Plan Review Details - Permit 17120145
Plan Review Stops For Permit 17120145
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-12-05 Cont ID  
Sent By rmcdouga Date 2017-12-05 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2017-12-05 Time 15:31 Sent To I
Notes
2017-12-05 15:56:57APPROVED WITH EXCEPTION
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 1) SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS THAT IS
 REQUIRED FOR THE NEW TILE FLOORING. TEST REPORTS MAY BE
 BASED ON THE FOLLOWING ASTM'S: E-84, E-90 & E-492. FBC
 603.1 FLAME SPREAD - ASTM E 84-09, FBC 1207.2 AIR-BORNE
 SOUND - ASTM E 90-04 AND FBC 1207.3 STRUCTURE-BORNE
 SOUND - ASTM E 492-09.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-05 Cont ID  
Sent By rmcdouga Date 2017-12-05 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2017-12-05 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-05 Cont ID  
Sent By rmcdouga Date 2017-12-05 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2017-12-05 Time 17:42 Sent To  
Notes
2017-12-05 17:43:18REMOVE AND REPLACE FIXTURES IN SAME LOCATIONS.

Review Stop Z ZONING
Rev No 1 Status N Date 2017-12-05 Cont ID  
Sent By rmcdouga Date 2017-12-05 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2017-12-05 Time 15:57 Sent To  
Notes
***NONE***