Plan Review Details - Permit 17111177
Plan Review Stops For Permit 17111177
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By jwitmer Date 2018-02-07 Time 16:49 Rev Time 0.00
Received By jwitmer Date 2018-02-07 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-08 Cont ID  
Sent By jwitmer Date 2017-12-08 Time 15:30 Rev Time 0.00
Received By jwitmer Date 2017-12-08 Time 15:02 Sent To  
Notes
2017-12-08 15:30:022014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17111177
 ADD: 330 CLEMATIS ST. SUITE: 110
 CONT: NEW VISION CONSTRUCTION & DESIGN
 TEL: 954-709-6360
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 08/2017
 ACTION: DENIED
  
 1) SHEET A1.0 THE FLOOR PLAN HAS 61 SEATS THAT ARE
 ACCOUNTED FOR, THE PLAN IS NOT CLEAR TO THE RIGHT SIDE
 OF THE SHEET WHAT APPEARS AS SEATS AND TABLES BUT THIS
 AREA MAY BRING THE SEATING LOAD TO OVER 80 CLIENTS. 80
 X 0.05 = 4 ACCESSIBLE SEATS REQUIRED. 2014
 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 1A) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1B) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 1B)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2) THE A1.0 SHEET SHOWS THE REMOVAL AND INDICATES NEW
 MECHANICAL EQUIPMENT. THERE IS NO MECHANICAL SHEET IN
 THIS SET OF PLANS. THIS REVIEW CYCLE A THOROUGH REVIEW
 COULD NOT BE COMPLETED AND ADDITIONAL AND OR NEW
 COMMENTS MAY OCCUR ON SUBSEQUENT REVIEWS.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-23 Cont ID  
Sent By jpearson Date 2018-02-23 Time 14:36 Rev Time 0.00
Received By jpearson Date 2018-02-23 Time 14:36 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By jpearson Date 2017-12-14 Time 10:05 Rev Time 0.00
Received By jpearson Date 2017-12-14 Time 08:25 Sent To  
Notes
2017-12-14 10:05:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO CONFIRM THE
 ADDITIONAL FIXTURES DOES NOT EXCEED THE ALLOWABLE
 WATTAGE FOR THE SPACE. FBC EC 405.5.2
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 FOR NEW LIGHTING INSTALLED STIPULATED IN THE FBC ENERGY
 CODE. FBC EC 405.2.2, 405.2.2.2
 3. PROVIDE CORRECT ADDRESS ON PLANS, THE SUITE NUMBER
 IS NOT LISTED. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By pleduc Date 2018-02-07 Time   Rev Time 0.00
Received By pleduc Date 2018-02-06 Time 16:27 Sent To  
Notes
2018-02-07 08:34:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL HOODS & FIRE SUPPRESSION SYSTEMS SHALL HAVE
 CURRENT CLEANING AND CERTIFICATION TAGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-04 Cont ID  
Sent By pleduc Date 2017-12-04 Time   Rev Time 0.00
Received By pleduc Date 2017-12-04 Time 11:23 Sent To  
Notes
2017-12-04 15:52:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED PROJECT SHALL COMPLY WITH THE 2014
 EDITION OF THE FLORIDA FIRE PREVENTION CODE AND ALL
 APPLICABLE CHAPTERS INCLUDING CHAPTER 7, MEANS OF
 EGRESS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 14:26 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 14:26 Sent To  
Notes
2018-01-18 14:26:49GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-01 Time 12:39 Sent To  
Notes
2018-02-02 12:39:17B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 14:43 Rev Time 0.00
Received By gjohnson Date 2017-11-30 Time 11:00 Sent To  
Notes
2017-12-01 11:00:33B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-12-08 Cont ID  
Sent By jwitmer Date 2017-12-08 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2017-12-08 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By ccole Date 2018-02-22 Time 12:11 Rev Time 0.00
Received By ccole Date 2018-02-22 Time 12:07 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-12-12 Cont ID  
Sent By ccole Date 2017-12-12 Time 10:55 Rev Time 0.00
Received By ccole Date 2017-12-12 Time 10:50 Sent To  
Notes
2017-12-12 11:15:141ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, FUEL
 GAS CODES 2014.
 PERMIT #17111177
 12/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GRIDDLE- SECTION 623.1 FBC-14 FUEL GAS.
  
 2) PLACE A NOTE ON THE PLAN INDICATING THAT ANY
 ALTERATIONS TO THE EXISTING KITCHEN EXHAUST HOOD AND
 FIRE SUPPRESSION SYSTEM WILL BE DONE UNDER SEPARATE
 PERMIT.
  
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-02-06 Cont ID  
Sent By gjohnson Date 2018-02-06 Time 11:17 Rev Time 0.00
Received By gjohnson Date 2018-02-06 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 14:27 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 14:27 Sent To  
Notes
2018-01-18 14:43:301ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE COVER SHEET IS LISTING THE WRONG FBC IT SHALL BE
 2014 5TH EDITION P[LEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE EXISTING DISHWASHING ON A1.0 DOES NOT MATCH AREA
 ON D1.0 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. A BACKFLOW DEVISE IS REQUIRED ON THE WATER FILTER
 AND SODA MACHINE. PER FBC PL 608.3, 608.16.1
  
 4. SHOW WATER PIPING FOR SODA MACHINE. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 5. HAND SINK SHOWN ON D1.0 NEXT TO NEW COFFEE MACHINE
 LOCATION IS NOT SHOWN ON A1.0 OR P1.0 PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 6. THE SINK NEXT TO WIC NOT SHOWN ON D1.0 IS THIS A NEW
 SINK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. A SEPARATE PERMIT WILL BE REQUIRED FOR ANY GAS WORK
 CAPPING OF EXISTING APPLIANCES AND INSTALLING NEW ONES.
 PROVIDE NOTE ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  