Plan Review Details - Permit 17120197
Plan Review Stops For Permit 17120197
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-19 Cont ID  
Sent By skennedy Date 2018-01-19 Time 13:51 Rev Time 0.00
Received By skennedy Date 2018-01-19 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-12 Cont ID  
Sent By jwitmer Date 2018-01-12 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2018-01-12 Time 16:56 Sent To  
Notes
2018-01-12 17:29:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050779
 ADD: 2161PALM BEACH LAKES BLVD 1ST FLOOR
 CONT: ALL PHASE CONSTRUCTION
 TEL: 561-723-8246
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JAN 11/2018
 ACTION: DENIED
  
 1) SEMI-COMPLIED. SHEET C-1 THE COVERSHEET HAS A INDEX,
 MISSING SHEETS:
 SHEET 1.5A SECTIONS & DETAILS
  
 2-4D) COMPLIED
  
 4D)SEMI- COMPLIED. SEE 4E. NEITHER SHEET 1.2A NOR 1.4A
 SHOW COMPLIANCE WITH COMPLIANCE WITH 2014 FBC-ACCESS.
 CODE 226.1. WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. THE COVERSHEET LIST 292
 SEATS X 0.05 = 15 ACCESSIBLE SEATS.
 ACTUAL SEATING COUNT OF 343 X 0.05 = 18 ACCESSIBLE
 SEATS.
  
 4E) 2ND REQUEST. PLEASE PROVIDE A CUT SECTION THROUGH
 THE ACCESSIBLE BAR TOPS SHOWING THE ELEVATION. CAN NOT
 BE A DROPPED LEAF DESIGN.
 1ST ROUND COMMENTS. PLEASE NOTE COMPLIANCE WITH ACCESS.
 CODE 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4F)SHOW COMPLIANCE WITH FBC-ACCESS. CODE 902.1DINING
 SURFACES AND WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3.
  
 4F)(1) FBC-ACCESS. 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4F)(2) FBC-ACCESS. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5) DELETED FROM PROJECT. SHEET 1.2A NOTE 10 INDICATES
 THE REMOVAL AND REPLACEMENT OF EXTERIOR SLIDING GLASS
 DOORS. PLEASE PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. PLEASE ALSO PROVIDE THE PRESSURES IN VASD.
 PLEASE SHOW COMPLIANCE WITH:
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
  
 5B) DELETED FROM PROJECT. W. P. B. 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) PLEASE PROVIDE A LIST HOW UP TO AN ADDITIONAL
 $24,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE
 UPGRADES. 2014 FBC-ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-12 Cont ID  
Sent By jwitmer Date 2017-12-12 Time 14:40 Rev Time 0.00
Received By jwitmer Date 2017-12-12 Time 11:57 Sent To  
Notes
2017-12-12 14:40:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050779
 ADD: 2161PALM BEACH LAKES BLVD 1ST FLOOR
 CONT: ALL PHASE CONSTRUCTION
 TEL: 561-723-8246
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 12/2017
 ACTION: DENIED
  
 1) SHEET C-1 THE COVERSHEET HAS A INDEX, MISSING
 SHEETS:
 SHEETS 1.1A EQUIPMENT PLAN & SCHEDULE MISSING IN BOTH
 SETS.
 SHEET 1.5A SECTIONS & DETAILS
 SHEET 1.7A REFLECTED CEILING PLAN
  
 2) SHEET C-1 THE COVERSHEET LIST INTERIOR SEATING AND
 EXTERIOR SEATING AS 292 SEATS. SHEET 1.4A WHEN YOU
 TOTAL UP ALL OF THE SEATING THE COUNT IS 343 SEATS NOT
 COUNTING THE OCCUPANT LOAD IN THE VIDEO GAMES AND
 BILLIARD AREA NOT THE KITCHEN AREA, BEHIND THE BARS(
 WORK AREAS) NOR FOR STORAGE AREAS, PLEASE PROVIDE THE
 SQUARE FEET FOR EACH OF THESE AREAS AND THE OCCUPANT
 LOADS BASED FROM FBC-B TABLE 1004.1.2. SHEET A1.4 THE
 LIFE SAFETY SHEET LIST A OCCUPANT LOAD A LOT LESS THAN
 THE SEATING COUNT FOUND ON THE COVER SHEET. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET C-1 THE COVERSHEET ALSO INDICATES THIS IS A
 LEVEL II ALTERATION. THE 2014 FBC-EXISTING BUILDING
 CODE. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN
 ALL WORK AREAS WHEN REQUIRED BY SECTION 804.2 OR THIS
 SECTION. THE EXISTING BUILDING CODE SECTION 804.2.2
 GROUP A OCCUPANCY. WILL REQUIRE AUTOMATIC SPRINKLER
 PROTECTION WHERE ALL OF THE FOLLOWING CONDITIONS OCCUR:
 1. THE WORK AREA IS REQUIRED TO BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING AS APPLICABLE TO NEW
 CONSTRUCTION; AND
 2. THE WORK AREA EXCEEDS 50 PERCENT OF THE FLOOR AREA.
  
 4) SHEET 1.4A THE LIFE SAFETY SHEET:
  
 4A) THE MAIN ENTRY THERE IS EMERGENCY POWERED EXIT
 LIGHTING BUT TO THE LEFT OF THIS AREA THERE IS A LARGE
 DINING AREA AND THE NORTH AND SOUTH EXTERIOR DINING
 AREAS ARE WITHOUT ANY EMERGENCY POWERED BACKUP LIGHTS.
 PLEASE PROVIDE COMPLIANCE WITH FBC-B 1006.1 AND 1011.1
 WHERE EXITS SIGNS ARE REQUIRED.
  
 4B) PLEASE SHOW HOW MANY AND WHICH OF THE EXITS HAVE
 LEVEL EXIT DISCHARGES TO THE PUBLIC WAY. MEANING THERE
 ARE NO DROPS IN ELEVATION OVER 1/4 INCH OR THERE IS
 SLOPED OR RAMPED SIDEWALKS, DROPPED CURB CUTS ETC...
 2014 FBC-ACCESSIBILITY CODE IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED.
  
 4C) THE OCCUPANT LOAD OF THE NORTH EXTERIOR SEATING
 AREA EXCEEDS 50 OCCUPANTS REQUIRING 2 MEANS OF EGRESS.
 2014 EBC-B TABLE 1015.1.
 PLEASE NOTE WITH A NON-SPRINKLERED BUILDING THE EXITS
 NEED TO BE 1/2 THE OVERALL DIAGONAL DISTANCE APART.
 2014 FBC-B 1015.2.1. SPRINKLERED 1/3RD THE DIAGONAL
 DISTANCE APART.
  
 4D) NEITHER SHEET 1.2A NOR 1.4A SHOW COMPLIANCE WITH
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 226.1. WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. THE COVERSHEET LIST 292 SEATS X 0.05 = 15
 ACCESSIBLE SEATS.
 ACTUAL SEATING COUNT OF 343 X 0.05 = 18 ACCESSIBLE
 SEATS.
  
 4E) PLEASE NOTE COMPLIANCE WITH ACCESS. CODE 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4F)SHOW COMPLIANCE WITH FBC-ACCESS. CODE 902.1DINING
 SURFACES AND WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3.
  
 4F)(1) FBC-ACCESS. 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4F)(2) FBC-ACCESS. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5A) SHEET 1.2A NOTE 10 INDICATES THE REMOVAL AND
 REPLACEMENT OF EXTERIOR SLIDING GLASS DOORS. PLEASE
 PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING. PLEASE
 ALSO PROVIDE THE PRESSURES IN VASD. PLEASE SHOW
 COMPLIANCE WITH:
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
  
 5B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) PLEASE PROVIDE A LIST HOW UP TO AN ADDITIONAL
 $24,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE
 UPGRADES. 2014 FBC-ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 12/ 18/2017
 PLEASE REVIEW E-MAIL SENT TO PETE RUSSO:
 GOOD MORNING PETE,
 I JUST WANTED TO RECAP OUR CONVERSATION TODAY AND THE
 POINTS MR. BROWN WANTED TO SEE IN THE NEXT REVIEW
 CYCLE. THE TENANT ON THE 1ST FLOOR DOES HAVE A OCCUPANT
 LOAD OVER 300. ROBERT WAS OK IN NOT FIRE SPRINKLERING
 THE TENANT SPACE IF THE PLANS SHOW THE OCCUPANTS ON THE
 NORTH AND SOUTH EXTERIOR SPACES & BARS WOULD NOT HAVE
 TO GO BACK INSIDE THE MAIN BUILDING BUT EXIT THROUGH
 THE 2 EXITS DIRECTLY TO THE EXTERIOR OF THE BUILDING
 WITHIN THE NORTH AND SOUTH OPEN AREAS. THAT SINCE THE
 OCCUPANT LOAD ON BOTH SIDES HAD AN OCCUPANT LOAD OF 50
 OR MORE, THAT FOR BOTH SIDES THERE WOULD BE (2) EXITS
 DIRECTLY TO THE EXTERIOR. TO NOTE ON THE PLANS THAT
 BOTH THE NORTH AND SOUTH AREAS ARE OPEN TO THE EXTERIOR
 TO ALLOW PARTICLES OF SMOKE TO DISSIPATE QUICKLY THE
 ONLY BARRIERS ON THE 2 EXTERIOR AREAS BEING GRILLE WORK
 FOR SECURITY. WITH THIS INFORMATION ADDED TO THE PLANS
 BUILDING WOULD BE ABLE TO PASS THE REVIEW WITHOUT THE
 ADDITION OF FIRE SPRINKLERS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-12-21 Cont ID  
Sent By jpearson Date 2017-12-21 Time 14:48 Rev Time 0.00
Received By jpearson Date 2017-12-21 Time 13:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-10 Cont ID  
Sent By pleduc Date 2018-01-10 Time   Rev Time 0.00
Received By pleduc Date 2018-01-09 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By scaldero Date 2017-12-12 Time   Rev Time 0.00
Received By pleduc Date 2017-12-12 Time 10:40 Sent To  
Notes
2017-12-18 14:56:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS INDCATE AN OCCUPANCY LOAD OF
 292, HOWEVER, ACTUAL SQ FT CALCULATINS INDICATE OVER
 300.
  
 PER NFPA 101, CHAPTER 13, EXISTING ASSEMBLY OCCUPANCIES
 A FIRE SPRINKLER SYSTEM IS REQUIRED.
  
 13.3.5 EXTINGUISHMENT REQUIREMENTS. SEE ALSO 13.1.6,
 13.2.6, AND 13.3.2.
 13.3.5.1 WHERE THE OCCUPANT LOAD EXCEEDS 100 300, THE
 FOLLOWING ASSEMBLY OCCUPANCIES SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1):
 (1) DANCE HALLS
 (2) DISCOTHEQUES
 (3) NIGHTCLUBS
 (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
  
 PLEASE PROVIDE FOR THE REQUIREMENT OR JUSTIFY SPECIFIC
 ALTENRATIVES FOR CONSIDERATION PER:
  
  
 13.1.1.4 AN EXISTING BUILDING HOUSING AN ASSEMBLY
 OCCUPANCY ESTABLISHED PRIOR TO THE EFFECTIVE DATE OF
 THIS CODE SHALL BE PERMITTED TO BE APPROVED FOR
 CONTINUED USE IF IT CONFORMS TO, OR IS MADE TO CONFORM
 TO, THE PROVISIONS OF THIS CODE TO THE EXTENT THAT, IN
 THE OPINION OF THE AUTHORITY HAVING JURISDICTION,
 REASONABLE LIFE SAFETY AGAINST THE HAZARDS OF FIRE,
 EXPLOSION, AND PANIC IS PROVIDED AND MAINTAINED.
 13.1.1.5 ADDITIONS TO EXISTING BUILDINGS SHALL CONFORM
 TO THE REQUIREMENTS OF 4.6.7.
 13.1.1.6 EXISTING PORTIONS OF BUILDINGS SHALL BE
 UPGRADED IF THE ADDITION RESULTS IN AN INCREASE IN THE
 REQUIRED MINIMUM NUMBER OF SEPARATE MEANS OF EGRESS IN
 ACCORDANCE WITH 7.4.1.2.
  
 THE ALTERANTIVES NEED TO BE IN BUILDING DRAWING AND
 NARRATIVE FORM FOR CLARIFICATION PURPOSES.
  
  
  
  
 2) THE SUBMITTED PLANS INDCATE AN OCCUPANCY LOAD OF
 292, HOWEVER, ACTUAL SQ FT CALCULATINS INDICATE OVER
 300.
  
 13.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 13.3.4.1 GENERAL.
 13.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF
 MORE THAN 300 AND ALL THEATERS WITH MORE THAN ONE
 AUDIENCE-VIEWING ROOM SHALL BE PROVIDED WITH AN
 APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH 9.6.1 AND
 13.3.4, UNLESS OTHERWISE PERMITTED BY 13.3.4.1.2,
 13.3.4.1.3, OR 13.3.4.1.4.
  
 PLEASE PROVIDE FOR THE REQUIREMENT OR JUSTIFY SPECIFIC
 ALTENRATIVES FOR CONSIDERATION PER:
  
 13.3.4.1.4 THE REQUIREMENT OF 13.3.4.1.1 SHALL NOT
 APPLY TO ASSEMBLY OCCUPANCIES WHERE, IN THE JUDGMENT OF
 THE AUTHORITY HAVING JURISDICTION, ADEQUATE ALTERNATIVE
 PROVISIONS EXIST OR ARE PROVIDED FOR THE DISCOVERY OF A
 FIRE AND FOR ALERTING THE OCCUPANTS PROMPTLY.
  
 THE ALTERANTIVES NEED TO BE IN BUILDING DRAWING AND
 NARRATIVE FORM FOR CLARIFICATION PURPOSES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-01-17 Cont ID  
Sent By gjohnson Date 2018-01-17 Time 07:32 Rev Time 0.00
Received By gjohnson Date 2018-01-17 Time 07:32 Sent To  
Notes
2018-01-17 07:36:14GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OK SYSTEM.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By gjohnson Date 2017-12-27 Time 11:03 Rev Time 0.00
Received By gjohnson Date 2017-12-27 Time 11:03 Sent To  
Notes
2017-12-27 11:34:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. MY CALCULATIONS OF THE KITCHEN EQUIPMENT EQUAL
 674,000 BTU ON THE RISER IT SHOWS 700,000 BTU AND UNDER
 THE GAS LOAD CALCULATIONS IT LIST IT AS 722,00 BTU
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. UNDER THE GAS LOAD CALCULATION IT SHOWS 11/4 @ 28'
 ON THE RISER IT SHOWS 11/2 @ 29' CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 3. UNDER THE GAS LOAD CALCULATION IT SHOWS A TOTAL BTU
 LOAD AS 1,052,00 MY CALCULATIONS WERE 1,004,000 BTU THE
 RISER SHOWS 880,000 CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. UNDER THE GAS LOAD CALCULATION IT SHOWS THE WATER
 HEATER AS 180,000 BTU THE RISER SHOWS 199,000 BTU
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. FOR THE SIZING TABLES IT SHOWS LESS THAN 2PSI 2 .5
 PSI PRESSURE DROP WHICH IS FBC FG TABLE 402.4(2) BUT
 THE PLAN LIST 402.4(4) PLEASE CLARIFY WHICH TABLE WAS
 USED IN SIZING THE SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 8. SUBMIT MANUFACTURER?S SPECIFICATION AND INSTILLATION
 GUIDE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS
 SEC. 402.2
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-19 Cont ID  
Sent By skennedy Date 2018-01-19 Time 13:55 Rev Time 0.00
Received By skennedy Date 2018-01-18 Time 09:07 Sent To  
Notes
2018-01-19 09:07:58GIVEN TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-17 Cont ID  
Sent By gjohnson Date 2018-01-17 Time 08:00 Rev Time 0.00
Received By gjohnson Date 2018-01-04 Time 08:12 Sent To  
Notes
2018-01-09 08:12:27B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-27 Cont ID  
Sent By gjohnson Date 2017-12-27 Time 11:35 Rev Time 0.00
Received By gjohnson Date 2017-12-06 Time 13:24 Sent To  
Notes
2017-12-07 13:25:03B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-12-12 Time   Rev Time 0.00
Received By jwitmer Date 2017-12-12 Time 11:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-19 Cont ID  
Sent By skennedy Date 2018-01-19 Time 13:37 Rev Time 0.00
Received By skennedy Date 2018-01-19 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-11 Cont ID  
Sent By ccole Date 2018-01-11 Time 08:01 Rev Time 0.00
Received By ccole Date 2018-01-10 Time 17:05 Sent To  
Notes
2018-01-11 08:39:172ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17120197
 1/11/18
  
 PLAN REVIEW RESULTS: DENIED.
 NEW PLAN SHEETS 3.2M AND 3.3M REVIEWED AND NOT
 APPROVED.
  
 1) SHEET 3.2M: SEE COMMENT #2 FROM THE 1ST REVIEW-
 SMOKE DETECTORS REQUIRED FOR AHU- 1, 4 & 5. AN
 EXEMPTION CAN BE APPLIED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE UNITS DO NOT HAVE THE
 CAPACITIES TO EXCEED 2000 CFMS OF SUPPLY AIR. PLEASE
 SUBMIT THE SPECS TO VERIFY THE CFMS OR PROVIDE THE
 DETECTORS.
  
 2) 3.2M: SEE COMMENT #6 FROM THE 1ST REVIEW- PROVIDE
 THE DIMENSIONS OF THE RETUN AIR OPENING ABOVE THE AHU-
 2 & 3 CLOSET WALL.
  
 3) 3.2M & 3.3M: SEE COMMENTS #4, 7, & 8 FROM THE 1ST
 REVIEW- INSUFFICIENT OUTDOOR AIR PROVIDED. THE
 VENTILATION SCHEDULE IS INCORRECTLY SHOWING 5 CFMS PER
 PERSON REQUIRED FOR THE DINING ROOM AND BAR AREA- TABLE
 403.3 REQUIRES 7.5 CFM PER PERSON. TOTAL O/A REQUIRED
 IS 1388 CFMS + 642 CFMS = 2030. PLEASE CORRECT THE
 VENTILATION SCHEDULE AND THE AIR BALANCE SCHEDULE.
 REFER
  
 TO SECTION C403.2.5.1 AND PROVIDE DEMAND CONTROLLED
 VENTILATION FOR THE DINING ROOM AND BAR AREA.
  
 4) 3.3M: SEE COMMENT #8 FROM THE 1ST REVIEW- WIND LOAD
 DESIGN CRITERIA NOT PROVIDED.
  
 5) 3.2M & 3.3M: SEE COMMENT #10 FROM THE 1ST REVIEW-
 SHOW THE CONDENSATE PIPING RUNS, SUBMIT SPECS FOR THE
 CONDENSATE PUMPS, AND ADD THE PUMPS TO THE ELECTRICAL
 SCOPE OF WORK.
  
 6) 3.2M & 3.3M: SEE COMMENT #11 FROM THE 1ST REVIEW-
 REQUESTED COMBUSTION AIR CALCULATIONS NOT PROVIDED.
  
 7) SEE COMMENT #12 FROM THE 1ST REVIEW- REQUESTED FL.
 PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE
 CONDENSER STANDS AND LOUVERS NOT PROVIDED.
  
 8) SEE COMMENT #13 FROM THE 1ST REVIEW- CUT SHEETS FOR
 THE GAS-FIRED COOKING APPLIANCES AND MOTORIZED DAMPERS
 NOT PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By ccole Date 2017-12-18 Time 16:39 Rev Time 0.00
Received By ccole Date 2017-12-18 Time 16:28 Sent To  
Notes
2017-12-18 17:06:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120197
 12/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0M: LABEL THE (2) 5TON SYSTEMS AND SHOW HOW
 AIR IS BEING RETURNED TO THE SYSTEM IN THE CLOSET BY
 THE RECTANGULAR BAR.
  
 2) 4.0M: SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 3) 4.0M: A SMOKE DETECTOR IS REQUIRED IN THE MECHANICAL
 CLOSET HOUSING THE (2) 10-TON AIR HANDLERS- SECTION
 606.2.2.
  
 4) 4.0M: SHOW THE OUTSIDE DUCT AND INLET LOCATION FOR
 THE 5-TON AIR HANDLER IN THE CLOSET- TABLE 403.3.
  
 5) 4.0M: PROVIDE AN AUTOMATICALLY CONTROLLED SHUT OFF
 DAMPER FOR THE 16"X12" O/A DUCT TO THE 5-TON AIR
 HANDLER BY THE FRONT ENTRANCE- SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 6) 4.0M: THE 24"X24" RETURN GRILLS FOR THE (2) 10-TON
 AIR HANDLERS ARE UNDERSIZED. GENERALLY RETURN GRILLS
 ARE SIZED AT 200 SQ, INCHES PER TON, OR 50 SQ. INCHES
 PER 100 CFMS. USING THESE CALCULATIONS THE GRILLS WOULD
 HAVE TO BE 2000 SQ. INCHES EACH
  
 7) 4.1M: THE VENTILATION SCHEDULE IS NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH INDICATES O/A FOR DINING ROOMS
 TO BE CALCULATED AT 70 PERSONS PER 1000 SQ.FT AT 7.5
 CFMS PER PERSON AND 0.18 CFMS. BASED ON THE SQUARE
 FOOTAGES SHOWN IN THE SCHEDULE THE TOTAL O/A REQUIRED
 FOR THE DINING AREAS IS 2588 CFMS. THIS TOTAL DOES NOT
 INCLUDE THE BARS WHICH ARE CALCULATED AT 100
  
 PERSONS PER 1000 SQ. FT. REVISE THE SCHEDULE TO SHOW
 THE REQUIRED CFMS FOR THE BARS AND THE DINING AREAS.
 PLEASE NOTE THAT THE BUILDING REVIEWER IS REQUIRING
 MORE INFORMATION IN ORDER TO DETERMINE AN ACCURATE
 OCCUPANT LOAD.
  
 8) 4.1M: BASED ON COMMENT #5 PRINTED ABOVE, THE AIR
 BALANCE SCHEDULE WILL HAVE TO BE REVISED TO SHOW THE
 ACCURATE CFMS TOTALS.
  
 9) 4.1M: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOP CONDENSERS AND STANDS-
 SECTION 1609 FBC-14 BUILDING.
  
 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS- SECTION 307.
  
 11) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 12) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR THE CONDENSER STANDS AND O/A LOUVERS.
  
 13) PROVIDE CUT SHEETS FOR THE GAS-FIRED COOKING
 APPLIANCES AND THE MOTORIZED SHUTOFF DAMPERS.
  
 14) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR
 ALTERATIONS TO, OR REPLACEMENT OF, THE KITCHEN EXHAUST
 HOOD, THE FIRE SUPPRESSION SYSTEM, AND THE WALK-IN
 COOLER AND FREEZER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-17 Cont ID  
Sent By gjohnson Date 2018-01-17 Time 07:56 Rev Time 0.00
Received By gjohnson Date 2018-01-17 Time 07:55 Sent To  
Notes
2018-01-17 07:58:112ND REVIEW: FBC 2014 5TH EDITION
 PLUMBING COMMENTS:
  
 PROVISO:
  
 PREVIOUS COMMENT NOT COMPLIED 3. PLEASE PROVIDE A LIST
 HOW UP TO AN ADDITIONAL $24,000.00 DOLLARS WILL BE
 SPENT IN ACCESSIBLE UPGRADES. 2014 FBC-ACCESS. CODE
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 SHALL COMPLY WITH BUILDINGS COMMENT #6 PRIOR TO PERMIT
 ISSUE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By gjohnson Date 2017-12-27 Time 10:09 Rev Time 0.00
Received By gjohnson Date 2017-12-27 Time 06:43 Sent To  
Notes
2017-12-27 11:03:071ST REVIEW: FBC 2014 5TH EDITION
 PLUMBING COMMENTS:
  
  
 1. SHEET C-1 THE COVERSHEET HAS A INDEX, MISSING
 SHEETS:
 SHEETS 1.1A EQUIPMENT PLAN & SCHEDULE MISSING IN BOTH
 SETS.
 SHEET 1.5A SECTIONS & DETAILS
 SHEET 1.7A REFLECTED CEILING PLAN
  
 2. SHEET C-1 THE COVERSHEET LIST INTERIOR SEATING AND
 EXTERIOR SEATING AS 292 SEATS. SHEET 1.4A WHEN YOU
 TOTAL UP ALL OF THE SEATING THE COUNT IS 343 SEATS NOT
 COUNTING THE OCCUPANT LOAD IN THE VIDEO GAMES AND
 BILLIARD AREA NOT THE KITCHEN AREA, BEHIND THE BARS(
 WORK AREAS) NOR FOR STORAGE AREAS, PLEASE PROVIDE THE
 SQUARE FEET FOR EACH OF THESE AREAS AND THE OCCUPANT
 LOADS BASED FROM FBC-B TABLE 1004.1.2. SHEET A1.4 THE
 LIFE SAFETY SHEET LIST A OCCUPANT LOAD A LOT LESS THAN
 THE SEATING COUNT FOUND ON THE COVER SHEET. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3. PLEASE PROVIDE A LIST HOW UP TO AN ADDITIONAL
 $24,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE
 UPGRADES. 2014 FBC-ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4. SHT. 3.0P IN THE PLUMBING NOTES IT REFERENCES THE
 2007 AND 2010 CODES IT IS THE 2014 CODE THAT IS IN
 EFFECT PLEASE CORRECT . PER WPB AMEND TO FBC 107.2.1
  
 5. THE WASTE FROM THE NEW MAIN BAR AREA IS NOT
 CONSIDERED GREASE LADEN WASTE AND THEREFOR SHALL NOT
 DISCHARGE TO THE GREASE INTERCEPTOR IT SHALL CONNECT TO
 THE SANITARY. PER FBC PL 1003.2
  
 6. PLEASE PROVIDE WATER RISER DIGRAM. PER WPB AMEND TO
 FBC 107.2.1
  
 7. PLEASE SHOE WATER AND GAS ON THE FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 8. THE GREASE RISER DOES NOT MATCH THE FLOOR PLAN
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  