Plan Review Details - Permit 17120025
Plan Review Stops For Permit 17120025
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-12-13 Cont ID  
Sent By mgonzale Date 2017-12-13 Time   Rev Time  
Received By mgonzale Date 2017-12-13 Time   Sent To Z
Notes
2017-12-13 15:07:06CALL 811 BEFORE DIGG

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-14 Cont ID  
Sent By cpuell Date 2017-12-14 Time 12:49 Rev Time 0.00
Received By cpuell Date 2017-12-01 Time 10:23 Sent To  
Notes
2017-12-04 10:23:36ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By llouie Date 2017-12-13 Time   Rev Time 0.00
Received By llouie Date 2017-12-13 Time   Sent To I
Notes
2017-12-13 16:41:32REPLACEMENT OF EXISTING DRIVE ONLY. DRIVEWAY 11 FT.
 WIDE BY 25 FT. LONG.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-07 Cont ID  
Sent By LL Date 2017-12-07 Time   Rev Time 0.00
Received By llouie Date 2017-12-06 Time 15:35 Sent To ENG
Notes
2017-12-07 10:41:56** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) HOW WIDE IS THE PROPOSED DRIVEWAY? THE ZONING CODE
 DOES NOT ALLOW FOR A DRIVEWAY WIDER THAN 20 FT. [ZLDR
 S.94-312]
  
 2.) CLEARLY SHOW SETBACK DIMENSIONS FROM THE SIDE
 PROPERTY LINE TO THE PROPOSED DRIVEWAY. PER THE
 REQUIREMENTS OF THE ZONING CODE, THE DRIVEWAY SHALL BE
 SETBACK AT LEAST 3 FT. FROM THE SIDE PROPERTY LINE.
 [ZLDR S.94-482(D)]
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  