Plan Review Details - Permit 17110986
Plan Review Stops For Permit 17110986
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By jleahy Date 2018-06-27 Time 10:12 Rev Time 0.00
Received By jleahy Date 2018-06-27 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-16 Cont ID  
Sent By jleahy Date 2018-04-16 Time 11:13 Rev Time 0.00
Received By jleahy Date 2018-04-16 Time 11:12 Sent To  
Notes
2018-04-16 11:31:05FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CUT SHEETS NOT SUBMITTED FOR WALL PACKS OR WHAT EVER IS
 INSTALLED ON BUILDING.
  
 LIGHTING CONTROL NOT SHOWN ON PLANS
  
 ORIGINAL PLANS SHOW TWO (2) PARKING LOT FIXTURES AND
 ZERO (0) ON THE BUILDING
 NEW PLAN SHOWS SEVEN (7) PARKING LOT FIXTURES, AND
 THREE OR FOUR WALL PACKS ON BUILDING.
 PLEASE INCLUDE THE VALUE FOR THESE FIXTURES AND WORK.
  
 IF VALUE IS NOT INCLUDED WITH THE RESUBMITTAL THIS NEXT
 TIME YOU WILL BE ACCESSED A PENALTY FOR EXCESSIVE PLAN
 REVIEW FOR SAME ITEM.
  
 CGC IS NOT ALLOWED TO PULL A PERMIT FOR ELECTRICAL
 WORK!!!!!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-12 Cont ID  
Sent By jleahy Date 2017-12-12 Time 10:18 Rev Time 0.00
Received By jleahy Date 2017-12-12 Time 10:18 Sent To  
Notes
2017-12-12 10:25:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEEDS ELECTRICAL CONTRACTOR TO PULL PERMIT.
  
 ORIGINAL PLAN SHOWS ONLY TWO POLE LIGHTS YOUR PLAN
 SHOWS 7, PLUS 4 FIXTURES ON BUILDING.
  
 SUBMIT PLAN SHOWING THE BRANCH CIRCUIT NUMBER AND SIZE
 FOR THESE FIXTURES.
  
 NEED TO SUBMIT CUTSHEETS FOR THE FIXTURES AND POLE
 LIGHTS, INCLUDING THE WIND LOADS FOR THE POLE LIGHTS.
  
 PLANS WILL NEED TO SIGNED AND SEALED BY ENGINEER OF
 RECORD.
  
 VALUE COULD NOT HAVE BEEN INCLUDED FOR THE FIXTURES IF
 THEY ARE NOT SHOWN ON ORIGINAL PLANS, PLEASE INCLUDE
 THE VALUE FOR THE ADDITIONAL WORK SHOWN ON PLANS.
  
 LIGHTING CONTROL WILL BE REVIEW PER FBC ENERGY
 CONSERVATION CODE 2014

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-27 Cont ID  
Sent By jleahy Date 2018-06-27 Time 10:13 Rev Time 0.00
Received By jleahy Date 2018-06-27 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-16 Cont ID  
Sent By jleahy Date 2018-04-16 Time 11:31 Rev Time 0.00
Received By jleahy Date 2018-04-10 Time 10:32 Sent To  
Notes
2018-04-11 10:32:47RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-12-12 Cont ID  
Sent By jleahy Date 2017-12-12 Time 10:25 Rev Time 0.00
Received By jleahy Date 2017-11-27 Time 13:13 Sent To  
Notes
2017-11-28 13:13:17ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-12-08 Time   Rev Time 0.00
Received By ajones Date 2017-11-30 Time 14:42 Sent To E
Notes
2017-12-08 15:50:49ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE GLARE
 AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE AWAY
 FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES, OR PUBLIC THOROUGHFARES. ILLUMINATION OF
 SIGNS SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF
 ARTICLE XIII OF THIS CHAPTER
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]