Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-26 Cont ID  
Sent By aclange Date 2018-02-26 Time 09:02 Rev Time 0.00
Received By aclange Date 2018-02-26 Time 07:49 Sent To  
Notes
2018-02-26 09:02:31****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 SECOND REVIEW:
  
  
 1) ADDRESSED OK
  
 PLEASE UPDATE DEMO KEY NOTES TO INCLUDE #12 AND #13
 THAT ARE NOT SHOWN ON PAGE AD1.1. ON PAGE A-2.01
 ELEVATION #6 NOTE SHOWN AS NEEDED.
  
 2) SUBMIT SEPARATE PERMIT FOR AWNING WHEN READY
  
 PROVIDE STRUCTURAL SHOP DRAWINGS FOR AWNING SHOWN AS
 KEY NOTE #7 ON A-2.0.1.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
 3) PARTIALLY ADDRESSED. RECEIVED PRODUCT APPROVAL.
 DESIGNER OF RECORD HAS NOT REVIEWED.
  
 PROVIDE PRODUCT APPROVAL FOR TRULITE DOOR USED WITH THE
 TRULITE STOREFRONT WALL SYSTEM. IT HAS ITS OWN PRODUCT
 APPROVAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4) THIS PATH OF TRAVEL IS THROUGH AN EXISTING MOTOR
 VEHICLE REPAIR GARAGE FBC 311.2. AD1.1 SHOWS NO WORK IN
 THIS AREA. ALS1.1 SHOWS TRAVEL THROUGH THIS AREA.
  
 ON LIFE SAFETY ALS.1.1 THE SECOND EXIT SHOWN IS THROUGH
 A STORAGE ROOM.
  
 FBC 1014.2 EGRESS THROUGH INTERVENING SPACES.
  
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
  
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
  
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS: 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT
 ACCESS IS THROUGH THE STOCKROOM.
 NOTE: THIS EGRESS DOES NOT EXCEED THE 50 PERCENT
 ALLOWED BY EXCEPTION 2.2. BUT SHALL COMPLY WITH FBC
 1014.2 EXCEPTION 2. AN EXIT ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
  
 5) NOT ADDRESSED
 PROVIDE THE STORAGE CLASSIFICATION FOR THE EXISTING
 STORAGE AREA AND ITS COMPLIANCE WITH FBC 311 STORAGE
 GROUP S. BASED ON THIS DETERMINATION. INCLUDE
 INFORMATION ON THE DOOR, RATING AND IF A CLOSURE WILL
 BE PROVIDED AND IF THE WINDOW WILL BE PROVIDED WITH A
 RATING.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By aclange Date 2017-12-27 Time 13:33 Rev Time 0.00
Received By aclange Date 2017-12-27 Time 09:24 Sent To  
Notes
2017-12-27 13:37:00****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1) PLEASE UPDATE DEMO KEY NOTES TO INCLUDE #12 AND #13
 THAT ARE NOT SHOWN ON PAGE AD1.1. ON PAGE A-2.01
 ELEVATION #6 NOTE SHOWN AS NEEDED.
  
 2) PROVIDE STRUCTURAL SHOP DRAWINGS FOR AWNING SHOWN AS
 KEY NOTE #7 ON A-2.0.1.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
 3) PROVIDE PRODUCT APPROVAL FOR TRULITE DOOR USED WITH
 THE TRULITE STOREFRONT WALL SYSTEM. IT HAS ITS OWN
 PRODUCT APPROVAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4) ON LIFE SAFETY ALS.1.1 THE SECOND EXIT SHOWN IS
 THROUGH A STORAGE ROOM.
  
 FBC 1014.2 EGRESS THROUGH INTERVENING SPACES.
  
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
  
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
  
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS: 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT
 ACCESS IS THROUGH THE STOCKROOM.
 NOTE: THIS EGRESS DOES NOT EXCEED THE 50 PERCENT
 ALLOWED BY EXCEPTION 2.2. BUT SHALL COMPLY WITH FBC
 1014.2 EXCEPTION 2. AN EXIT ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
  
 5) PROVIDE THE STORAGE CLASSIFICATION FOR THE EXISTING
 STORAGE AREA AND ITS COMPLIANCE WITH FBC 311 STORAGE
 GROUP S. BASED ON THIS DETERMINATION. INCLUDE
 INFORMATION ON THE DOOR, RATING AND IF A CLOSURE WILL
 BE PROVIDED AND IF THE WINDOW WILL BE PROVIDED WITH A
 RATING.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By jpearson Date 2018-03-06 Time 09:26 Rev Time 0.00
Received By jpearson Date 2018-03-06 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-01-04 Cont ID  
Sent By jpearson Date 2018-01-04 Time 15:38 Rev Time 0.00
Received By jpearson Date 2018-01-04 Time 15:38 Sent To  
Notes
2018-01-04 15:38:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. GRAPH FOR ENERGY COMPLIANCE OF LIGHTING SHOWS THAT
 THE ALLOWED AMOUNT OF WATTS IS 3016, AND THE DESIGNED
 WATTAGE OF FIXTURES IS 3069, WHICH IS 53 WATTS IN
 EXCESS OF WHAT IS ALLOWED. PROVIDE CORRECTION. FBC CE
 405.5.2
 2. PROVIDE NOTE FOR MARKING OF HIGH LEG PER CODE. NEC
 110.15
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 6. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-04-30 Cont ID  
Sent By pleduc Date 2018-04-30 Time   Rev Time 0.00
Received By pleduc Date 2018-04-30 Time 12:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-20 Cont ID  
Sent By pleduc Date 2018-02-20 Time   Rev Time 0.00
Received By pleduc Date 2018-02-20 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By pleduc Date 2017-12-06 Time   Rev Time 0.00
Received By pleduc Date 2017-12-06 Time 10:02 Sent To  
Notes
2017-12-06 13:54:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) ALS 1.1 - THERE ARE THREE (3) OCCUPANCIES INDICATED;
 BUSINESS, ASSEMBLY & STORAGE. IS THIS A MIXED OR
 SEPARATED OCCUPANCY PER NFPA 101?
  
 CHAPTER 6, OCCUPANCY CLASSIFICATION STATES:
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
  
 PLEASE CLARIFY
  
  
  
  
 2) ALS 1.1 - TWO(2) EXITS ARE INDICATED; HOWEVER, ONE
 EXIT TRAVERSES A STORAGE CLASSIFICATION.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS:
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS
 OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT
 ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO
 PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM
 HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PER # 1 ABOVE, ASSEMBLY OCCUPANCY IS THE MSOT
 RESTRICTIVE OF A MIXED OCCUPANCY.
  
 PER CHAPTER 12, NEW ASSEMBLY OCCUPANCIES:
  
 12.2.5.2 ACCESS THROUGH HAZARDOUS AREAS. MEANS OF
 EGRESS FROM A ROOM OR SPACE FOR ASSEMBLY PURPOSES SHALL
 NOT BE PERMITTED THROUGH KITCHENS, STOREROOMS,
 RESTROOMS, CLOSETS, PLATFORMS, STAGES, PROJECTION
 ROOMS, OR HAZARDOUS AREAS AS DESCRIBED IN 12.3.2.
  
  
 PLEASE RELOCATE THE EXIT TO COMPLY WITH THE REQUIRMENTS
 OR JUSTIFY WITH SPECIFIC CODE REFERENCES.
  
  
  
  
 3) ALS 1.1 & A 3.0.1 - DOOR # 117 IS INDICATED WITH A
 FOB ENTRY W/MANUAL KEY. PER NFPA 101, CHAPTER 12.
  
 12.2.2.2.6 DOORS IN THE MEANS OF EGRESS SHALL BE
 PERMITTED TO BE EQUIPPED WITH AN APPROVED ACCESS
 CONTROL SYSTEM COMPLYING WITH 7.2.1.6.2, AND SUCH DOORS
 SHALL NOT BE LOCKED FROM THE EGRESS SIDE WHEN THE
 ASSEMBLY OCCUPANCY IS OCCUPIED. (SEE 7.2.1.1.3.)
  
 PLEASE PROVIDE JSUTIFICATION MEETING THIS REQUIREMENT.
  
  
  
  
 4) SHEET ALS 1.1 - THERE IS A DOOR # 117 AND WINDOW "F"
 INDICATED IN THE WALL SEPRATING THE OFFICE AREA AND THE
 STORAGE AREA. THOUGH THIS WOULD NOT BE CONSIDERED A
 SEPARATION OF OCCUPANCY IT IS CONSIDERED A SEPARATION
 OF HAZARD.
  
 PER NFPA 101, CHAPTER 6:
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND
 SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED,
 AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS
 OF A BUILDING OR STRUCTURE, THE MOST HAZARDOUS SHALL
 GOVERN THE CLASSIFICATION, UNLESS HAZARDOUS AREAS ARE
 SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND
 THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH 43.
  
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE
 PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS INACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43
  
 PLEASE PROVIDE THE CLASSIFICATION HAZARD IN DETAIL AND
 PROVIDE FOR THE REQUIRED SEPARATION PER THE REQUIRMENT.
  
  
  
 5) SHEET AD 1.1 - THERE ARE NOTE BOXES IN THE DRAWING
 INDICATED AS # 12 & # 13. THERE IS NO CORRESPONDING
 NOTE EXPLANATIONS FOR THESE NUMBERS.
  
 PLEASE PROVIDE.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
 THE STORAGE IS NOT ACCESSORY AND THE EXIT CAN NOT
 TRAVERSE IT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 19:04 Rev Time 0.00
Received By shill Date 2018-04-25 Time 15:20 Sent To  
Notes
2018-04-26 15:20:44C05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-12 Cont ID  
Sent By gjohnson Date 2018-03-12 Time 17:13 Rev Time 0.00
Received By gjohnson Date 2018-02-06 Time 14:46 Sent To  
Notes
2018-02-07 14:46:45C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-19 Cont ID  
Sent By gjohnson Date 2018-01-19 Time 09:45 Rev Time 0.00
Received By gjohnson Date 2017-12-01 Time 14:54 Sent To  
Notes
2017-12-04 14:54:46C14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 15:55 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 14:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-02 Cont ID  
Sent By ccole Date 2018-01-02 Time 16:42 Rev Time 0.00
Received By ccole Date 2018-01-02 Time 15:46 Sent To  
Notes
2018-01-02 17:16:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120050
 1/2/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL SHALL BE
 ON THE PLANS AND ENERGY CALCULATIONS AS REQUIRED BY
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
 ELECTRONIC SIGNATURES AND SEALS ARE NOT ACCEPTED ON THE
 PAPER PLANS UNLESS ALL REQUIREMENTS LISTED UNDER
 SECTION 61G15-23.005 (2) & (3) FLORIDA ADMINISTRATIVE
 CODE ARE MET.
  
 2) M2.1: LABEL THE RETURN GRILLS AT THE OFFICE AND THE
 EXERCISE ROOM.
  
 3) M6.1, O/A CALCULATIONS: A) CORRECT THE OUTDATED
 ASHRAE 62.1-2004 REFERENCE. B) CORRECT THE CLAUCLATIONS
 PER ASHRAE 62.1-2010 OR TABLE 403.3 - CONFERENCE ROOMS
 ARE CALCULATED AT 50 PERSONS PER 1000 SQ. FT; RECEPTION
 AREAS AT 30 PERSONS PER SQ. FT.; LOUNGES OR DINING
 ROOMS AT 70 PERSONS PER SQ. FT. AT 7.5 CFM PER PERSON
 AND 0.18 CFMS PER SQ. FT.; EXERCISE ROOMS ARE
  
 CALCULATED AT 40 PERSONS PER SQ. FT. AT 20 CFMS PER
 PERSON AND 0.06 PER SQ. FT.
  
 4) KITCHEN EXHAUST AT A RATE OF 0.70 CFMS PER SQ. FT.
 IS REQUIRED PER TABLE 403.3. INDICATE HOW THIS
 REQUIREMENT IS BEING MET.
  
 5) A TYPE II EXHAUST HOOD IS REQUIRED FOR THE OVEN PER
 SECTION 507.2.2. A SEPARATE PERMIT IS REQUIRED FOR THE
 HOOD BUT IT SHALL BE INDICATED ON THE MAIN PERMIT
 PLANS.
  
 6) PLEASE PROVIDE THE MAKE AND MODEL OF THE OVEN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 917.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By gjohnson Date 2018-03-12 Time 17:12 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-19 Cont ID  
Sent By gjohnson Date 2018-01-19 Time 08:47 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 17:23 Sent To  
Notes
2018-01-19 09:44:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DIGITAL SIGNATURES ON ALL THE PLAN SHEETS ARE
 INVALID. DIGITAL SIGNATURES SHALL NOT BE USED ON PAPER
 PLANS. ALL SIGNATURES SHALL FOR ENGINEERS THEY SHALL
 COMPLY WITH FAC 61G15-23.003 FOR ARCHITECT THEY SHALL
 COMPLY WITH FAC 61G1-16.005
  
 2. THE SHOWER IN BATHROOM 112 SHALL COMPLY WITH ONE OF
 3 DESIGN TYPES IN FBC ACC
  
 A) 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES BY
 36 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE
 CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT. CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED.
  
 B) 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES WIDE MINIMUM BY 60 INCHES DEEP MINIMUM CLEAR
 INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING
 SIDES AND SHALL HAVE A 60 INCHES WIDE MINIMUM ENTRY ON
 THE FACE OF THE SHOWER COMPARTMENT.
 608.2.2.1 CLEARANCE.
 A 30 INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM
 CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE
 OF THE SHOWER COMPARTMENT.
  
 C) 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36
 INCHES WIDE AND 60 INCHES DEEP MINIMUM CLEAR INSIDE
 DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING SIDES.
 A 36 INCH WIDE MINIMUM ENTRY SHALL BE PROVIDED AT ONE
 END OF THE LONG SIDE OF THE COMPARTMENT.
  
 3. PLEASE SHOW THE DIMENSIONS ON THE REQUIRED CLEAR
 FLOOR SPACE AT THE WATER CLOSET'S, LAVATORY'S, WATER
 FOUNTAIN'S AND KITCHEN SINK. PER WPB AMEND TO FBC
 107.2.1
  
 4. PLEASE SHOW DIMENSIONS FOR HEIGHT OF THE TOILET
 PAPER DISPENSER THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. PER
 FBC ACC 604.7
  
 5. PROVIDE DETAILS FOR GRAB BARS IN THE SHOWER FOR THE
 DESIGN TYPE SHOWN ON PLAN. FBC ACC
 A) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
 OR
 B) 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES MAXIMUM
 FROM ADJACENT WALLS.
 OR
 C) 608.3.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS.
  
 6. SHOW THE DIMENSION FOR THE SHOWER SPRAY UNITS. PER
 FBC ACC 608.5.1 OR 608.5.2 OR 608.5.3
  
 7. DUE TO THE FACT THAT THERE IS AN OVEN IN THE KITCHEN
 AND COOKING COULD BE DONE A GREASE INTERCEPTOR WILL BE
 REQUIRED ON THE KITCHEN SINK. PER FBC PL 1003.3.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-08 Cont ID  
Sent By llouie Date 2018-05-08 Time   Rev Time 0.00
Received By llouie Date 2018-05-04 Time   Sent To  
Notes
2018-05-08 15:27:51ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) LANDSCAPE PERMIT REVIEW AND APPROVAL REQUIRED PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.).

Review Stop Z ZONING
Rev No 2 Status F Date 2018-02-16 Cont ID  
Sent By llouie Date 2018-02-16 Time   Rev Time 0.00
Received By llouie Date 2018-02-16 Time   Sent To  
Notes
2018-02-16 16:38:27** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE ARCHITECT'S RESPONSE TO COMMENT #5 FROM
 12/13/17 STATES THAT THE USE ON THE PROPERTY IS
 "WAREHOUSES FOR FAMILIES AND SMALL BUSINESSES," WHICH
 ALSO HAS AN OFFICE COMPONENT; HOWEVER, IF THIS IS THE
 CASE, THE OFFICE COMPONENT SHOULD BE ACCESSORY TO THE
 PRIMARY USE (WAREHOUSES FOR FAMILIES AND SMALL
 BUSINESSES) AND THEREFORE, THE OFFICE COMPONENT OF THE
 BUILDING SHOULD BE SIGNIFICANTLY LESS THAN 50% OF THE
 PROPOSED WAREHOUSE SPACE. THE PLANS DO NOT INDICATE
 THAT THE OFFICE COMPONENT OF THE BUILDING IS ACCESSORY
 TO THE PRIMARY USE. PLEASE ADDRESS.
  
 2.) WHEEL STOPS REQUIRED FOR ALL PARKING STALLS. PLEASE
 ILLUSTRATE.
  
 3.) HOW WIDE IS THE DRIVE AISLE? PLEASE SHOW DIMENSION
 IN THE SITE PLAN.
  
 4.) PROVIDE A PARKING STALL STRIPING DETAIL THAT IS
 CONSISTENT WITH THE REQUIREMENTS OF SECTION 94-485 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 5.) WHAT IS THE DISTANCE FROM THE ROLL UP DOORS TO THE
 NEAREST PARKING STALL(S)?
  
 6.) WHERE IS THE LOADING ZONE? PLEASE SHOW.
  
 7.) ALTHOUGH THE CHANGE IN USE (AUTO SALES TO
 WAREHOUSES FOR FAMILIES AND SMALL BUSINESSES) DOES NOT
 REQUIRE THE PROPOSED USE TO MEET THE PARKING
 REQUIREMENT ON SITE, IT WOULD BE HELPFUL TO PROVIDE THE
 PARKING INFORMATION IN THE SITE PLAN.
  
 8.) THE VALUE OF THE CONSTRUCTION ($300,000) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($420,292) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: I
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-13 Cont ID  
Sent By LL Date 2017-12-13 Time   Rev Time  
Received By llouie Date 2017-12-13 Time   Sent To  
Notes
2017-12-13 16:54:51** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SURVEY OF THE PROPERTY IS REQUIRED.
  
 2.) DEMOLITION KEY NOTES INCOMPLETE ON SHEET AD1.1.
 PLEASE ADDRESS (WHAT IS NOTE 12 AND 13?).
  
 3.) ELEVATION KEY NOTE 6 AND 7 MISSING ON SHEETS A-2.01
 THROUGH A-2.04. PLEASE ADDRESS.
  
 4.) WHAT IS THE PROPOSED USE OF THE PROPERTY? PLANS
 INDICATE OFFICE USE; HOWEVER, MORE INFORMATION ON THE
 TYPE OF OFFICE USE IS REQUIRED. PER THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), CERTAIN TYPE OF OFFICE
 USES ARE NOT PERMITTED IN THE INDUSTRIAL (I) ZONING
 DISTRICT. [ZLDR S.94-272]
  
 5.) PLEASE PROVIDE A SITE PLAN SHOWING INGRESS/EGRESS
 POINT, PARKING FOR THE USE, ETC. IT IS UNCLEAR HOW THE
 SITE WILL ACCOMMODATE THE CHANGE IN USE.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  