Plan Review Details - Permit 17111031
Plan Review Stops For Permit 17111031
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2017-12-18 Cont ID  
Sent By cthroop Date 2017-12-18 Time 12:37 Rev Time 0.00
Received By cthroop Date 2017-12-18 Time 12:35 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-05-30 Cont ID  
Sent By jleahy Date 2018-05-30 Time 12:36 Rev Time 0.00
Received By jleahy Date 2018-05-30 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-05-01 Cont ID  
Sent By jleahy Date 2018-05-01 Time 17:06 Rev Time 0.00
Received By jleahy Date 2018-05-01 Time 17:06 Sent To  
Notes
2018-05-01 17:24:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLAN STATES LANDSCAPE LIGHTING, PLAN IS SHOWING POOL
 LIGHTING?
  
 PANEL SCHEDULE SHOWS CIRCUIT #7 AS LANDSCAPE LIGHTING?
 THIS CIRCUIT FEEDS THE POOL LIGHTS.
  
 FBC 454.1.9.8.4
 IF NIGHT OPERATION IS PROPOSED, 6 FOOTCANDLES (60 LUX)
 OF LIGHT SHALL BE PROVIDED ON THE POOL DECK AND THE
 WATER FEATURE AREA.
 LIGHTING THAT MAY BE EXPOSED TO THE FEATURE POOL WATER
 SHALL NOT EXCEED 15 VOLTS, SHALL BE INSTALLED IN
 ACCORDANCE WITH
 MANUFACTURER?S SPECIFICATIONS AND BE APPROVED FOR SUCH
 USE BY UL OR NSF.
  
 SEE 64E-9.006 (C) (3)
 3. UNDERWATER LIGHTING ? UNDERWATER LIGHTING SHALL
 UTILIZE TRANSFORMERS AND LOW VOLTAGE CIRCUITS WITH EACH
 UNDERWATER LIGHT BEING GROUNDED. THE MAXIMUM VOLTAGE
 FOR EACH LIGHT SHALL BE 15 VOLTS AND THE MAXIMUM
 INCANDESCENT LAMP SIZE SHALL BE 300 WATTS. THE LOCATION
 OF THE UNDERWATER LIGHTS SHALL BE SUCH THAT THE
 UNDERWATER ILLUMINATION IS AS UNIFORM AS POSSIBLE AND
 SHALL NOT BE LESS THAN 18 INCHES BELOW THE NORMAL
 OPERATING WATER LEVEL DETERMINED BY THE CENTERLINE OF
 THE SKIMMER OR TOP LIP OF THE GUTTER. ALL UNDERWATER
 LIGHTS WHICH DEPEND UPON SUBMERSION FOR SAFE OPERATION
 SHALL HAVE PROTECTION FROM OVERHEATING WHEN NOT
 SUBMERGED. UNDERWATER LIGHTING REQUIREMENTS CAN BE
 WAIVED WHEN THE OVERHEAD LIGHTING PROVIDES AT LEAST
 15 FOOT CANDLES OF ILLUMINATION AT THE POOL WATER
 SURFACE AND POOL WET DECK SURFACE. ALTERNATIVE LIGHTING
 SYSTEMS WHICH USE 15 VOLTS OR LESS, OR USE NO
 ELECTRICITY IN THE POOL OR ON THE POOL DECK, SUCH AS
 LED, (LIGHT
 EMITTING DIODE) OR FIBER OPTIC SYSTEMS, MAY BE UTILIZED
 IF THE APPLICANT DEMONSTRATES TO REASONABLE CERTAINTY
 THAT THE SYSTEM DEVELOPMENT HAS ADVANCED TO THE POINT
 WHERE THE DEPARTMENT IS CONVINCED THAT THE POOL
 ILLUMINATION IS EQUAL TO THE REQUIREMENTS IN
 SUBPARAGRAPH 1. AND 2. ABOVE.
  
 FIXTURES L-4 ARE SHOWN TO BE 120 VOLT, SEE FBC ABOVE
  
 NEED CUT SHEETS FOR FIXTURE AND NICHE
  
 PLEASE SUBMIT A SHEET SHOWING THE MOUNTING IN THE WALL
 ABOVE OR BELOW THE WATER.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-03-19 Cont ID  
Sent By jleahy Date 2018-03-19 Time 14:46 Rev Time 0.00
Received By jleahy Date 2018-03-19 Time 14:46 Sent To Z
Notes
2018-03-19 14:52:16FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL WORK IS NOT CLEAR ON WHAT IS BEING DONE.
  
 SUBMIT AN ELECTRICAL PLAN SHOWING EXACTLLY WHAT IS
 BEING DONE.
  
 FOR LIGHTING OUTDOORS SEE BELOW
  
 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED
 BY AN ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
 FBC CE 405.2.4
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-12-15 Cont ID  
Sent By jleahy Date 2017-12-15 Time 15:05 Rev Time 0.00
Received By jleahy Date 2017-12-15 Time 15:05 Sent To B
Notes
2017-12-15 15:07:04NO ELECTRICAL WORK SHOWN BUT BONDING PER 680 WILL BE
 REQUIRED.
  
 JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-30 Cont ID  
Sent By jleahy Date 2018-05-30 Time 12:37 Rev Time 0.00
Received By jleahy Date 2018-05-11 Time 14:56 Sent To  
Notes
2018-05-14 14:57:00RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-01 Cont ID  
Sent By jleahy Date 2018-05-01 Time 17:24 Rev Time 0.00
Received By jleahy Date 2018-04-23 Time 14:04 Sent To  
Notes
2018-04-24 14:05:03RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-13 Cont ID  
Sent By cpuell Date 2018-04-13 Time 16:15 Rev Time 0.00
Received By cpuell Date 2018-02-20 Time 14:42 Sent To  
Notes
2018-02-21 14:43:00RESUB ROUTED TO AHANSEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-19 Cont ID  
Sent By cpuell Date 2017-12-19 Time 14:10 Rev Time 0.00
Received By cpuell Date 2017-12-07 Time 14:00 Sent To  
Notes
2017-12-11 14:01:06ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2018-04-30 Cont ID  
Sent By Alex H Date 2018-04-30 Time   Rev Time 0.00
Received By ahansen Date 2018-04-30 Time 15:56 Sent To E
Notes
2018-05-01 15:58:46APPROVED BY AH ON 4/30/18. SENT TO JAKE LEAHY ON 5/1/18
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-13 Cont ID  
Sent By   Date 2018-04-13 Time   Rev Time 0.00
Received By ahansen Date 2018-02-22 Time 16:42 Sent To I
Notes
2018-04-13 14:40:58THE BUILDING PERMIT APPLICATION NEEDS TO INCLUDE AND BE
 CONSISTENT WITH THE SITE PLAN THAT WAS APPROVED ON
 4/13/18 THROUGH THE MINOR PD AMENDMENT PROCESS.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ahansen Date 2017-12-13 Time 14:03 Sent To E
Notes
2017-12-13 15:42:29SHEET LC-2 OF THE SUBMITTAL INCLUDES A PARKING PAVING
 (AND STRIPING) DETAIL WHICH DOES NOT COMPLY WITH THE
 CITY'S PARKING STRIPING STANDARDS.
 SHEET LC-4 INCLUDES A BIKE RACK DETAIL BUT IS MISSING A
 DETAIL OF THE BIKE PAD AREA WHERE THE BIKE RACKS WILL
 BE LOCATED.
 THE APPROVAL LETTER FOR THE BELLA VITA MINOR SITE PLAN
 AMENDMENT ISSUED ON OCTOBER 26, 2017 INCLUDES THE
 FOLLOWING CONDITION OF APPROVAL:
 "5. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT
 FOR THE PROJECT, THE LANDSCAPE PLAN, SITE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS SHALL BE REVISED
 TO RELOCATE THE CURBS TO THE POSITION OF THE WHEEL
 STOPS AND PROVIDE A LANDSCAPED OVERHANG WHERE POSSIBLE
 WITHIN THE PARKING AREAS TO PROVIDE MORE PERVIOUS
 LANDSCAPE AREA. THE DESIGN SHALL FOLLOW THE TYPICAL
 PARKING STALL LAYOUT AS SHOWN ON THE APPROVED PLANS. A
 MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE REQUIRED TO
 REFLECT ANY REVISIONS TO THE PLANS."
 SINCE NO REVISED SITE PLAN, LANDSCAPE PLAN, AND
 ENGINEERING PAVING AND DRAINAGE PLANS CONSISTENT WITH
 THE ABOVE CONDITION HAVE BEEN SUBMITTED, THE BUILDING
 PLANS INCLUDED IN THIS PERMIT CANNOT BE APPROVED.
  