Plan Review Details - Permit 17120018
Plan Review Stops For Permit 17120018
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 06:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-11 Cont ID  
Sent By jwitmer Date 2017-12-11 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2017-12-11 Time 07:57 Sent To  
Notes
2017-12-11 13:28:262014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120018 / PARTIAL CHANGE IN
 OCCUPANCY.
 ADD: 854 CONNISTON RD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-400-1804 / CAMILA SA
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 11/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE IN BOTH SETS OF THE ARCHITECTURAL PLANS
 THE PLANS ARE SIGNED AND DATED BY THE ARCHITECT OF
 RECORD BUT NOT SEALED. PLEASE SEAL ALL PLANS BEING
 SUBMITTED TO THE CITY FOR ISSUANCE.
  
 FL ADMIN CODE 61G16.003(1) ARCHITECTS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 2) COVERSHEET- CS-101:
  
 2A) THE COVERSHEET LIST UNDER THE HEADING PROJECT
 DESCRIPTION A LEVEL III ALTERATION. PLEASE REVIEW UNDER
 THE 2014 EXISTING BUILDING CODE SEE SECTIONS AND
 CORRECT:
  
 EXIST. BLDG CODE 506.1 SCOPE. CHANGE OF OCCUPANCY
 PROVISIONS APPLY WHERE THE ACTIVITY IS CLASSIFIED AS A
 CHANGE OF OCCUPANCY AS DEFINED IN CHAPTER 2. CHANGE OF
 OCCUPANCY. A CHANGE IN THE PURPOSE OR LEVEL OF ACTIVITY
 WITHIN A BUILDING THAT INVOLVES A CHANGE IN APPLICATION
 OF THE REQUIREMENTS OF THIS CODE.
  
 EXIST. BLDG. CODE 506.2 APPLICATION. CHANGES OF
 OCCUPANCY SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTER 10.
  
 EXIST. BLDG CODE 1001.3.1. PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 1012 SHALL APPLY.
  
 2B) THE COVERSHEET DOES NOT PROVIDE ENOUGH DETAIL AS
 HOW THE R3 UNIT IS TO BE USED. IF THIS IS UNIT IS A
 SINGLE DWELLING UNIT OR TO BE CONSIDERED TWO SLEEPING
 UNITS SIMILAR TO DORM UNITS. IF THE INTENT IS TO BE
 SIMILAR TO DORMS THEN THE SLEEPING UNITS WILLO NEED TO
 BE FIRE RATED , IF THIS IS A SINGLE DWELLING UNIT THEN
 THEY DO NOT.
 DIFINITION: SLEEPING UNIT. A ROOM OR SPACE IN WHICH
 PEOPLE SLEEP, WHICH CAN ALSO INCLUDE PERMANENT
 PROVISIONS FOR LIVING, EATING, AND EITHER SANITATION OR
 KITCHEN FACILITIES BUT NOT BOTH. SUCH ROOMS AND SPACES
 THAT ARE ALSO PART OF A DWELLING UNIT ARE NOT SLEEPING
 UNITS.
  
 DIFINITION: DORMITORY. A SPACE IN A BUILDING WHERE
 GROUP SLEEPING ACCOMMODATIONS ARE PROVIDED IN ONE ROOM,
 OR IN A SERIES OF CLOSELY ASSOCIATED ROOMS, FOR PERSONS
 NOT MEMBERS OF THE SAME FAMILY GROUP, UNDER JOINT
 OCCUPANCY AND SINGLE MANAGEMENT, AS IN COLLEGE
 DORMITORIES OR FRATERNITY HOUSES.
  
 PLEASE PROVIDE A BETTER DISCRIPTION OF THE OCCUPANCY
 USAGE TO SEE IF UNDER THE 2014 FBC-B SEPARATION WALLS
 WOULD BE REQUIRED BETWEEN SLEEPING UNITS, FBC-B 420.2.
  
 2C) THE 2ND FLOOR OF THE R3 OCCUPANCY IS ALSO TO BE
 CONSIDERED A MIXED OCCUPANCY SINCE THE GYM IS OVER 10 %
 OF THE FLOOR PLATE. THE INSIDE DIMENSIONS OF THE
 BUILDING GIVE 2026 SQ. FEET. THE GYM IS 435.76 SQ. FT.
 OR 21% OF THE FLOOR PLATE, PLEASE PROVIDE COMPLIANCE:
  
 FBC-B 508.4.1 OCCUPANCY CLASSIFICATION. SEPARATED
 OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN
 ACCORDANCE WITH SECTION 302.1. EACH SEPARATED SPACE
 SHALL COMPLY WITH THIS CODE BASED ON THE OCCUPANCY
 CLASSIFICATION OF THAT PORTION OF THE BUILDING. TABLE
 508.4.
  
 3) SHEET A-103:
 3A) SHEET A-103 INDICATES NEW CASEMENT WINDOW MARKED
 WINDOW TYPE A. IN THE WINDOW SCHEDULE AND ON THE PLANS
 IT IS DEPICTED AS A CASEMENT WINDOW. THE WINDOW
 SCHEDULE INDICATES A MIAMI-DADE NOA 16-0714.23 WHICH
 HAS BEEN SUPERCEDED BY 17-0614.20. BOTH NOAS ARE FOR A
 PGT MODEL AW-740 A AWNING WINDOW NOT A CASEMENT WINDOW.
 PLEASE CORRECT PLANS. 107.2.1.3 ADDITIONAL INFORMATION
 WILL BE REQUIRED. SUBMITTED PRODUCT APPROVAL IS FOR
 AWNING TYPE WINDOW.
  
 3B) SHEET A-103 ALSO HAS THE DOOR SCHEDULE, THE NEW
 EXTERIOR DOOR WITH SIDELITE IS IDENTIFIED BY THE
 MIAMI-DADE NOA 17-0504.01. PLEASE IDENTIFY THE SIZE OF
 THE SIDELITE IN THE SUBMITTED PRODUCT APPROVAL. . THE
 PLANS INDICATE THE DOOR IS A OUTSWING DOOR AND THE DOOR
 ITSELF IS 3 FEET IN WIDTH, THE OVERALL OPENING IS 6
 FEET WIDE, HOW WIDE IS THE REMAINDER OF THE SIDE LITE
 AND FRAME. PLEASE REVIEW THE PRESSURES FOR UNREINFORCED
 SIDE LITES SHEET 2 OF 15 AND TABLE 3. PLEASE IDENTIFY
 ALL OF THE COMPONENTS OF THE DOOR, SIDE LITE ASSEMBLY
 AND ASSCIATED PRESSURES.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 3C) THE SHEET A-103 INDICATES THE ASSUMED VASD
 PRESSURES BUT THE WIND DESIGN FOR THESE PRESSURES IS
 NOT GIVEN.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3C) 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
  
 3C) 2. RISK CATEGORY.
  
 3C)3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 3C) 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3C) 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 3D) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS
  
 3E) SHEET A-103 DETAILS 5 & 6 BOTH SHOW THE USE OF
 PAPER BACKED WIRE LATH OVER19/32NDS PLYWOOD. PLEASE ADD
 A SECONDARY WATER BARRIER REQUIRED BY 2014 FBC-B
 SECTION:
  
 2510.6 WATER-RESISTIVE BARRIERS. WATER-RESISTIVE
 BARRIERS SHALL BE INSTALLED AS REQUIRED IN SECTION
 1404.2 AND, WHERE APPLIED OVER WOOD-BASED SHEATHING,
 SHALL INCLUDE A WATER-RESISTIVE VAPOR-PERMEABLE BARRIER
 WITH A PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF
 GRADE D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 3E) SHEET A-103 THE VENT SIZE FOR EGRESS WINDOWS IS
 STATED IN QUOTING THE CODE, NOT SHOWING COMPLIANCE.
  
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3: W.P.B.
 ADMINISTRATIVE CODE. SUCH INFORMATION SHALL BE SPECIFIC
 TO THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET .
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS.
 THE MINIMUM NET CLEAR OPENING HEIGHT DIMENSION SHALL BE
 24 INCHES (610 MM). THE MINIMUM NET CLEAR OPENING WIDTH
 DIMENSION SHALL BE 20 INCHES (508 MM). THE NET CLEAR
 OPENING DIMENSIONS SHALL BE THE RESULT OF NORMAL
 OPERATION OF THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR.
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE THE
 BOTTOM OF THE CLEAR OPENING NOT GREATER THAN 44 INCHES
 (1118 MM) MEASURED FROM THE FLOOR.
  
 4) SHEET A-101 THE BATHROOMS INDICATE TO INSTALL GREEN
 BOARD ON CMU WALLS. PLEASE REVIEW THE 2014
 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. GLASS MAT WATER-RESISTANT GYPSUM
 BACKING PANELS, DISCRETE NONASBESTOS FIBER-CEMENT
 INTERIOR SUBSTRATE SHEETS OR NONASBESTOS FIBER-MAT
 REINFORCED CEMENTITIOUS BACKER UNITS IN COMPLIANCE WITH
 ASTM C 1178, C 1288 OR C 1325 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS SHALL BE
 USED AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS
 AND WALL AND CEILING PANELS IN SHOWER AREAS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A
 BASE FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840 AND
 MANUFACTURER RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD
 IS PERMITTED UNDER TILE OR WALL PANELS IN OTHER WALL
 AND CEILING AREAS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840.
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-05 Cont ID  
Sent By jpearson Date 2018-03-05 Time 15:01 Rev Time 0.00
Received By jpearson Date 2018-03-05 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By jpearson Date 2017-12-14 Time 15:48 Rev Time 0.00
Received By jpearson Date 2017-12-14 Time 15:48 Sent To  
Notes
2017-12-14 15:47:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL DOES NOT INDICATE ALL REQUIRED AFCI CIRCUITS.
 PER CODE: "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE
 BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL
 HAVE AFCI PROTECTION." PROVIDE CORRECTION. NEC 210.12
 2. PLAN SHOWS STANDARD RECESS LIGHTS IN CLOSETS. PER
 CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC
 410.16
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 4. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD BE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13
 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By pleduc Date 2018-02-22 Time   Rev Time 0.00
Received By pleduc Date 2018-02-22 Time 12:56 Sent To  
Notes
2018-02-22 13:10:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS AN INFORMATIONAL
 PROVISO:
  
 THIS INFORMATIONAL PROVISO COMMENTS WILL BE VERIFIED
 AND CONFIRMED AT THE TIME OF FIRE INSPECTION. FAILURE
 TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN A
 FAILED FIRE INSPECTION.
  
  
 1) NOT WITHSTANDING THE COMMENT REGARDING THE REVISION
 NOTE REGARDING THE SCOPE OF PERMIT ON SHEET E 1, ALL OF
 THE SYSTEMS NOTED, INCLUDING FIRE ALARM, ARE CONDITIONS
 OF OCCUPANCY.
  
  
  
 2) THE FIRE ALARM SHALL BE EXTENDED INTO THE APARTMENT
 AND PROVIDE CODE COMPLIANT DECIBEL LEVELS AT THE
 PILLOW.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-06 Cont ID  
Sent By pleduc Date 2017-12-06 Time   Rev Time 0.00
Received By pleduc Date 2017-12-06 Time 10:02 Sent To  
Notes
2017-12-06 12:18:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS AN INFORMATIONAL
 PROVISO:
  
 THIS INFORMATIONAL PROVISO COMMENTS WILL BE VERIFIED
 AND CONFIRMED AT THE TIME OF FIRE INSPECTION. FAILURE
 TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN A
 FAILED FIRE INSPECTION.
  
  
  
 1) THE FIRE ALARM SHALL BE EXTENDED INTO THE APARTMENT
 AND PROVIDE CODE COMPLIANT DECIBEL LEVELS AT THE
 PILLOW.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-21 Cont ID  
Sent By   Date 2018-03-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-16 Time 15:04 Sent To  
Notes
2018-03-19 15:04:22IMPACT FEES ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-08 Cont ID  
Sent By lmarchan Date 2018-03-08 Time 14:14 Rev Time 0.00
Received By lmarchan Date 2018-02-16 Time 15:22 Sent To  
Notes
2018-02-20 15:23:06B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-03 Cont ID  
Sent By eschneid Date 2018-01-03 Time 17:46 Rev Time 0.00
Received By eschneid Date 2017-12-01 Time 14:14 Sent To  
Notes
2017-12-04 14:15:06B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-03-21 Cont ID  
Sent By jwitmer Date 2018-03-21 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2018-03-21 Time 08:09 Sent To  
Notes
2018-03-21 08:17:46PALM BEACH COUNTY IMPACT FEE OFFICE
 RECEIPT NUMBER 2018-0313-215
 TRACKING NUMBER MU-2018-008129-0000
 FEES PAID: $2,562.21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-03-08 Cont ID  
Sent By lmarchan Date 2018-03-08 Time 14:14 Rev Time 0.00
Received By lmarchan Date 2018-03-08 Time 14:14 Sent To  
Notes
2018-03-08 14:14:54PER JWITMER SEE PREVIOUS DENIAL FOR COMMENTS

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-12-11 Cont ID  
Sent By jwitmer Date 2017-12-11 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2017-12-11 Time 07:57 Sent To  
Notes
2017-12-11 13:29:02BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 13:39 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 12:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By ccole Date 2017-12-14 Time 07:45 Rev Time 0.00
Received By ccole Date 2017-12-13 Time 17:39 Sent To  
Notes
2017-12-14 08:09:051ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17120018
 12/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED APARTMENT IS DEFINED AS A CHANGE OF
 OCCUPANCY PER SECTION 202 FBC-14 EXISTING BUILDING,
 HOWEVER BASED ON THE BUILDING REVIEW COMMENTS, IT
 APPEARS THAT THE OCCUPANCY CLASSIFICATION OF THE NEW
 APARTMENT, WHETHER R2 OR R3 IS STILL IN QUESTION. REFER
 TO SECTIONS C101.4.4 AND R101.4.4 FBC-14 ENERGY
 CONSERVATION AND PROVIDE AN ENERGY COMPLIANCE SUBMITTAL
 IN ACCORDANCE WITH EITHER SECTION C101.5.1 OR R101.5.1.
 PLEASE NOTE THAT THE SUBMITTED C402-1014 FORM SHALL NOT
 BE USED TO SHOW COMPLIANCE FOR A COMMERCIAL SPACE
 CHANGED TO AN R3 OR R2 OCCUPANCY.
  
 2) BUILDING REVIEW COMMENTS 2B AND 2C ARE INDICATING
 THE THAT FIRE-RATED SEPARATION WALLS MAY BE REQUIRED
 BETWEEN THE BEDROOMS AND TO SEPARATE THE GYM. PLEASE
 NOTE THAT FIRE DAMPERS MAY BE REQUIRED FOR DUCTS
 PENETRATING THESE WALLS PENDING RESOLUTION OF THIS
 ISSUE.
  
 3) REFER TO TABLE 403.3 IN REGARD TO O/A CALCULATIONS
 FOR THE GYM. PENDING RESOLUTION OF THE OCCUPANCY
 CLASSIFICATION, ADDITIONAL O/A MAY BE REQUIRED FOR THE
 GYM. THREE OPTIONS ARE LISTED IN THE TABLE UNDER SPORTS
 AND AMUSEMENT. PLEASE CHOOSE WHICH OPTION BEST SUITS
 THE USE OF THE ROOM.
  
 4) EXHAUST VENTILATION IS REQUIRED FOR THE KITCHEN AT A
 RATE OF 100 CFMS INTERMITTENT OR 25 CFMS CONTINUOUS-
 SEE 403.3 FBC-14 MECHANICAL OR TABLE M1507.4 FBC-14
 RESIDENTIAL AND INDICATE COMPLIANCE. CLARIFY IF A RANGE
 HOOD WILL BE INSTALLED OVER THE RANGE AND SUBMIT
 SPECIFICATIONS FOR BOTH THE RANGE AND THE HOOD.
  
 5) SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE DRYER
 AND INDICCATE THE RATE OF MAKEUP AIR REQUIRED AND HOW
 IT IS BEING PROVIDED.
  
 THE MECHANICAL REVIEW IS STOPPED AT THIS TIME PENDING
 PLAN REVISIONS TO CLARIFY THE OCCUPANCY CLASSIFICATION
 OF THE NEW APARTMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-22 Cont ID  
Sent By gjohnson Date 2017-12-22 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2017-12-22 Time 15:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-02 Cont ID  
Sent By eschneid Date 2018-03-02 Time 16:12 Rev Time 0.50
Received By eschneid Date 2018-03-02 Time 16:12 Sent To  
Notes
2018-03-02 16:12:55NO OVERNIGHT GUESTS PERMITTED.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-01-03 Cont ID  
Sent By ES Date 2018-01-03 Time 17:44 Rev Time 0.50
Received By eschneid Date 2017-12-28 Time 11:31 Sent To  
Notes
2018-01-03 17:46:24FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) PLEASE EXPLAIN WHO WILL BE LIVING IN THE NEW
 APARTMENT.
  
 2) PROVIDE SECTION DRAWINGS TO VERIFY THAT THE NEW
 ROOFTOP AC UNIT WILL BE SCREENED FROM OFF-SITE VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]