Plan Review Details - Permit 17120096
Plan Review Stops For Permit 17120096
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-06 Cont ID  
Sent By jwitmer Date 2018-03-06 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2018-03-06 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-29 Cont ID  
Sent By jwitmer Date 2018-01-29 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2018-01-29 Time 14:32 Sent To  
Notes
2018-01-29 16:45:082014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120096
 ADD: 500 BELVEDERE RD. SUITE 642
 CONT: RCE GROUP, INC.
 TEL: 786-444-7134
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 29/ 2018
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST. THIS REVIEW MANUFACTURER SPEC SHEETS
 WERE SUBMITTED, BUT PROCESS NOT FOLLOWED. THE BOTTOM OF
 THE SPEC SHEET INDICATES THE USER MUST CONTACT
 CARBOLINE COMPANY TO VERIFY CORRECTNESS BEFORE
 SPECIFYING OR ORDERING. MUST KNOW THE TYPE OF PRIMER,
 METHOD OF APPLICATION AND RATE OF BASE COAT AND
 SECONDARY TOP FINAL COAT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO ASSURE THE PROPER FIRE
 RATING PER TABLE 601 OF THE 2014 FBC-B.
  
 COMMENTS FROM 1ST REVIEW. SHEET F-2 LIST IN THE FLOOR
 PLAN THE USE OF NULLIFIRE S606 PAINT TO BE APPLIED TO
 ALL EXPOSED ROOF STRUCTURAL SURFACES, BEING THIS IS
 LISTED AS EITHER TYPE IIA OR TYPE III UNSPRINKLERED.
 SEE TABLE 601 ROOF CONSTRUCTION AND ASSOCIATED
 SECONDARY MEMBERS. PLEASE PROVIDE HOW THE FIRE RATING
 WILL BE ACHIEVED, PROVIDE THE MANUFACTURERS RATE OF
 APPLICATION INSTRUCTIONS.
  
 7-8) COMPLIED.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By jwitmer Date 2017-12-18 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2017-12-15 Time 15:10 Sent To  
Notes
2017-12-18 07:45:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120096
 ADD: 642 BELVEDERE RD. SUITE # ???
 CONT: RCE GROUP, INC.
 TEL: 786-444-7134
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 15/ 2017
 ACTION: DENIED
  
 1) THE PLANS DOES NOT PROVIDE A SUITE ADDRESS AND THE
 PERMIT APPLICATION INDICATES THE SUITE NUMBER AS 111.
 PLEASE NOTE THE SITE ADDRESS IS: 500 BELVEDERE ROAD,
 GOOGLE EARTH SHOWS THE TENANT SPACE AS UNIT :624.
 PLEASE CORRECT THE ADDRESS ON THE PLANS AS WELL AS THE
 PERMIT APPLICATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE COVERSHEET A-0 UNDER THE HEADING ZONING DATA
 LIST THE BUILDING TYPE A TYPE III-UNSPRINKLERED
 BUILDING. ON SHEET F-2 THE TYPE OF CONSTRUCTION LISTED
 AS II-A FULLY SPRINKLERED. THERE IS A DISCREPANCY IN
 THE PLANS AS TO THE TYPE OF CONSTRUCTION AS WELL AS IF
 THE BUILDING IS FIRE SPRINKLERED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE COVERSHEET A-0 UNDER THE HEADING OCCUPANCY
 SEPARATION LIST FIRE SEPARATION REQUIRED N/A.
 SHEET F-2 INDICATES THE EXISTING TENANT SEPARATION
 WALLS AS EXISTING 2 HOUR WALLS. THERE IS A TENANT ON
 THE EAST SIDE AND PLEASE PROVIDE THE OCCUPANCY, PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B TABLE 508.4 FOR
 HOUR RATING, AND IF THE BUILDING IS SPRINKLERED OR NOT.
  
 4) BOTH SHEETS A-0 THE COVERSHEET AND SHEET F-2 BOTH
 CLASSIFY THE ALTERATION AS A LEVEL III ALTERATION.
 PLEASE REVIEW THE 2014 EXISTING BUILDING CODE SECTION
 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK
 AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE
 BUILDING.
 THE CODE STATES BUILDING NOT TENANT SPACE. THIS SPACE
 WAS A BAR/ RESTAURANT (A-2 OCCUPANCY) AND CONVERTED
 INTO A KARATE SCHOOL/ GYM (A-3 GYM).
  
 2014 FBC-EXISTING BUILDING CODE 1001.2 CHANGE IN
 OCCUPANCY WITH NO CHANGE OF OCCUPANCY CLASSIFICATION. A
 CHANGE IN OCCUPANCY, AS DEFINED IN SECTION 202, WITH NO
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL NOT BE MADE TO
 ANY STRUCTURE THAT WILL SUBJECT THE STRUCTURE TO ANY
 SPECIAL PROVISIONS OF THE APPLICABLE FLORIDA BUILDING
 CODES, INCLUDING THE PROVISIONS OF SECTIONS 1002
 THROUGH 1011, WITHOUT THE APPROVAL OF THE CODE
 OFFICIAL. A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED
 WHERE IT HAS BEEN DETERMINED THAT THE REQUIREMENTS FOR
 THE CHANGE IN OCCUPANCY HAVE BEEN MET.
  
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 5) BOTH SHEETS A-0 THE COVERSHEET AND SHEET F-2 HAVE
 INTERIOR FINISH SCHEDULE WITH A CLASS B INTERIOR WALL &
 CEILING FINISH- FLAME SPREAD OF 26- 75, AND SMOKE
 DEVELOPMENT OF 0- 450. PLEASE NOTE THIS IS FOR FIRE
 SPRINKLERED BUILDINGS. UNTIL COMMENT # 2 IS SATISFIED
 FOR FIRE SPRINKLERS THIS MAY BE CORRECT OR NOT. SEE
 2014 FBC-B TABLE 803.9
  
 6) SHEET F-2 LIST IN THE FLOOR PLAN THE USE OF
 NULLIFIRE S606 PAINT TO BE APPLIED TO ALL EXPOSED ROOF
 STRUCTURAL SURFACES, BEING THIS IS LISTED AS EITHER
 TYPE IIA OR TYPE III UNSPRINKLERED. SEE TABLE 601 ROOF
 CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS. PLEASE
 PROVIDE HOW THE FIRE RATING WILL BE ACHIEVED, PROVIDE
 THE MANUFACTURERS RATE OF APPLICATION INSTRUCTIONS.
  
 7) THE FLOOR PLAN F-2 SHOWS THE OFFICE DOOR AND BOTH
 RESTROOMS AS A DOOR LABEL IDENTIFICATION TAG AS TYPE A.
 ON THE FLOOR PLAN A-1 WITH THE DOOR SCHEDULE THESE
 DOORS ARE LISTED AS NUMBER 3 AND ALL 3 ARE 2 FEET- TEN
 INCHES WIDE.
 THE 2014 FBC-B SECTION 1008.1.1 SIZE OF DOORS REQUIRES
 A 3 FOOT WIDE DOOR. THE MINIMUM WIDTH OF EACH DOOR
 OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP WITH
 THE DOOR OPEN 90 DEGREES. WHERE THIS SECTION REQUIRES A
 MINIMUM CLEAR WIDTH OF 32 INCHES AND A DOOR OPENING
 INCLUDES TWO DOOR LEAVES WITHOUT A MULLION, ONE LEAF
 SHALL PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES.
  
 8) SHEET A-2 DETAIL # 2 SHOWS A WALL OVEN WITH THE
 CONTROLS ABOVE THE REACH RANGES FOR OPERABLE PARTS.
 WILL THIS OVEN BE USED FOR JUST EMPLOYEES OR EMPLOYEES
 AND GUEST?
  
 2014 ACCESSIBILITY CODE. 308 REACH RANGES. 308.2
 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH. 308.3 SIDE REACH. / 308.3.1
 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH REACH.
  
 2014 ACCESSIBILITY CODE. 309 OPERABLE PARTS. 309.3
 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR
 MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4
 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH ONE
 HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR
 TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE
 OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
 2014 ACCESSIBILITY CODE ADVISORY 226.1. IN FACILITIES
 COVERED BY THE ADA, THIS REQUIREMENT DOES NOT APPLY TO
 WORK SURFACES USED ONLY BY EMPLOYEES. HOWEVER, THE ADA
 AND, WHERE APPLICABLE, SECTION 504 OF THE
 REHABILITATION ACT OF 1973, AS AMENDED, PROVIDE THAT
 EMPLOYEES ARE ENTITLED TO ?REASONABLE ACCOMMODATIONS.?
 WITH RESPECT TO WORK SURFACES, THIS MEANS THAT
 EMPLOYERS MAY NEED TO PROCURE OR ADJUST WORK STATIONS
 SUCH AS DESKS, LABORATORY AND WORK BENCHES, FUME HOODS,
 RECEPTION COUNTERS, TELLER WINDOWS, STUDY CARRELS,
 COMMERCIAL KITCHEN COUNTERS, AND CONFERENCE TABLES TO
 ACCOMMODATE THE INDIVIDUAL NEEDS OF EMPLOYEES WITH
 DISABILITIES ON AN ?AS NEEDED? BASIS. CONSIDER WORK
 SURFACES THAT ARE FLEXIBLE AND PERMIT INSTALLATION AT
 VARIABLE HEIGHTS AND CLEARANCES.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By jpearson Date 2018-02-07 Time 15:56 Rev Time 0.00
Received By jpearson Date 2018-02-07 Time 15:56 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-20 Cont ID  
Sent By jpearson Date 2017-12-20 Time 15:50 Rev Time 0.00
Received By jpearson Date 2017-12-20 Time 15:50 Sent To  
Notes
2017-12-20 15:50:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN INCLUDES A BLOCK NOTE REFERENCING THE FBC
 RESIDENTIAL FOR ENERGY COMPLIANCE. THIS PROJECT IS NOT
 RESIDENTIAL, REMOVE ANY INFORMATION NOT RELEVANT TO
 THIS PROJECT. FBC 107.2.1
 2. PLAN INCLUDES A BLOCK NOTE REFERENCING SMOKE ALARMS
 IN DWELLING UNITS. REMOVE ANY INFORMATION NOT RELEVANT
 TO THIS PLAN. FBC 107.2.1
 3. PLAN NOTE STATES THIS INSTALLATION TO COMPLY WITH
 THE NEC 2014, WHICH IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 5. PLAN SHOWS EMERGENCY AND EXIT LIGHTS ON CIRCUIT #
 31. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 6. PROVIDE SHOW WINDOW OUTLETS PER CODE. NEC 210.62
 7. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC 405.2.4
 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES LOCATED
 WITHIN 6 FEET OF A SINK. NEC 210.8
 9. PLAN DOES NOT SHOW ANY RECEPTACLE OUTLETS AT POS.
 HOW WILL THE COMPUTERS THERE RECEIVE POWER? FBC 107.2.1
 10. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING
 POWER ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO
 THE CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-03-07 Cont ID  
Sent By pleduc Date 2018-03-07 Time   Rev Time 0.00
Received By pleduc Date 2018-03-07 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-25 Cont ID  
Sent By pleduc Date 2018-01-25 Time   Rev Time 0.00
Received By pleduc Date 2018-01-25 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-06 Cont ID  
Sent By pleduc Date 2017-12-06 Time   Rev Time 0.00
Received By pleduc Date 2017-12-06 Time 10:01 Sent To  
Notes
2017-12-06 11:54:52THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A O - THERE IS AN INDICATION THAT THE BUILDING
 CONSTRUCTION IS A TYPE III UNSPRINKLED. SHEET F 2
 INDICATES A FULLY SPRINKLED BUIDLING W/FIRE ALARM.
  
 PLEASE CLARIFY WHICH IS CORRECT AND UPDATE ACCORDINGLY.
  
 IF A FIRE SPRINKLER SYSTEM IS EXISITNG, PROVIDE A
 APPLICABLE CLOUDED NOTE INDICATING THAT "ALL FIRE
 SPRINKLER WORK SHALL BE DONE BY CERTIFIED FIRE
 SPRINKLER CONTRACTOR UNDER SEPARATE SHOP DRAWINGS".
  
  
  
 2) SHEET F 2 - THERE IS AN INDICATION THAT A FIRE ALARM
 SYSTEM IS EXISTING.
  
 PLEASE CONFIRM WITH EXSITING DEVICES ON THE DEMO SHEET.
  
 IF A FIRE ALARM SYSTEM IS EXISITNG, PROVIDE A
 APPLICABLE CLOUDED NOTE INDICATING THAT "ALL FIRE ALARM
 WORK SHALL BE DONE BY CERTIFIED FIRE ALARM CONTRACTOR
 UNDER SEPARATE SHOP DRAWINGS".
  
  
  
  
 3) SHEET A 1 - THERE IS AN INDICATION OF DBL OVEN IN
 THE MULT-IPURPOSE ROOM.
  
 PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS INCLUDING
 ANY REQUIRED VENTING.
  
 PLEASE BE AWARE THAT PER NFPA 101, CHAPTER 12, NEW
 ASSEMBLY OCCUPANCIES:
  
 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 PLEASE ALSO PROVIDE A NARRATIVE OF HOW THE MENU WILL BE
 CONTROLLED TO COMPLY WITH COMPLIANCE OF THE NOTED CODE
 REQUIREMENTS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By gjohnson Date 2018-02-07 Time 11:48 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 11:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By gjohnson Date 2017-12-28 Time 12:24 Rev Time 0.00
Received By gjohnson Date 2017-12-28 Time 12:24 Sent To  
Notes
2017-12-28 12:27:001ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DEMO PLAN FOR THE GAS . PER WPB AMEND
 TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-20 Cont ID  
Sent By ajones Date 2018-03-20 Time 16:37 Rev Time 0.00
Received By ajones Date 2018-03-01 Time 09:35 Sent To  
Notes
2018-03-02 09:37:54B10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-23 Time 14:11 Sent To  
Notes
2018-01-24 14:11:50B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-28 Cont ID  
Sent By gjohnson Date 2017-12-28 Time 13:03 Rev Time 0.00
Received By gjohnson Date 2017-12-04 Time 15:18 Sent To  
Notes
2017-12-05 15:19:12B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-03-06 Cont ID  
Sent By jwitmer Date 2018-03-06 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2018-03-06 Time 14:34 Sent To  
Notes
2018-03-06 14:52:50TUES. MARCH 06/ 2018
 PALM BEACH COUNTY IMPACT FEE STAMP
 NO FEES DUE KARATE SCHOOL
 DATE STAMPED 03/01/2018
 TECH: MAB

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-01-29 Cont ID  
Sent By jwitmer Date 2018-01-29 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2018-01-29 Time 16:45 Sent To  
Notes
2018-01-29 16:46:191) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By jwitmer Date 2017-12-18 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2017-12-15 Time 15:10 Sent To  
Notes
2017-12-18 07:45:041) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 08:41 Rev Time 0.00
Received By ccole Date 2018-03-12 Time 17:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-02-02 Cont ID  
Sent By ccole Date 2018-02-02 Time 12:59 Rev Time 0.00
Received By ccole Date 2018-02-02 Time 12:23 Sent To  
Notes
2018-02-02 13:07:502ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120096
 2/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE OUTSIDE AIR CALCULATION IS INDICATING
 1204 CFMS REQUIRED FOR THE KARATE STUDIO AREA. BASED ON
 THAT CALCULATION THE EXISTING 5-TON 2000 CFM SYSTEM
 WHICH IS SUPPLYING MOST OF THE ROOM WOULD BE UNDERSIZED
 TO CONDITION THAT HIGH PERCENTAGE OF OUTSIDE AIR.
 PERCENTAGE OF OUTSIDE AIR TO SUPPLY AIR IS GENERALLY
 AROUND 20 %.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By ccole Date 2017-12-18 Time 15:04 Rev Time 0.00
Received By ccole Date 2017-12-18 Time 14:55 Sent To  
Notes
2017-12-18 15:18:361ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120096
 12/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR
 PACKAGE UNIT'S #1 & 2 IN COMPLIANCE WITH SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM OF AHU #3- SECTION 606.2.1.
  
 4) SHOW THE TOILET ROOM EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- SECTION 501.3.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By gjohnson Date 2018-02-07 Time 11:48 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-28 Cont ID  
Sent By gjohnson Date 2017-12-28 Time 12:27 Rev Time 0.00
Received By gjohnson Date 2017-12-28 Time 11:01 Sent To  
Notes
2017-12-28 13:00:111ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE ISOMETRIC DRAWINGS FOR SANITARY AND WATER.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. THE KITCHEN SINK IS REQUIRED TO DISCHARGE THROUGH A
 GREASE TRAP OR INTERCEPTOR. PER FBC PL 1003.3.1
  
 3. PLEASE PROVIDE MANUFACTURE SPECS FOR TANKLESS WATER
 HEATER. PER WPB AMEND TO FBC 107.2.1
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-20 Cont ID  
Sent By llouie Date 2018-03-20 Time 16:37 Rev Time 0.00
Received By ajones Date 2018-03-20 Time 16:37 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-12-13 Cont ID  
Sent By LL Date 2017-12-13 Time   Rev Time  
Received By llouie Date 2017-12-13 Time   Sent To  
Notes
2017-12-13 10:08:46- INTERIOR MODIFICATIONS ONLY.
 - Z=GC (PROPOSED USE: MARTIAL ARTS STUDIO PERMITTED).