIRES FOR THE PUBLIC ART ASSESSMENT | | | (SEC. 98-129 OF CHAPTER 28 OF THE CITY OF WEST PALM | | | BEACH CODE OF ORDINANCES). IT IS ENCOURAGED THAT THE | | | ART BE INTEGRATED INTO THE SITE PLAN NOW TO ASSIST WITH | | | MITIGATION OF THE FA?ADE ORIENTATION. | | | | | | SPECIFIC COMMENTS | | | | | | --BUILDING SIZE DIFFERS FROM APPROVED PLANS AND WILL | | | REQUIRE A MINOR SITE PLAN AMENDMENT BEFORE CERTIFICATE | | | OF OCCUPANCY. | | | | | | --FRONT ELEVATION DIFFERS FROM APPROVED PLANS, PROVIDE | | | PROOF OF EQUIVALENCY MATERIALS. IF DEEMED EQUIVALENT, | | | WILL REQUIRE A MINOR SITE PAN AMENDMENT. | | | | | | --SITE LIGHTING PLAN DIFFERS FROM APPROVED PLAN AND | | | APPEARS TO EXCEED ILLUMINATION REQUIREMENTS AT NE | | | CORNER OF THE SITE NEAR THE ?D? OF THE DRIVE SHACK | | | SIGN. | | | | | | --ALL MECHANICAL EQUIPMENT LOCATED ON THE ROOF MUST BE | | | SCREENED FROM THE RIGHT-OF-WAY. | | | |
|
|
|