Plan Review Details - Permit 17120055
Plan Review Stops For Permit 17120055
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-19 Cont ID  
Sent By jgomez Date 2018-03-19 Time 11:32 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 08:13 Sent To  
Notes
2018-03-19 08:21:03BUILDING REVIEW APPROVED WITH PROVISO:
 1- NEED CARBON MONOXIDE ALARMS BY ALL BEDROOMS. SEC.
 R315.1 FBC-RESIDENTIAL.
 2- DESIGNER OF RECORD TO REVISE ROOF CLAY TILE
 FASTENING SPECIFIED ON SHEET A-3. IT DOESN'T MEET THE
 UPLIFT MOMENT FOR FOR PERIMETER AND CORNER AREAS. SEE
 TABLE 2A OF FRSA 5TH EDITION REVISED AND CLAY TILE NOA
 17-0626.03 SUBMITTED..
 3- FLAT ROOF NOA 14-1030.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-22 Cont ID  
Sent By jgomez Date 2018-01-22 Time 15:07 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 13:09 Sent To  
Notes
2018-01-22 13:48:42RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET A-1:
 A) DESIGN LOADS SPECIFIED ON THE ROOF PLAN NOTES DON'T
 MATCH THE DESIGN LOADS SPECIFIED ON THE SAME SHEET
 BELOW THE ROOF SHEATHING NAILING PATTERN TABLE.
 CLARIFY/REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: CLARIFY WHY THE MEAN ROOF HEIGHT IS LESS THAN 15
 FEET AND THE ROOF SLOPE IS 23 DEGREES?. COORDINATE WITH
 THE NEW SECOND STORY WALK-IN CLOSET ALSO.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROPOSED FLAT ROOF & PARAPET SHOWN ON THE PROPOSED
 ROOF PLAN DOESN'T MATCH NORTH ELEVATION ON SHEET A-2.
 THE LOCATION OF THE OVERFLOW SCUPPERS IS NOT CLEAR.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) PROPOSED METAL STAIRS INFORMATION SHOWN ON THE
 PROPOSED FIRST FLOOR PLAN DOESN'T MATCH INFORMATION
 SHOWN ON SHEET A-4. CLARIFY SIZE OF FOOTING AND RISER
 HEIGHT. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- SHEET A-4:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ATTACHMENT OF THE SPIRAL STAIRS SHOWING COMPLIANCE WITH
 THE WIND LOADS. SPECIFY ALL CONNECTORS AT THE TOP AND
 BOTTOM. SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- SHEET A-5:
 A) LOCATION OF OVERFLOW SCUPPERS SHOWN ON THE ROOF PLAN
 DON'T MATCH LOCATION SHOWN ON THE NORTH ELEVATION.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) WALL SECTIONS; SPECIFY TWO LAYERS OF WATER RESISTIVE
 BARRIERS AS REQUIRED BY SEC. R703.6.3 FBC-RESIDENTIAL.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- SPECIFY ON PLANS CARBON MONOXIDE ALARMS IN THE
 LOCATIONS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL BY
 ALL BEDROOMS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 6- DESIGNER OF RECORD TO SPECIFY ROOF CLAY TILE
 FASTENING AS REQUIRED BY SEC. 107.2.1.2 CITY
 AMENDMENTS. NOTE: IF SPECIFYING SCREWS, THEN SPECIFY
 SIZE AND NUMBER OF SCREWS. IF SPECIFYING ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF CLAY TILES AS SPECIFIED ON PLANS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE CLAY TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) TERRACE FLOATING FLOOR TILES AS SPECIFIED ON PLANS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By jgomez Date 2017-12-29 Time 17:58 Rev Time 0.00
Received By jgomez Date 2017-12-29 Time 09:30 Sent To I
Notes
2017-12-29 15:12:16RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET A-1:
 A) DESIGN LOADS SPECIFIED ON THE ROOF PLAN NOTES DON'T
 MATCH THE DESIGN LOADS SPECIFIED ON THE SAME SHEET
 BELOW THE ROOF SHEATHING NAILING PATTERN TABLE.
 CLARIFY/REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: CLARIFY WHY THE MEAN ROOF HEIGHT IS LESS THAN 15
 FEET AND THE ROOF SLOPE IS 23 DEGREES?. COORDINATE WITH
 THE NEW SECOND STORY WALK-IN CLOSET ALSO.
  
 B) PROPOSED FLAT ROOF & PARAPET SHOWN ON THE PROPOSED
 ROOF PLAN DOESN'T MATCH NORTH ELEVATION ON SHEET A-2.
 THE LOCATION OF THE OVERFLOW SCUPPERS IS NOT CLEAR.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) PROPOSED METAL STAIRS INFORMATION SHOWN ON THE
 PROPOSED FIRST FLOOR PLAN DOESN'T MATCH INFORMATION
 SHOWN ON SHEET A-4. CLARIFY SIZE OF FOOTING AND RISER
 HEIGHT. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHEET A-4:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICTIONS FOR THE
 ATTACHMENT OF THE SPIRAL STAIRS SHOWING COMPLIANCE WITH
 THE WIND LOADS. SPECIFY ALL CONNECTORS AT THE TOP AND
 BOTTOM. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- SHEET A-5:
 A) LOCATION OF OVERFLOW SCUPPERS SHOWN ON THE ROOF PLAN
 DON'T MATCH LOCATION SHOWN ON THE NORTH ELEVATION.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) WALL SECTIONS; SPECIFY TWO LAYERS OF WATER RESISTIVE
 BARRIERS AS REQUIRED BY SEC. R703.6.3 FBC-RESIDENTIAL.
  
 5- SPECIFY ON PLANS CARBON MONOXIDE ALARMS IN THE
 LOCATIONS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL BY
 ALL BEDROOMS.
  
 6- DESIGNER OF RECORD TO SPECIFY ROOF CLAY TILE
 FASTENING AS REQUIRED BY SEC. 107.2.1.2 CITY
 AMENDMENTS. NOTE: IF SPECIFYING SCREWS, THEN SPECIFY
 SIZE AND NUBMER OF SCREWS. IF SPECIFYING ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF ASSEMBLY WITH INSULATION AS SPECIFIED ON
 WALL SECTIONS ON SHEET A-5. NOTE: CLEARLY MARK SPECIFIC
 ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
  
 B) ROOF CLAY TILES AS SPECIFIED ON PLANS.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE CLAY TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 D) TERRACE FLOATING FLOOR TILES AS SPECIFIED ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-12-28 Cont ID  
Sent By jpearson Date 2017-12-28 Time 12:28 Rev Time 0.00
Received By jpearson Date 2017-12-28 Time 12:28 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-03-05 Cont ID  
Sent By fmittner Date 2018-03-05 Time 15:31 Rev Time 0.00
Received By fmittner Date 2018-03-05 Time 15:31 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-12-19 Cont ID  
Sent By FM Date 2017-12-19 Time 11:25 Rev Time 0.00
Received By fmittner Date 2017-12-15 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-19 Cont ID  
Sent By jgomez Date 2018-03-19 Time 11:46 Rev Time 0.00
Received By jgomez Date 2018-02-28 Time 13:02 Sent To I
Notes
2018-03-01 13:03:05RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-22 Cont ID  
Sent By jgomez Date 2018-01-22 Time 15:42 Rev Time 0.00
Received By jgomez Date 2018-01-16 Time 11:13 Sent To I
Notes
2018-01-17 11:14:02RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-29 Cont ID  
Sent By jgomez Date 2017-12-29 Time 18:01 Rev Time 0.00
Received By jgomez Date 2017-12-01 Time 13:19 Sent To I
Notes
2017-12-04 13:20:05R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-03-19 Cont ID  
Sent By jgomez Date 2018-03-19 Time 08:22 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 08:22 Sent To  
Notes
2018-03-19 08:23:05ACCORDING TO PBC IMPACT FEE TABLE EFFECTIVE JUNE 15,
 2014 NO ADDITIONAL IMPACT FEES FOR RESIDENCES WITH OVER
 3600 S.F.
  
 RESIDENTIAL (PER UNIT NET SQ. FT.)
 800 & UNDER 269.67 0.00 140.96 793.40 1,204.03
 801 -1,399 541.51 0.00 170.54 1,593.23 2,305.28
 1,400 - 1,999 581.16 0.00 194.88 1,709.89 2,485.93
 2,000 - 3,599 634.09 0.00 222.80 1,865.63 2,722.52
 3,600 & OVER 603.49 0.00 244.71 1,775.58 2,623.78
 HOTEL/MOTEL 201.51 0.00 57.18 0.00 258.69

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-01-22 Cont ID  
Sent By jgomez Date 2018-01-22 Time 14:05 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 14:05 Sent To  
Notes
2018-01-22 14:06:091- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By jgomez Date 2017-12-29 Time 17:59 Rev Time 0.00
Received By jgomez Date 2017-12-29 Time 17:59 Sent To  
Notes
2017-12-29 17:59:571- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-03-19 Cont ID  
Sent By jgomez Date 2018-03-19 Time 11:44 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 11:44 Sent To  
Notes
2018-03-19 11:46:231- DESIGNER OF RECORD TO REVISE ROOF CLAY TILE
 FASTENING SPECIFIED ON SHEET A-3. IT DOESN'T MEET THE
 UPLIFT MOMENT FOR FOR PERIMETER AND CORNER AREAS. SEE
 TABLE 2A OF FRSA 5TH EDITION REVISED AND CLAY TILE NOA
 17-0626.03 SUBMITTED..
 2- FLAT ROOF NOA 14-1030.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
  
 APPROVED ROOF TILE NOA 17-0626.03.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-01-22 Cont ID  
Sent By jgomez Date 2018-01-22 Time 15:40 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 15:40 Sent To  
Notes
2018-01-22 15:42:261- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF CLAY TILES AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE CLAY TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) TERRACE FLOATING FLOOR TILES AS SPECIFIED ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-12-29 Cont ID  
Sent By jgomez Date 2017-12-29 Time 18:00 Rev Time 0.00
Received By jgomez Date 2017-12-29 Time 13:40 Sent To  
Notes
2017-12-29 18:00:59NEED FLAT ROOF AND ROOF CLAY TILES PRODUCT APPROVALS

Review Stop Z ZONING
Rev No 1 Status P Date 2017-12-19 Cont ID  
Sent By fmittner Date 2017-12-19 Time 11:25 Rev Time 0.00
Received By fmittner Date 2017-12-19 Time 11:25 Sent To  
Notes
***NONE***