| 2017-12-05 18:26:04 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1-PERMIT APPLICATION DESCRIBES RE-ROOF OF 3 SQUARES OF |
| | FLAT ROOF. PROVIDE PRODUCT APPROVAL (2 COPIES) OF FLAT |
| | ROOF PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001. |
| | NO PRODUCT APPROVAL WAS SUBMITTED AT THIS TIME. CLEARLY |
| | SPECIFY ASSEMBLY TO BE INSTALLED. AND PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. |
| | NOTE: KEEP IN MIND THAT THIS HOUSE IS LOCATED IN |
| | EXPOSURE "D". THIS IS IMPORTANT WHEN DETERMINING THE |
| | ROOF DESIGN PRESSURES. |
| | |
| | 2- MEAN ROOF HEIGHT SPECIFIED ON THE PERMIT APPLICATION |
| | IS INCORRECT. THIS HOUSE HAS A SECOND FLOOR. THEREFORE, |
| | 12'-0" MEAN ROOF HEIGHT IS INCORRECT. REVISE AS |
| | REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 3- ROOF TILE NOA 16-0711.05 SUBMITTED: CLEARLY MARK ON |
| | THE NOA THE ROOF TILE FASTENING METHOD TO BE USED TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. NOTE: KEEP IN MIND THAT THIS |
| | BUILDING IS LOCATED IN EXPOSURE "D". IF USING SCREWS, |
| | THEN SPECIFY NUMBER OF SCREWS AND SIZE. IF USING |
| | ADHESIVE, THEN PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| | REQUIRED BY FAC 61G20-3.001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |