Plan Review Details - Permit 17110874
Plan Review Stops For Permit 17110874
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-09-19 Cont ID  
Sent By shill Date 2018-09-19 Time 12:48 Rev Time 0.00
Received By shill Date 2018-09-19 Time 12:48 Sent To  
Notes
2018-09-19 12:49:39****PROVISOS****
 REVISED 10/15/19 (ITEM D)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 C) PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 D) VALET DROP OFF TO COMPLY WITH FBC ACCESSIBILITY 503.
  
 E) A DETAIL FOR HORIZONTAL SHAFT WAS PROVIDED, BUT IT
 SHOWS A SHAFT ON TWO SIDES SUPPORTED BY SOMETHING
 UNIDENTIFIED ON TWO SIDES; ALSO THIS APPEARS TO BE
 NON-SYMMETRICAL; NOT CLEAR IF THIS WAS TESTED FROM
 INSIDE AND OUTSIDE. PLEASE PROVIDE ADDITIONAL
 INFORMATION AS TO HOW THIS WAS TESTED.
  
 F) POOL DECK, POOL UNDER A SEPARATE PERMIT.
  
 1) SHEET 049-LS-102, 058-A-104 BOTH SHOW A LINEAR POOL
 DECK DRAIN. NONE OF THE ARCHITECTURAL SHEETS SHOW THE
 ELEVATION OR CROSS SLOPES OF THE POOL DECK. THE
 STRUCTURAL SHEET 012-S-1.04 SHOWS (2) ELEVATIONS ONE AT
 T. O. SLAB AT EL= 83 FEET AND A 2ND ELEVATION AT
 ELEVATION T. O. SLAB 82 FEET. THE STRUCTURAL SHEET
 036-S-4.20 DETAIL # 4 SHOWS 2 HEIGHTS IN THE CONCRETE
 DECK. A FINISHED CONCRETE DECK AND A DROPPED STRUCTURAL
 DECK AROUND THE POOL DECK ASSUMED AT T. O. SLAB AT EL=
 82 FEET.
  
 2) SHEET 037-S-4.21 DETAIL 10 SHOWS THE SUPPORT LIFT BY
 THE EDGE OF THE POOL, BUT THIS SAME DETAIL SHOWS THE
 SIDE WALL OF THE POOL, SECONDARY POOL STRUCTURE BY POOL
 DESIGNER. THERE ARE ONLY THE 2 ELEVATIONS AROUND THE
 POOL. THE STRUCTURAL SHEET 036-S-4.20 DETAIL # 4 HAS A
 NOTE SEE ARCHITECTURAL SHEETS FOR SLOPE.
  
 3) 2014 FBC-B SECTION 454.1.3.1.2. POOL WET DECKS SHALL
 BE UNIFORMLY SLOPED AT A MINIMUM OF 2 PERCENT TO A
 MAXIMUM OF 4 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER. THE PLANS ONLY SHOW A
 LINEAR POOL DRAIN ON THE WEST SIDE OF THE POOL. PLEASE
 SHOW COMPLIANCE FOR THE OTHER 3 SIDES.
  
 4) THE ACCESSIBILITY CODE SECTION 403.3 CROSS SLOPES
 FOR WALKING SURFACES SHALL BE NOT STEEPER THAN 1:48.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED FOR BOTH
 SECTIONS OF THE CODE.
  
 5) SHEET 036-S-4.20 DETAIL # 1 AND 037-S-4.21 DETAIL #
 10 SHOWS THE POOL STRUCTURAL WALL LEVEL WITH THE
 STRUCTURAL DECK HOW WILL WATER FROM THE POOL DECK BE
 SLOPED BACK TO THE LINEAR DECK DRAIN. WATER ON THE POOL
 DECK SHALL BE SLOPED AWAY FROM THE POOL EDGE. 2014
 FBC-B SECTION 454.1.3.1.2.
  
 6) SHEET 037-S-4.21 DETAIL # 10 SHOWS A STRUCTURAL BASE
 FOR AN ADA CHAIR LIFT. THE ARCHITECTURAL SHEET
 058-A-104 SHOWS THE POSITION OF THE CHAIR LIFT AND THE
 CLEAR 48X30 INCHES PLEASE PROVIDE THE MANUFACTURES SPEC
 ON THE LIFT THE DISTANCE FROM EDGE OF THE WATER TO THE
 CENTERLINE OF THE SEAT IS 4.75 FEET. WILL THE LIFT BE
 ABLE TO LIFT A PERSON INTO THE WATER WITH A SPAN OF 6
 FEET OR MORE? 2014 FBC-ACCESSIBILITY CODE 1009.2. THE
 LOCATION OF THE STRUCTURAL STAND APPEARS CLOSER THAN
 THE ARCHITECTURAL SHEET?
  
 G) AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED
 PRIOR TO C.O.
  
 H) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
 I) PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A
 PDF VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL.
  
 J) SHORING/RESHORE ENGINEERING IS REQUIRED TO BE
 SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE
 ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED
 PRIOR TO CONCRETE POUR.
  
 K) A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS
 REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-09-11 Cont ID  
Sent By shill Date 2018-09-02 Time 11:37 Rev Time 0.00
Received By shill Date 2018-09-02 Time 11:20 Sent To  
Notes
2018-09-02 11:42:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 IT IS NOT CLEAR HOW THIS WAS ADDRESSED.
  
 A DETAIL FOR HORIZONTAL SHAFT WAS PROVIDED, BUT IT
 SHOWS A SHAFT ON TWO SIDES SUPPORTED BY SOMETHING
 UNIDENTIFIED ON TWO SIDES; ALSO THIS APPEARS TO BE
 NON-SYMMETRICAL; NOT CLEAR IF THIS WAS TESTED FROM
 INSIDE AND OUTSIDE. PLEASE PROVIDE ADDITIONAL
 INFORMATION AS TO HOW THIS WAS TESTED.
  
 DETAIL FOR STAIR WAS REVISED, BUT IT STILL SHOWS WHAT
 APPEARS TO BE A SHAFT THROUGH THE STAIR, ALTHOUGH
 LANGUAGE STATES THE STAIR WILL NOT BE PENETRATED.
  
 PLEASE SEND ADDITIONAL DETAILS VIA EMAIL. A PROVISO CAN
 BE ISSUED, AT APPLICANT'S RISK, BUT THE CONCERN IS IF
 THERE IS LIMITED SPACE, AND IF THIS IS ALREADY POURED,
 RESOLUTIONS AFTER STAIR CONSTRUCTION MAY BE DIFFICULT
 OR EXPENSIVE. THE DESIGN PARAMETERS NEED TO BE AGREED
 UPON AND UNDERSTOOD PRIOR TO A PROVISO.
  
  
  
 27. PENETRATIONS THROUGH 2 HOUR RATED STAIRWAYS
  
 A) PAGE 098-A-701 SHOWS WHAT APPEARS TO BE A 2 HOUR
 DROPPED CEILING.
  
 B) PAGE 048-LS101 AND 050-A101 BOTH SHOW STAIRWAY 3 AS
 A 2HR VERTICAL EXIT STAIRWAY. PENETRATIONS WERE FOUND
 ON PAGE 124-P-101.
  
 SEE FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 PROVISOS:
  
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 C) PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 D) VALET DROP OFF COMPLIANCE TO BE SHOWN ON SEPARATE
 PERMIT.
  
 E) POOL DECK, POOL UNDER A SEPARATE PERMIT.
  
 A) SHEET 049-LS-102, 058-A-104 BOTH SHOW A LINEAR POOL
 DECK DRAIN. NONE OF THE ARCHITECTURAL SHEETS SHOW THE
 ELEVATION OR CROSS SLOPES OF THE POOL DECK. THE
 STRUCTURAL SHEET 012-S-1.04 SHOWS (2) ELEVATIONS ONE AT
 T. O. SLAB AT EL= 83 FEET AND A 2ND ELEVATION AT
 ELEVATION T. O. SLAB 82 FEET. THE STRUCTURAL SHEET
 036-S-4.20 DETAIL # 4 SHOWS 2 HEIGHTS IN THE CONCRETE
 DECK. A FINISHED CONCRETE DECK AND A DROPPED STRUCTURAL
 DECK AROUND THE POOL DECK ASSUMED AT T. O. SLAB AT EL=
 82 FEET.
  
 B) SHEET 037-S-4.21 DETAIL 10 SHOWS THE SUPPORT LIFT BY
 THE EDGE OF THE POOL, BUT THIS SAME DETAIL SHOWS THE
 SIDE WALL OF THE POOL, SECONDARY POOL STRUCTURE BY POOL
 DESIGNER. THERE ARE ONLY THE 2 ELEVATIONS AROUND THE
 POOL. THE STRUCTURAL SHEET 036-S-4.20 DETAIL # 4 HAS A
 NOTE SEE ARCHITECTURAL SHEETS FOR SLOPE.
  
 C) 2014 FBC-B SECTION 454.1.3.1.2. POOL WET DECKS SHALL
 BE UNIFORMLY SLOPED AT A MINIMUM OF 2 PERCENT TO A
 MAXIMUM OF 4 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER. THE PLANS ONLY SHOW A
 LINEAR POOL DRAIN ON THE WEST SIDE OF THE POOL. PLEASE
 SHOW COMPLIANCE FOR THE OTHER 3 SIDES.
  
 D) THE ACCESSIBILITY CODE SECTION 403.3 CROSS SLOPES
 FOR WALKING SURFACES SHALL BE NOT STEEPER THAN 1:48.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED FOR BOTH
 SECTIONS OF THE CODE.
  
 E) SHEET 036-S-4.20 DETAIL # 1 AND 037-S-4.21 DETAIL #
 10 SHOWS THE POOL STRUCTURAL WALL LEVEL WITH THE
 STRUCTURAL DECK HOW WILL WATER FROM THE POOL DECK BE
 SLOPED BACK TO THE LINEAR DECK DRAIN. WATER ON THE POOL
 DECK SHALL BE SLOPED AWAY FROM THE POOL EDGE. 2014
 FBC-B SECTION 454.1.3.1.2.
  
 F) NA
  
 G) SHEET 037-S-4.21 DETAIL # 10 SHOWS A STRUCTURAL BASE
 FOR AN ADA CHAIR LIFT. THE ARCHITECTURAL SHEET
 058-A-104 SHOWS THE POSITION OF THE CHAIR LIFT AND THE
 CLEAR 48X30 INCHES PLEASE PROVIDE THE MANUFACTURES SPEC
 ON THE LIFT THE DISTANCE FROM EDGE OF THE WATER TO THE
 CENTERLINE OF THE SEAT IS 4.75 FEET. WILL THE LIFT BE
 ABLE TO LIFT A PERSON INTO THE WATER WITH A SPAN OF 6
 FEET OR MORE? 2014 FBC-ACCESSIBILITY CODE 1009.2. THE
 LOCATION OF THE STRUCTURAL STAND APPEARS CLOSER THAN
 THE ARCHITECTURAL SHEET?
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 15:43 Rev Time 0.00
Received By shill Date 2018-07-07 Time 19:04 Sent To  
Notes
2018-07-30 16:08:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 27. PENETRATIONS THROUGH 2 HOUR RATED STAIRWAYS
  
 A) PAGE 098-A-701 SHOWS WHAT APPEARS TO BE A 2 HOUR
 DROPPED CEILING.
  
 B) PAGE 048-LS101 AND 050-A101 BOTH SHOW STAIRWAY 3 AS
 A 2HR VERTICAL EXIT STAIRWAY. PENETRATIONS WERE FOUND
 ON PAGE 124-P-101.
  
 SEE FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 PROVISOS:
  
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 C) PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 D) VALET DROP OFF COMPLIANCE TO BE SHOWN ON SEPARATE
 PERMIT.
  
 E) POOL DECK, POOL UNDER A SEPARATE PERMIT.
  
 A) SHEET 049-LS-102, 058-A-104 BOTH SHOW A LINEAR POOL
 DECK DRAIN. NONE OF THE ARCHITECTURAL SHEETS SHOW THE
 ELEVATION OR CROSS SLOPES OF THE POOL DECK. THE
 STRUCTURAL SHEET 012-S-1.04 SHOWS (2) ELEVATIONS ONE AT
 T. O. SLAB AT EL= 83 FEET AND A 2ND ELEVATION AT
 ELEVATION T. O. SLAB 82 FEET. THE STRUCTURAL SHEET
 036-S-4.20 DETAIL # 4 SHOWS 2 HEIGHTS IN THE CONCRETE
 DECK. A FINISHED CONCRETE DECK AND A DROPPED STRUCTURAL
 DECK AROUND THE POOL DECK ASSUMED AT T. O. SLAB AT EL=
 82 FEET.
  
 B) SHEET 037-S-4.21 DETAIL 10 SHOWS THE SUPPORT LIFT BY
 THE EDGE OF THE POOL, BUT THIS SAME DETAIL SHOWS THE
 SIDE WALL OF THE POOL, SECONDARY POOL STRUCTURE BY POOL
 DESIGNER. THERE ARE ONLY THE 2 ELEVATIONS AROUND THE
 POOL. THE STRUCTURAL SHEET 036-S-4.20 DETAIL # 4 HAS A
 NOTE SEE ARCHITECTURAL SHEETS FOR SLOPE.
  
 C) 2014 FBC-B SECTION 454.1.3.1.2. POOL WET DECKS SHALL
 BE UNIFORMLY SLOPED AT A MINIMUM OF 2 PERCENT TO A
 MAXIMUM OF 4 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER. THE PLANS ONLY SHOW A
 LINEAR POOL DRAIN ON THE WEST SIDE OF THE POOL. PLEASE
 SHOW COMPLIANCE FOR THE OTHER 3 SIDES.
  
 D) THE ACCESSIBILITY CODE SECTION 403.3 CROSS SLOPES
 FOR WALKING SURFACES SHALL BE NOT STEEPER THAN 1:48.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED FOR BOTH
 SECTIONS OF THE CODE.
  
 E) SHEET 036-S-4.20 DETAIL # 1 AND 037-S-4.21 DETAIL #
 10 SHOWS THE POOL STRUCTURAL WALL LEVEL WITH THE
 STRUCTURAL DECK HOW WILL WATER FROM THE POOL DECK BE
 SLOPED BACK TO THE LINEAR DECK DRAIN. WATER ON THE POOL
 DECK SHALL BE SLOPED AWAY FROM THE POOL EDGE. 2014
 FBC-B SECTION 454.1.3.1.2.
  
 F) NA
  
 G) SHEET 037-S-4.21 DETAIL # 10 SHOWS A STRUCTURAL BASE
 FOR AN ADA CHAIR LIFT. THE ARCHITECTURAL SHEET
 058-A-104 SHOWS THE POSITION OF THE CHAIR LIFT AND THE
 CLEAR 48X30 INCHES PLEASE PROVIDE THE MANUFACTURES SPEC
 ON THE LIFT THE DISTANCE FROM EDGE OF THE WATER TO THE
 CENTERLINE OF THE SEAT IS 4.75 FEET. WILL THE LIFT BE
 ABLE TO LIFT A PERSON INTO THE WATER WITH A SPAN OF 6
 FEET OR MORE? 2014 FBC-ACCESSIBILITY CODE 1009.2. THE
 LOCATION OF THE STRUCTURAL STAND APPEARS CLOSER THAN
 THE ARCHITECTURAL SHEET?
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-06 Cont ID  
Sent By aclange Date 2018-03-19 Time 09:52 Rev Time 0.00
Received By aclange Date 2018-03-21 Time 07:35 Sent To  
Notes
2018-03-21 16:01:42 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 IF YOU HAVE ANY QUESTIONS OR IF I CAN BE OF FURTHER
 ASSISTANCE FEEL FREE TO CONTACT ME.
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 MARRIOTT HOTEL 17110874
  
 2ND REVIEW
  
 DATE: APRIL 6, 2018
  
  
 1. ADDRESSED.
  
 2. PROVIDE A SQUARE FOOTAGE BREAKDOWN BY USE AND
 OCCUPANCY CLASSIFICATION ON PAGE A-000.
  
 THIS IS USED TO ESTIMATE THE PROJECT COST USING ICC
 BUILDING VALUATION DATA.
 FBC 107.3
  
 PLAN REVIEW RESPONSE:
  
 A) PLEASE NOTE SINCE THE OCCUPANT LOAD FOR THE ROOFTOP
 FLOOR IS OVER 1,000 OCCUPANTS. THERE ARE ONLY 3
 VERTICAL STAIRWAYS IN THE CURRENT CONFIGURATION.
 STAIRWAY # 2 WOULD NEED TO BE RE-CONFIGURED WITH A 2
 HOUR WALL SEPARATING THE TWO SETS OF STAIRS INTO TWO
 SEPARATE STAIR ENCLOSURES TO BE ABLE TO COMPLY WITH
 FBC-B 1021.2.4.
  
 B) SHEET 049-LS-102. IN THE EVENT ROOM 803 CAN BE MADE
 INTO 4 SMALLER ROOMS PLEASE BREAK DOWN THE SQUARE
 FOOTAGE OF EACH ROOM AND THE OCCUPANT LOAD IN EACH.
 WITH THE OCCUPANT LOAD BEING TAKEN @ 7 NET IT WOULD
 APPEAR THAT EACH OF THE FOLDING WALLS WILL NEED A 2ND
 MEANS OF EGRESS IN EACH ROOM. SEE FBC-B TABLE 1015.1.
  
 C) PLEASE NOTE ON THE ROOFTOP DECK THERE MAYBE 3
 VERTICAL EXIT STAIRS BUT STAIRS 1 & 2 ARE LOCATED WHERE
 YOU HAVE TO GO THROUGH SERVICE AREAS. STAIR # 1, JUST
 TO THE EAST OF THIS STAIR IT LOOKS LIKE THIS IS A
 SERVICE AREA FOR DRINKS, AND FOR STAIR # 2 THE SERVICE
 AREA # 800 IS JUST THAT SERVICE AND STORAGE AREAS.
  
 D) INCLUDE THE PREFUNCTION AREAS AND TERRACE AS 7 NET
 AS PART OF THE OCCUPANT LOAD CALCULATIONS.
 SEE TABLE 1004.1.2
  
 2014 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
  
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. 4. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 SHEET 049-LS-102 SHOWS WHAT APPEARS TO BE A SLIDING
 DOOR 802B A FOLDING GLASS PARTITION WALL. PLEASE
 PROVIDE HOW COMPLIANCE WITH 2014 FBC-B 1008.1.2 DOOR
 SWING. EGRESS DOORS SHALL BE OF THE PIVOTED OR
 SIDE-HINGED SWINGING TYPE.
  
 EXCEPTIONS: 9. IN OTHER THAN GROUP H OCCUPANCIES,
 MANUALLY OPERATED HORIZONTAL SLIDING DOORS ARE
 PERMITTED IN A MEANS OF EGRESS FROM SPACES WITH AN
 OCCUPANT LOAD OF 10 OR LESS.
  
 D) SEE ALSO SLIDING GLASS DOOR 802B. THIS CANNOT BE
 USED TO ACCESS THE CORRIDOR LABELED SERVICE 610.
  
 E) SHEET 049-LS-102. THE KEY PLAN INDICATES AREAS OF
 THE FLOOR PLAN WHERE THERE WILL BE NON-SIMULTANEOUS
 OCCUPANT LOADS. THE PRE-FUNCTION AREA LOBBY AND SERVICE
 AREA 610. PLEASE NOTE FOR ASSEMBLY OCCUPANCIES THE ONLY
 AREAS NOT TO BE FIGURED ARE NET AREAS. 2014 FBC-B 201:
 FLOOR AREA, NET. THE ACTUAL OCCUPIED AREA NOT INCLUDING
 UNOCCUPIED ACCESSORY AREAS SUCH AS CORRIDORS,
 STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS AND CLOSETS.
 BUILDINGS ARE LOOKED AT IN THE WORST CASE SCENARIO.
 PROVIDE A CHART NAMING EACH ROOM, AND ROOM NUMBER, THE
 SQUARE FOOT PER OCCUPANT, AND OCCUPANT LOAD PER ROOM,
 PLUS THE TOTAL OCCUPANT LOAD FOR THIS FLOOR PER TABLE
 1004.1.2.
  
 F) IN ORDER TO MAINTAIN A CLEAR FLOW TO THE STAIRS WE
 CAME UP WITH A FEW OPTIONS.
  
 A. ADD A STAY OPEN DOOR TO PREVENT FLOW OF TRAVEL BACK
 INTO THE CORRIDOR NEAR THE WALK IN COOLER ADJACENT TO
 DOOR 807A.
  
 B. AREAS 610 AND 800 SHOULD BE LABELED AS CORRIDOR NOT
 SERVICE AREA.
  
 C. ADDING A DOOR FROM THE POOL DECK TO STAIRS #3 NEAR
 DOOR 814A AND MOVING DOOR 814A OVER TO ALLOW CLEARANCE
 FOR THE NEW DOOR.
  
 D. ADDING A SERIES OF EXIT SIGNS STARTING AT THE
 PREFUNCTION AREA 802 THROUGH LOBBY 801 DIRECTING THE
 FLOW TO THE #1 STAIRS. IF YOU WOULD LIKE TO DISCUSS
 THESE OPTIONS FEEL FREE TO CONTACT ME.
  
 3. OK. ADDRESSED.
  
 4. ELEVATION CERTIFICATE ADDRESSED, WILL ISSUE WITH
 PROVISIO
  
 5. OK. ADDRESSED. WITH FOUNDATION PERMIT.
  
 6. THRESHOLD AGREEMENTS WITH FOUNDATION PERMIT.
  
 7. OK. ADDRESSED.
  
 8. OK. ADDRESSED.
  
 9. OK. ADDRESSED.
  
 10. OK. ADDRESSED.
  
 11. OK. ADDRESSED.
  
 12. OK. ADDRESSED.
  
 13. OK. ADDRESSED.
  
 14. OK. ADDRESSED.
  
 15. AN IMPACT FEE STOP HAS BEEN ADDED SO THAT THIS
 COMMENT CAN BE REMOVED FROM THE STRUCTURAL REVIEW
 COMMENTS.
  
 16. OK. ADDRESSED.
  
 17. OK. ADDRESSED.
  
 18. OK. ADDRESSED.
  
 19. ACCESSIBILITY NOT ADDRESSED. PLEASE SHOW HOW
 COMPLIANCE WILL BE MET FOR THE FOLLOWING AREAS.
  
 226.2 DISPERSION. DINING SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES.
 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS AS WELL
 AS BARS.
  
 A. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR GUEST
 RECEPTION COUNTER.
  
 B. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR BAR AND
 ROOF TOP BARS.
  
 C. PROVIDE ACCESSIBLE SEATING IN DINING ROOM 1ST FLOOR
 CAF? ON TERRACE, RESTAURANT.
  
 D. PROVIDE ACCESSIBLE COUNTER AT ROOF TOP MAIN POOL BAR
 AND SATELLITE BAR.
  
 E. PROVIDE A FURNITURE PLAN FOR THE RESTAURANT AND BAR
 AREAS.
  
 INCLUDE ELEVATIONS OF THESE AREAS TO SHOW COMPLIANCE
 WITH THE FLORIDA ACCESSIBILITY CODE FOLLOWING SECTIONS.
  
 902.1 DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
  
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 902.4.1 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED, EXCEPT
 THAT KNEE CLEARANCE 24 INCHES (610 MM) MINIMUM ABOVE
 THE FINISH FLOOR OR GROUND SHALL BE PERMITTED.
  
 902.4.2 HEIGHT.
 THE TOPS OF TABLES AND COUNTERS SHALL BE 26 INCHES (660
 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 F. 19-2 PROVIDE THE FOLLOWING DETAILS FOR THE HOTEL
 DROP OFF ZONE.
 SHEET 047-AS-101 SHOWS A DROP OFF ZONE IN FRONT OF THE
 HOTEL. THE DETAIL INDICATES SEE SHEET AS102 CURB RAMP
 DETAILS. THE DETAIL SHEET DOES NOT PROVIDE DETAILS FOR
 THE:
 2014 FBC-ACCESSIBILITY CODE:
  
 503.2 VEHICLE PULL-UP SPACE.
 503.3 ACCESS AISLE.
 503.3.1 WIDTH.
 503.3.2 LENGTH.
 503.3.3 MARKING.
 503.4 FLOOR AND GROUND SURFACES.
 503.5 VERTICAL CLEARANCE.
  
 20. OK. ADDRESSED.
  
 21. OK. ADDRESSED.
  
 22. TO BE A PROVISO. PRODUCT APPROVALS AND SHOP
 DRAWINGS WILL BE DEFFERED SUBMITTALS.
  
 23. NOT ADDRESSED.
  
 CONFIRM THAT THE NANA WALL ASSEMBLY USED WILL EXCEED
 THE PRESSURES FOR THE AREAS THAT THEY ARE LOCATED.
 OFTEN THESE DOORS DO NOT MEET THE PRESSURE REQUIREMENTS
 FOR THIS TYPE OF BUILDING. FBC CHAPTER 16 FOR
 COMPONENTS AND CLADDING.
 24. PARTIALLY ADDRESSED. THANK YOU FOR PROVIDING THE
 WEST FACADE AREA CALCULATIONS.
  
 WE VARIFIED THAT THE CALCULATED OPENINGS ARE ACCURATE.
 WE WERE NOT ABLE TO LOCATE THE DISTANCE OF 16FT. 3 IN.
 FOR AREA B. PLEASE CONFIRM THIS DISTANCE. IT APPEARS TO
 BE APPROXIMATLEY 12FT. 7IN. THE CALCULATIONS WILL BE OK
 AT THIS DISTANCE.
  
 PROVIDE THE CALCULATIONS TO SHOW MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION ON THE WEST
 SIDE OF THE HOTEL AND THE PROPOSED BUILDING ALONG THAT
 WEST WALL.
  
 FBC 705.8.1 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
  
 25. OK. ADDRESSED.
  
 26. GENERATOR
  
 AS MENTIONED IN A RESPONSE FOR THE MECHANICAL REVIEW.
 PLEASE PROVIDE INFORMATION ON THE GENERATOR ENCLOSURE
 THAT WILL BE PROVIDED ALONG WITH THE FOLLOWING. ALSO
 SHOW HOW THIS ENCLOSURE WILL COMPLY WITH FBC 1609 BASIC
 WIND SPEED.
  
 A) DISCREPANCY IN PLANS, THE LS SHEET 048-LS-101 DOES
 NOT SHOW A GENERATOR WHEREAS SHEET 050-A101 DOES SHOW A
 GENERATOR. PLEASE NOTE THIS BUILDING DOES REQUIRE A
 GENERATOR BEING A HIGHRISE BUILDING.
  
 2014 FBC-B 403.4.8 STANDBY POWER.
 2014 FBC-B 403.4.8.1 SPECIAL REQUIREMENTS FOR STANDBY
 POWER.
  
 B) DISCREPANCY IN PLANS, THE LS SHEET 048-LS-101 DOES
 NOT SHOW A GENERATOR WHEREAS SHEET 050-A101 DOES SHOW A
 GENERATOR. IN NEITHER SHEET DOES THE PLANS SHOW THE
 GENERATOR FULLY ENCASED IN A 2 HOUR WALL. THE PROPERTY
 LINE WALL IS MISSING. PLEASE SEE FBC-B 403.8.1
 REQUIRING A 2 HOUR FIRE BARRIERS ENCLOSURE WITHIN A
 BUILDING. JUST THE OTHER SIDE OF THE PROPERTY LINE
 THERE IS A 3 HOUR WALL AT THE ASSUMED PROPERTY LINE.
  
 C) SHEETS LS SHEET 048-LS-101 ONLY INDICATE THIS ROOM
 IS TO BE A GENERATOR, PLEASE NOTE THAT NO INFORMATION
 IS GIVEN ON THE LIFE SAFETY SHEET IF THE GENERATOR HAS
 A DAY TANK AND OTHER STORAGE TANKS, NOR DOES EITHER OF
 THESE SHEETS NOTE INTAKE AND EXHAUST FOR THE GENERATOR,
 104-M-101 IS ALSO SILENT ON THIS MATTER. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 D) SHEET 104-M-101 SHOWS WHAT APPEARS TO BE AN EXTERIOR
 WALL ON THE PROPERTY LINE BUT A 18 X 18 INCH EXTERIOR
 LOUVER WHICH WOULD NEED TO BE EXTENDED OUT OF THE
 GENERATOR ROOM. 701.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. THERE SHOULD BE AN EXTERIOR WALL FOR THE
 GENERATOR, NOT SHOWN ON THE CURRENT SET OF PLANS.
  
 27. PENETRATIONS THROUGH 2 HOUR RATED STAIRWAYS
  
 A) PAGE 098-A-701 SHOWS WHAT APPEARS TO BE A 2 HOUR
 DROPPED CEILING.
  
 B) PAGE 048-LS101 AND 050-A101 BOTH SHOW STAIRWAY 3 AS
 A 2HR VERTICAL EXIT STAIRWAY. PENETRATIONS WERE FOUND
 ON PAGE 124-P-101.
  
 SEE FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 28. LAUNDRY ROOM AND LAUNDRY CHUTE
  
 COMMON STATEMENT FOR FLOORS 2-7. SHEET 049LS102 AND
 SHEET 055-A-103 BOTH SHOW THE LAUNDRY CHUTE ACCESS ROOM
 WITHIN THE HOUSE KEEPING ROOM. THE HOUSE KEEPING ROOM
 IS SHOWN AS 1 HOUR RATED BUT NOT THE LAUNDRY CHUTE
 ACCESS ROOM.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 713.13.3 REFUSE,
 RECYCLING AND LAUNDRY CHUTE ACCESS ROOMS.
  
 ACCESS OPENINGS FOR REFUSE, RECYCLING AND LAUNDRY
 CHUTES SHALL BE LOCATED IN ROOMS OR COMPARTMENTS
 ENCLOSED BY NOT LESS THAN 1-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS
 SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION
 OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3.
  
 COMMON STATEMENT FOR FLOORS 2-7. SHEET 049LS102 AND
 SHEET 055-A-103 BOTH SHOW THE LAUNDRY CHUTE ACCESS ROOM
 WITHIN THE HOUSE KEEPING ROOM. THE LAUNDRY CHUTE ACCESS
 ROOM DOES NOT SHOW UP ON THE DOOR SCHEDULE, AND NEEDS
 TO BE 1 HOUR FIRE RATED PER 2014 FBC-B 713.13.3.
  
 29. BOOSTER PUMP
  
 A) BOOSTER PUMP ROOM MAYBE WILL NEED FIRE RATED WALLS
 AND OPENING PROTECTIVES? WHAT IS THIS BOOSTER PUMP TO
 BE USED IN CONJUNCTION WITH? SHEET 124-P-101 THE
 PLUMBING 1ST FLOOR DOES NOT SHOW THE BOOSTER PUMP TYING
 INTO THE PRESSURE POTABLE WATER SYSTEM. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 B) ON PAGE LS 101 THERE IS NOT A DOOR SHOWN TO GET OUT
 OF THE BOOSTER ROOM / STORAGE AREA. PLEASE UPDATE.
  
 30. SWIMMING POOL AREA
  
 NOTE: SEVERAL OF THESE COMMENTS COULD BE A PROVISO OR
 ADDED TO THE SWIMMING POOL PERMIT.
  
 POOL DECK ONLY POOL UNDER A SEPARATE PERMIT.
  
 A) SHEET 049-LS-102, 058-A-104 BOTH SHOW A LINEAR POOL
 DECK DRAIN. NONE OF THE ARCHITECTURAL SHEETS SHOW THE
 ELEVATION OR CROSS SLOPES OF THE POOL DECK. THE
 STRUCTURAL SHEET 012-S-1.04 SHOWS (2) ELEVATIONS ONE AT
 T. O. SLAB AT EL= 83 FEET AND A 2ND ELEVATION AT
 ELEVATION T. O. SLAB 82 FEET. THE STRUCTURAL SHEET
 036-S-4.20 DETAIL # 4 SHOWS 2 HEIGHTS IN THE CONCRETE
 DECK. A FINISHED CONCRETE DECK AND A DROPPED STRUCTURAL
 DECK AROUND THE POOL DECK ASSUMED AT T. O. SLAB AT EL=
 82 FEET.
  
 B) SHEET 037-S-4.21 DETAIL 10 SHOWS THE SUPPORT LIFT BY
 THE EDGE OF THE POOL, BUT THIS SAME DETAIL SHOWS THE
 SIDE WALL OF THE POOL, SECONDARY POOL STRUCTURE BY POOL
 DESIGNER. THERE ARE ONLY THE 2 ELEVATIONS AROUND THE
 POOL. THE STRUCTURAL SHEET 036-S-4.20 DETAIL # 4 HAS A
 NOTE SEE ARCHITECTURAL SHEETS FOR SLOPE.
  
 C) 2014 FBC-B SECTION 454.1.3.1.2. POOL WET DECKS SHALL
 BE UNIFORMLY SLOPED AT A MINIMUM OF 2 PERCENT TO A
 MAXIMUM OF 4 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER. THE PLANS ONLY SHOW A
 LINEAR POOL DRAIN ON THE WEST SIDE OF THE POOL. PLEASE
 SHOW COMPLIANCE FOR THE OTHER 3 SIDES.
  
 D) THE ACCESSIBILITY CODE SECTION 403.3 CROSS SLOPES
 FOR WALKING SURFACES SHALL BE NOT STEEPER THAN 1:48.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED FOR BOTH
 SECTIONS OF THE CODE.
  
 E) SHEET 036-S-4.20 DETAIL # 1 AND 037-S-4.21 DETAIL #
 10 SHOWS THE POOL STRUCTURAL WALL LEVEL WITH THE
 STRUCTURAL DECK HOW WILL WATER FROM THE POOL DECK BE
 SLOPED BACK TO THE LINEAR DECK DRAIN. WATER ON THE POOL
 DECK SHALL BE SLOPED AWAY FROM THE POOL EDGE. 2014
 FBC-B SECTION 454.1.3.1.2.
  
 F) SHEET 036-S-4.20 DETAIL 4 INDICATES THE USE OF WOOD
 DECK BY OTHERS, PLEASE PROVIDE EXACTLY WHERE THIS WOOD
 DECKING IS TO BE INSTALLED, SEE SECTION 454.1.3.1.1 OF
 THE 2014 FBC-B. POOL WET DECKS SHALL BE CONSTRUCTED OF
 CONCRETE OR OTHER NONABSORBENT MATERIAL HAVING A SMOOTH
 SLIP-RESISTANT FINISH. WET DECK AREA FINISHES SHALL BE
 DESIGNED FOR SUCH USE AND SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.
 WOODEN DECKS AND WALKWAYS ARE PROHIBITED.
  
 G) SHEET 037-S-4.21 DETAIL # 10 SHOWS A STRUCTURAL BASE
 FOR AN ADA CHAIR LIFT. THE ARCHITECTURAL SHEET
 058-A-104 SHOWS THE POSITION OF THE CHAIR LIFT AND THE
 CLEAR 48X30 INCHES PLEASE PROVIDE THE MANUFACTURES SPEC
 ON THE LIFT THE DISTANCE FROM EDGE OF THE WATER TO THE
 CENTERLINE OF THE SEAT IS 4.75 FEET. WILL THE LIFT BE
 ABLE TO LIFT A PERSON INTO THE WATER WITH A SPAN OF 6
 FEET OR MORE? 2014 FBC-ACCESSIBILITY CODE 1009.2. THE
 LOCATION OF THE STRUCTURAL STAND APPEARS CLOSER THAN
 THE ARCHITECTURAL SHEET?
  
 31. WALL IDENTIFICATION
  
 SHEET 048-LS101 AND 050-A101 THIS STATEMENT IS COMMON
 FOR ALL FLOOR PLANS. I COULD NOT FIND ANY WALL
 IDENTIFICATION TAGS IDENTIFYING WALL TYPES LISTED ON
 SHEET 093-A6.11. SHEET 093-A6-11 ALSO DOES NOT IDENTIFY
 WALL TYPES WITH WALL IDENTIFICATION TAGS.
 707.3.4 EXIT PASSAGEWAY.
 707.3.1 SHAFT ENCLOSURES.
 707.3.5 HORIZONTAL EXIT
 707.3.7 INCIDENTAL USES.
 420.2 SEPARATION WALLS.
  
 NOTE THIS LIST IS ONLY AN EXAMPLE OF MISSING WALL
 IDENTIFICATION TAGS. SHEET 092-A-601 DOES SHOW WALL
 TYPES BUT THE REFERENCE IS NOT FOUND ON THE
 ARCHITECTURAL FLOOR PLANS, A-101, A-102, A-103, &
 A-104.
  
 32. DOOR AND WALL RATINGS
  
 A) THE LIFE SAFETY PLAN SHOWS 2 HOUR FIRE RATED WALLS
 IN THE LIFE SAFETY ROOM 107 AND MAIN ELECTRICAL ROOM
 BUT THE DOORS 107A AND 108A ONLY SHOW 45 MINUTES. SEE
 FBC-B TABLE 716.5. 2 HOUR WALLS REQUIRE 1 ? HR. OPENING
 PROTECTIVES.
 B) DOOR INTO GENERATOR ROOM 137B. SEE FBC-B TABLE
 716.5. 2 HOUR WALLS REQUIRE 1 ? HR. OPENING
 PROTECTIVES.
 C) DOOR 128A VESTIBULE IN A ONE DOOR FIRE RATED WALL,
 TABLE 716.5 FOR A ONE HOUR FIRE BARRIER A ONE HOUR FIRE
 RATED DOOR.
 D) DOOR 128A VESTIBULE IN A ONE DOOR FIRE RATED WALL,
 TABLE 716.5 FOR A ONE HOUR FIRE BARRIER A ONE HOUR FIRE
 RATED DOOR.
 E) DOOR 124A FUTURE LAUNDRY IN A ONE HOUR RATED WALL
 REQUIRES 1 HR. FIRE RATING PER TABLE 716.5.
 F) PAGES 049 LS102, 055 A-103 AND M-102 AT STAIRWELL #3
 SHOULD SHOW A 2 HOUR RATING BETWEEN THE SMOKE PURGE
 MAKE- UP AIR AND THE STAIRWELL AND THE STAIRWELL
 PRESSURIZATION RISER.
 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
 G) DOOR 124A FUTURE LAUNDRY IN A ONE HOUR RATED WALL
 REQUIRES 1 HR. FIRE RATING PER TABLE 716.5.
 H) DOOR 118A LOOKS LIKE AN EXIT DOOR FROM THE
 STAIRWELL, THERE NEEDS TO BE SIGNAGE ON THIS DOOR NOT
 AN EXIT TO THE EXTERIOR. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. SIGNAGE REQUIRED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  
 PROVISOS:
  
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 C) PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By alange Date 2018-01-31 Time 11:32 Rev Time 0.00
Received By aclange Date 2018-01-26 Time 08:49 Sent To  
Notes
2018-01-31 11:29:56****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 MARRIOTT HOTEL 17110874
 1ST REVIEW
 DATE: JANUARY 31, 2018
  
 ACTION: DENIED
  
 ART IN PUBLIC PLACES
  
 NOTICE ONLY: THE CITY OF WEST PALM BEACH ART IN PUBLIC
 PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 1. ADDRESSING
  
 PROVIDE THE ADDRESS OF 251 NARCISSUS AVE. IN THE TILE
 BLOCK OF ALL PAGES AND SUPPORTING DOCUMENTS.
  
 IF YOU BELIEVE THIS ADDRESS IS NOT CORRECT CONTACT
 MICHAEL ORIO.
 CITY MUNI CODE SEC.78-6 (1-7)
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
 2. PROVIDE A SQUARE FOOTAGE BREAKDOWN BY USE AND
 OCCUPANCY CLASSIFICATION ON PAGE A-000.
 THIS IS USED TO ESTIMATE THE PROJECT COST USING ICC
 BUILDING VALUATION DATA.
 FBC 107.3
  
 3. WATERPROOFING
  
 ON PAGE A 711 ELEVATOR SECTIONS A AND B SHOW BLINDSIDE
 WATERPROOFING. PROVIDE SPECIFICATIONS FOR THIS PRODUCT.
 FBC 1805.3 WATERPROOFING.
  
 WHERE THE GROUND-WATER INVESTIGATION REQUIRED BY
 SECTION 1803.5.4 INDICATES THAT A HYDROSTATIC PRESSURE
 CONDITION EXISTS, AND THE DESIGN DOES NOT INCLUDE A
 GROUND-WATER CONTROL SYSTEM AS DESCRIBED IN SECTION
 1805.1.3, WALLS AND FLOORS SHALL BE WATERPROOFED IN
 ACCORDANCE WITH THIS SECTION.
  
 4. FLOOD ZONE CERTIFICATES
  
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
  
 (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
  
 (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 5. SUBMIT SUPPORTING DOCUMENTS FROM ARDAMAN @
 ASSOCIATES.THEY SHALL BE REVIEWED BY THE ARCHITECT OF
 RECORD AND STAMPED AS REVIEWED AND APPROVED.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 6. THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 6A. THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 6C. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 6D. A FOUNDATION PERMIT IS IN APPLICATION 17090201 AND
 HAS NOT BEEN APPROVED AT THIS POINT. PLEASE SUBMIT THE
 THRESHOLD INSPECTION PLAN, SOILS REPORTS AND THRESHOLD
 APPLICATION WITH THIS PERMIT AS WELL.
  
 7. PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. 2014
 FBC 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL
 SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO
 UNITS HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR
 PERMANENT EXCAVATIONS SHALL NOT BE STEEPER THAN ONE
 UNIT VERTICAL IN TWO UNITS HORIZONTAL (50-PERCENT
 SLOPE). DEVIATION FROM THE FOREGOING LIMITATIONS FOR
 CUT SLOPES SHALL BE PERMITTED ONLY UPON THE
 PRESENTATION OF A SOIL INVESTIGATION REPORT ACCEPTABLE
 TO THE BUILDING OFFICIAL.
  
 8. SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 9. PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION
 PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING
 PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM
 DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION
 WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF
 AND EROSION DURING CONSTRUCTION OR DEMOLITION
 ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION
 TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS
 OF ADJOINING BUILDINGS ADVISING THEM THAT THE
 EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
  
 10. IMPACT OF CONSTRUCTION 109.3.10. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 11. ADJACENT TO EXCAVATIONS FBC 3306.9. EVERY
 EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR LESS
 FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
  
 12. PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 13. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR
 BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL
 BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR
 MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT
 THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513,
 FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS
 WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 14. STANDPIPES. FBC 3311.1
  
 IN BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION
 905.3.1, NO FEWER THAN ONE STANDPIPE SHALL BE PROVIDED
 FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE
 INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE
 THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST
 LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE
 SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS
 AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 15. IMPACT FEES.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 16. WALL SECTIONS 3 / A. 301 AND 4 / A.301 SHOW FAUX
 BEAMS. PLEASE PROVIDE ADDITIONAL INFORMATION ON THIS
 PRODUCT. SHOW HOW THIS IS IN COMPLIANCE WITH FBC 603.1
 COMBUSTIBLE MATERIALS IN TYPE I CONSTRUCTION.
  
 17. INSULATION IN SEVERAL LOCATIONS IS SHOWN AS R-20.
 THE ENERGY CALCS PROVIDED SHOW R-19 AT ROOF LOCATIONS.
 PLEASE CLARIFY. FBC 107.3
  
 18. ON PAGE A. 204A PROVIDE A ROOM DESCRIPTION FOR THE
 ROOM NEXT TO THE ELEVATOR SHAFT WITH DOOR 808A. FBC
 107.3
  
 19. ACCESSIBILITY
  
 A. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR GUEST
 RECEPTION COUNTER.
  
 B. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR BAR.
  
 C. PROVIDE ACCESSIBLE SEATING IN DINING ROOM 1ST FLOOR
 CAF? ON TERRACE, RESTAURANT.
  
 D. PROVIDE ACCESSIBLE COUNTER AT ROOF TOP MAIN POOL BAR
 AND SATELLITE BAR.
  
 INCLUDE ELEVATIONS OF THESE AREAS TO SHOW COMPLIANCE
 WITH THE FLORIDA ACCESSIBILITY CODE FOLLOWING SECTIONS.
  
 902.1 DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
  
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 902.4.1 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED, EXCEPT
 THAT KNEE CLEARANCE 24 INCHES (610 MM) MINIMUM ABOVE
 THE FINISH FLOOR OR GROUND SHALL BE PERMITTED.
  
 902.4.2 HEIGHT.
 THE TOPS OF TABLES AND COUNTERS SHALL BE 26 INCHES (660
 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 20. DOOR ARRANGEMENT
  
 THE DISTANCE BETWEEN THE DOORS IN SERIES AT THE
 CORRIDOR BY THE CORNER SUITES IS LESS THAN 48?. SEE
 SUITES 211 AND 243 FOR AN EXAMPLE.
  
 FBC 1008.1.8 SPACE BETWEEN TWO DOORS IN A SERIES SHALL
 BE 48 INCHES (1219 MM) MINIMUM PLUS THE WIDTH OF A DOOR
 SWINGING INTO THE SPACE. DOORS IN A SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE
 BETWEEN THE DOORS.
  
  
 21. RAILING SHOWN ON ID 303 1. THE HEIGHT IS OK. WHAT
 IS ON THE OPPOSITE SIDE. SHOW COMPLIANCE WITH FBC
 1013.2 WHERE REQUIRED.
  
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS,
 STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN
 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR
 GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM)
 HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS SHALL
 BE ADEQUATE IN STRENGTH AND ATTACHMENT IN ACCORDANCE
 WITH SECTION 1607.8.
  
 FBC 1013.4 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 22. PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
  
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 23. CONFIRM THAT THE NANA WALL ASSEMBLY USED WILL
 EXCEED THE PRESSURES FOR THE AREAS THAT THEY ARE
 LOCATED. OFTEN THESE DOORS DO NOT MEET THE PRESSURE
 REQUIREMENTS FOR THIS TYPE OF BUILDING. FBC CHAPTER 16
 FOR COMPONENTS AND CLADDING.
  
 24. PROVIDE THE CALCULATIONS TO SHOW MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION ON THE WEST
 SIDE OF THE HOTEL AND THE PROPOSED BUILDING ALONG THAT
 WEST WALL.
 FBC 705.8 AND TABLE 705.8.
 FBC 705.8.1 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
  
 25. SEPARATE PERMITS REQUIRED FOR CONSTRUCTION
 TRAILERS, LANDSCAPING, SIGNS AND SWIMMING POOL.
 THE FOUNDATION PERMIT SUBMITTED 17090201 HAS COMPLETED
 THE FIRST ROUND OF PLAN REVIEWS. FBC 105.1
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-12 Cont ID  
Sent By jpearson Date 2018-07-12 Time 15:00 Rev Time 0.00
Received By jpearson Date 2018-07-12 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By jpearson Date 2018-04-12 Time 14:11 Rev Time 0.00
Received By jpearson Date 2018-04-12 Time 14:10 Sent To  
Notes
2018-04-12 14:10:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. PROVIDE SPECS OF FIRE PUMP CONTROLLER/ATS, FIRE
 PUMP MOTOR, AND JOCKEY PUMP. INCLUDE MOTOR SIZES AND
 AMPERAGE DRAW TO CONFIRM CONDUCTOR SIZING. NEC 110.3,
 695.4, 695.6 (INSUFFICIENT INFORMATION PROVIDED. MOTOR
 HP, LOCKED ROTOR CURRENT, AND NORMAL CURRENT NEED TO BE
 SHOWN ON PLAN FOR SIZING OF CONDUCTORS. FIRE PROTECTION
 SHEET DOES NOT PROVIDE THIS INFORMATION.)
 11. CORRECTED.
 12. CORRECTED.
 13. PROVIDE ACCURATE SIZE OF MAIN BONDING JUMPER. NEC
 250.28(D) (THE MAIN BONDING JUMPER IS DEFINED AS "THE
 CONNECTION BETWEEN THE GROUNDED CIRCUIT CONDUCTOR AND
 THE EQUIPMENT GROUNDING CONDUCTOR AT THE SERVICE". THE
 PLAN SHOWS A 750 KCMIL CONDUCTOR IN THE LOCATION THAT
 THE GROUNDING ELECTRODE CONDUCTOR IS INSTALLED, WHICH
 IS LABELED WRONG AS THE MAIN BONDING JUMPER. PER NEC
 250.66, THE GROUNDING ELECTRODE CONDUCTOR WOULD BE 3/0
 CU OR 250 KCMIL AL. THE MAIN BONDING JUMPER FOR SERVICE
 # 1 WOULD HAVE TO EQUAL OR EXCEED 12.5% OF THE TOTAL
 CONDUCTOR AREA. NINE SETS OF 750 KCMIL WOULD THEREFORE
 REQUIRE A CONDUCTOR SIZED AT 843.75 KCMIL CU, WHICH THE
 NEXT SIZE AVAILABLE IS 900 KCMIL, OR THE EQUIVALENT
 PARALLEL CONDUCTORS. THE MAIN BONDING JUMPERS FOR
 ADDITIONAL SERVICES WOULD ALSO NEED TO BE CALCULATED
 PER NEC 250.28(D)(1). PROVIDE CORRECTION.)
 14. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE.
 LOAD CALCULATION PROVIDED SHOWS DEMAND FACTORS APPLIED
 TWICE, ONCE FOR EACH PANEL, AND THEN AGAIN FOR NUMBER
 OF UNITS. DEMAND FACTORS CAN ONLY BE APPLIED ONCE FOR
 SERVICE. ADDITIONALLY, THE DEMAND FACTORS PERMITTED IN
 NEC 220.84 APPLY TO DWELLING UNITS, WHICH IS DEFINED AS
 A UNIT THAT HAS PERMANENT PROVISIONS FOR LIVING,
 SLEEPING, COOKING, AND SANITATION. MANY OF THE GUEST
 ROOMS DO NOT FIT THIS DEFINITION, THEREFORE, THE DEMAND
 FACTORS COULD NOT BE APPLIED. NO LOAD CALCULATION
 PROVIDED FOR SERVICE 2 OF 2, OR FOR GENERATOR. NEC 100,
 220; FBC 107.2.1 (THERE ARE STILL LOADS MISSING IN SOME
 PANEL SCHEDULES, THEREFORE, HOW CAN THE LOAD
 CALCULATION PROVIDED BE ACCURATE? AS AN EXAMPLE, THERE
 IS NO LOAD INCLUDED FOR THE POOL PANEL. THIS IS NOT THE
 ONLY EXAMPLE. PROVIDE ACCURATE LOAD CALCULATION AS
 PREVIOUSLY REQUESTED.)
 15. PROVIDE VOLTAGE DROP CALCULATIONS, SHOWING
 COMPLIANCE WITH FBC EC C405.7.3, PROVIDE BLOCK NOTE
 STATING COMPLIANCE WITH FBC EC C405.7.4 AT COMPLETION
 OF PROJECT. (THESE ARE 2 SEPARATE ITEMS. THE VOLTAGE
 DROP CALCULATIONS NEED TO BE SHOWN ON PLAN AS PART OF
 DESIGN PER C405.7.3. VOLTAGE DROP CALCULATION IS ALSO
 REQUIRED AT FIRE PUMP PER 695.7. THE BLOCK NOTE
 PROVIDED INCORRECTLY REQUIRES THE ELECTRICAL CONTRACTOR
 TO PROVIDE THIS INFORMATION. THE BLOCK NOTE SHOULD BE
 FOR SUBMITTAL DOCUMENTS REQUIRED PER C405.7.4. READ
 CODE SECTION AND PROVIDE ACCURATE BLOCK NOTE IN
 ADDITION TO THE VOLTAGE DROP CALCULATIONS THAT ARE
 REQUIRED TO BE ON PLAN.)
 16. CORRECTED.
 17. MANY PANEL SCHEDULES PROVIDED ARE MISSING
 INFORMATION INCLUDING LOAD INFORMATION, GFCI
 PROTECTION, AND WIRE SIZES. PROVIDE PANEL SCHEDULES FOR
 ALL PANELS WITH COMPLETE INFORMATION. NEC 215.2, 215.5,
 408.4, 408.30; FBC 107.2.1 (NOT CORRECTED COMPLETELY)
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87 (NOTE
 PROVIDED STATES THAT DOCUMENTATION WILL BE PROVIDED.
 HOWEVER, THERE IS NO EXPLANATION ON PLAN HOW THE ARC
 REDUCTION WILL BE ACCOMPLISHED. DETAIL WHICH METHOD
 WILL BE USED.)
 22. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
 (RESPONSE LETTER STATES THIS WILL BE PROVIDED IN AN
 ADDENDUM, BUT THIS COULD NOT BE LOCATED ON PLAN.
 PROVIDE AS PREVIOUSLY REQUESTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-04 Cont ID  
Sent By jpearson Date 2018-02-04 Time 15:51 Rev Time 0.00
Received By jpearson Date 2018-01-25 Time 08:08 Sent To  
Notes
2018-02-04 14:33:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PLAN DOES NOT SHOW ADDRESS OF PROJECT. PROVIDE
 ADDRESS ON PLAN SHEETS. FBC 107.2.1
 3. PROVIDE DETAILS OF THE ADDITIONAL LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2,
 405.2.2.2
 4. SHEET E-104 SHOWS LIGHTING ADJACENT TO THE POOL THAT
 APPEARS TO BE WITHIN THE ZONE WHERE LIGHTING IS NOT
 PERMITTED. PROVIDE CORRECTION. NEC 680.22(B)(1)
 5. SHEET E-201 SHOWS A ?GENERATOR LOAD BANK?. PROVIDE
 CLARIFICATION OF LOAD TEST PROCEDURE AND SPECS. WHY IS
 THIS FED FROM PANEL EH1? NEC 110.3, 215.5; FBC 107.2.1
 6. MOST BATHROOMS IN GUEST ROOMS DO NOT SHOW THE
 REQUIRED GFCI OUTLET WITHIN 3 FEET OF BASIN. ALSO, THE
 CIRCUIT SHOWN FOR THE BATHROOM IS SHOWN FEEDING LIGHTS
 OR OUTLETS OUTSIDE OF THE BATHROOM. PROVIDE
 CORRECTIONS. NEC 210.11, 210.60
 7. NOTE 35 OF GENERAL NOTES STATES THAT THE RECEPTACLES
 FOR WATER COOLERS SHALL BE DIRECTLY BEHIND THE WATER
 COOLER, OUT OF SIGHT. GFCI PROTECTION FOR WATER COOLERS
 IS REQUIRED TO BE READILY ACCESSIBLE. PROVIDE FURTHER
 EXPLANATION IN NOTE, OR AT LOCATION OF WATER COOLERS,
 THAT IF THE RECEPTACLE IS BEHIND COOLER, A GFCI BREAKER
 MUST BE USED. NEC 210.8, 422.52
 8. DIAGRAM FOR SERVICE DISCONNECT 2 OF 2 IS CONFUSING
 AND NEEDS CLARIFICATION. THIS IS LABELED AS A FIRE PUMP
 ATS, BUT IS SHOWS AS A DISCONNECT. THERE APPEARS TO BE
 A FEED FROM THE GENERATOR WHICH SHOWS TWO 600 AMP
 BREAKERS TIED TOGETHER, ONE FOR FIRE PUMP AND ONE FOR
 ATS-E. FEED FOR FIRE PUMP NEEDS TO BE INDEPENDENT OF
 ANY OTHER LOADS. FIRE PUMP AND JOCKEY PUMP ARE NOT
 SHOWN ON RISER DIAGRAM. PROVIDE CORRECTION AND
 CLARIFICATION. FBC 107.2.1; NEC 695.4, 695.6
 9. JOCKEY PUMP IS SHOWN AS BEING FED FROM PANEL EH1,
 CIRCUIT 7, 9, 11. JOCKEY PUMP FEED SHOULD NOT COME FROM
 A SOURCE THAT FEEDS LOADS OTHER THAN FIRE PUMP
 ASSOCIATED EQUIPMENT. PROVIDE CORRECTION. NEC 695.6
 10. PROVIDE SPECS OF FIRE PUMP CONTROLLER/ATS, FIRE
 PUMP MOTOR, AND JOCKEY PUMP. INCLUDE MOTOR SIZES AND
 AMPERAGE DRAW TO CONFIRM CONDUCTOR SIZING. NEC 110.3,
 695.4, 695.6
 11. PROVIDE GFI PROTECTION FOR MAIN MSB. NEC 230.95
 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 ESTIMATED VALUES ARE NOT ACCEPTABLE. NEC 110.9, 110.10
 13. PROVIDE ACCURATE SIZE OF MAIN BONDING JUMPER. NEC
 250.28(D)
 14. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE.
 LOAD CALCULATION PROVIDED SHOWS DEMAND FACTORS APPLIED
 TWICE, ONCE FOR EACH PANEL, AND THEN AGAIN FOR NUMBER
 OF UNITS. DEMAND FACTORS CAN ONLY BE APPLIED ONCE FOR
 SERVICE. ADDITIONALLY, THE DEMAND FACTORS PERMITTED IN
 NEC 220.84 APPLY TO DWELLING UNITS, WHICH IS DEFINED AS
 A UNIT THAT HAS PERMANENT PROVISIONS FOR LIVING,
 SLEEPING, COOKING, AND SANITATION. MANY OF THE GUEST
 ROOMS DO NOT FIT THIS DEFINITION, THEREFORE, THE DEMAND
 FACTORS COULD NOT BE APPLIED. NO LOAD CALCULATION
 PROVIDED FOR SERVICE 2 OF 2, OR FOR GENERATOR. NEC 100,
 220; FBC 107.2.1
 15. PROVIDE VOLTAGE DROP CALCULATIONS, SHOWING
 COMPLIANCE WITH FBC EC C405.7.3, PROVIDE BLOCK NOTE
 STATING COMPLIANCE WITH FBC EC C405.7.4 AT COMPLETION
 OF PROJECT.
 16. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC 405.7.1
 17. MANY PANEL SCHEDULES PROVIDED ARE MISSING
 INFORMATION INCLUDING LOAD INFORMATION, GFCI
 PROTECTION, AND WIRE SIZES. PROVIDE PANEL SCHEDULES FOR
 ALL PANELS WITH COMPLETE INFORMATION. NEC 215.2, 215.5,
 408.4, 408.30; FBC 107.2.1
 18. PROVIDE DETAIL OF LABELING FOR SERVICE. NEC
 230.2(E)
 19. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 20. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 21. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87
 22. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
  
 DUE TO LACK OF INFORMATION OF PLANS PROVIDED, A
 COMPLETE REVIEW COULD NOT BE COMPLETED AT THIS TIME. BE
 ADVISED THAT FURTHER REVIEW COMMENTS ARE POSSIBLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2018-10-31 Cont ID  
Sent By mgonzale Date 2018-10-31 Time 11:04 Rev Time 0.00
Received By mgonzale Date   Time   Sent To  
Notes
2018-10-31 11:04:49WPB AUTOGRAPH 17110874 (POOL BACKWASH) 251 NARCISSUS
 AVE.
  
 BELOW FROM JASON G. FROM GILLIANA POOLS LLC, HIS
 CONTACT INFO IS BELOW AS WELL.
  
 I HAVE ADDED THIS TO PROVIDE THE BREAKDOWN AS
 REQUESTED.
  
 696 GALLONS PER MONTH, AT AN INTERVAL OF 174 GALLONS
 WEEKLY.
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 13:52 Rev Time 0.00
Received By shill Date 2018-07-08 Time 13:52 Sent To  
Notes
2018-07-08 13:52:56OK PER MG
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 10:13 Rev Time 0.00
Received By shill Date 2018-04-21 Time 10:13 Sent To  
Notes
2018-04-21 10:13:46CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By squinone Date 2018-01-22 Time   Rev Time 0.00
Received By squinone Date 2018-01-22 Time   Sent To  
Notes
2018-01-22 13:20:481) SITE PLAN HAS NOT BEEN APPROVED.
 2) ADDRESS PPRC ENG COMMENTS.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-02 Cont ID  
Sent By pleduc Date 2018-07-02 Time   Rev Time 0.00
Received By pleduc Date 2018-06-12 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-15 Cont ID  
Sent By scaldero Date 2018-03-15 Time 14:38 Rev Time 0.00
Received By scaldero Date 2018-03-15 Time 14:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By scaldero Date 2018-01-31 Time 14:05 Rev Time 0.00
Received By scaldero Date 2018-01-23 Time 12:33 Sent To  
Notes
2018-01-31 14:05:10PERMIT #17110874
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 1) SHEET LS101: OCCUPANT LOADS ARE SLIGHTLY OFF IN
 SEVERAL AREAS. PLEASE REVIEW AND MAKE CHANGES AS
 NEEDED.
  
 2) LIFE SAFETY SHEETS AND ELECTRICAL LIGHTING PLAN
 SHEETS DO NOT APPEAR TO MATCH WITH REGARDS TO EXIT
 DIRECTIONAL SIGNS. THE LIFE SAFETY SHEETS SHOW THEM,
 BUT THEY ARE NOT LISTED OR NOT AS OBVIOUS ON THE
 ELECTRICAL LIGHTING PLAN SHEETS. PLEASE REVIEW AND
 ENSURE THAT ALL SHEETS SHOW THE SAME DETAILS.
  
 3) DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, HALLWAY OR LANDING
 UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN 7-INCHES
 INTO THE REQUIRED WIDTH OF THE EGRESS PATH WHEN FULLY
 OPEN. PLEASE REVIEW THE DOOR SWING PROJECTION FOR THE
 CONFERENCE ROOM AND MAIN ELECTRICAL ROOM ON SHEET
 LS101.
  
 4) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND
 WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 5) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS, AS APPLICABLE
 TO THIS PROJECT.
  
 6) PER NFPA 1: 16.3.5 STANDPIPES. IN ALL NEW BUILDINGS
 IN WHICH STANDPIPES ARE REQUIRED OR WHERE STANDPIPES
 EXIST IN BUILDINGS BEING ALTERED OR DEMOLISHED, SUCH
 STANDPIPES SHALL BE MAINTAINED IN CONFORMITY WITH THE
 PROGRESS OF BUILDING CONSTRUCTION IN SUCH A MANNER THAT
 THEY ARE ALWAYS READY FOR USE. [241:7.6]
  
 7) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 8) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 9) PLEASE REVIEW AND COMPLY WITH ALL COMMENTS FROM
 BUILDING PLAN REVIEW.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2018-09-21 Cont ID  
Sent By shill Date 2018-09-21 Time 12:24 Rev Time 0.00
Received By gjohnson Date 2018-09-21 Time 12:24 Sent To  
Notes
2018-09-24 12:04:08PROVISO:
  
 3. PROVIDE SHOP DRAWINGS FOR THE EXHAUST AND INTAKE
 PIPING FOR THE BOILERS SHOW ALL REQUIRED CLEARANCES
 FROM OPENINGS, PROPERTY LINES AND ROOFS OR OVERHANGS
 STAMPED BY THE ENGINEER OF RECORD.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-09-21 12:25:09***PROVISO***
  
 GEORGE JOHNSON, PLUMBING PLANS EXAMINER II
 [email protected]
 561-805-6711
  
 1. PROVIDE DOCUMINTATION FROM MANUFACTURE THAT THE
 CONFIGURATION OF THE BOILER INTAKE AND EXHAUST AND THE
 GENARATOR WILL FUNCTION PROPERLY WITH BOTH RUNNING
 SIMULTANIOUSLY. AS SHOWN ON THE PLAN.
  
 2. PROVIDE SIGNED ANS SEALED LETTER FROM THE ENGINEER
 OF RECORD THAT THE CONFIGURATION OF THE BOILER INTAKE
 AND EXHAUST AND THE GENARATOR WILL FUNCTION PROPERLY
 WITH BOTH RUNNING SIMULTANIOUSLY. AS SHOWN ON THE PLAN.
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2018-08-29 Cont ID  
Sent By gjohnson Date 2018-08-29 Time 12:11 Rev Time 0.00
Received By gjohnson Date 2018-08-29 Time 12:11 Sent To  
Notes
2018-08-29 12:19:14 
 4TH REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR
 ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW
 WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS
 NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE
 MANUFACTURE WILL BE REQUIRED STATING THAT THIS
 CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION
 PROPERLY. PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DOCUMENT A SIGNED AND SEALED LETTER FROM THE
 MANUFACTURES AND THE ENGINEER. STATING THAT THIS PIPING
 LAYOUT WILL ALLOW BOTH THE GENERATOR AND THE BOILERS TO
 FUNCTION PROPERLY SIMULTANEOUSLY.
  
 PREVIOUS COMMENT NOT COMPLIED 5. SHT. P-407 PLEASE SHOW
 ON THE PLAN THE MIN DISTANCE BETWEEN THE INTAKE AND
 EXHAUST. . PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DIMENSIONS ON THE PLAN.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-07-30 Cont ID  
Sent By gjohnson Date 2018-07-30 Time 14:19 Rev Time 0.00
Received By gjohnson Date 2018-07-30 Time 13:31 Sent To  
Notes
2018-07-30 15:02:16 
 3RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE LONGEST LENGTH FROM .5LB REGULATOR TO
 APPLIANCES IN THE KITCHENS. PER FBC FG 402.4.1
 2. THE SECTION OF PIPE BETWEEN THE REGULATOR FOR THE
 GENERATOR UPSTREAM TO THE FIRST TEE IS UNDERSIZED IT
 SHALL BE 11/2' USING 300' PER FBCFG TABLE 402.4(5)
 3. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE POOL
 HEATER. PER FBC FG 304.5
 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR
 ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW
 WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS
 NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE
 MANUFACTURE WILL BE REQUIRED STATING THAT THIS
 CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION
 PROPERLY. PER WPB AMEND TO FBC 107.2.1
 5. SHT. P-407 PLEASE SHOW ON THE PLAN THE MIN DISTANCE
 BETWEEN THE INTAKE AND EXHAUST. . PER WPB AMEND TO FBC
 107.2.1
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND PRESSURE
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By gjohnson Date 2018-04-12 Time 14:58 Rev Time 0.00
Received By gjohnson Date 2018-04-12 Time 16:50 Sent To  
Notes
2018-04-12 16:39:051ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-903 #3 UNDER THE KEYED NOTES LIST THE LONGEST
 RUN AT 150' WHEN I ADDED UP THE LENGTHS ON THE RISER TO
 THE MAIN KIT IT WAS OVER 200' AND THE ARE SOME LENGTHS
 MISSING AT THE END OF THE RUN PLEASE CLARIFY. PER FBC
 FG 402.4.1 AND WPB AMEND TO FBC 107.2.1
  
 2. THE 11/2" BRANCH FEEDING THE UPPER KITCHEN AND POOL
 EQUIPMENT AT 4142 CFH IS UNDERSIZED RESIZE AFTER
 LONGEST LENGTH IS CLARIFIED. PER FBC FG TABLE 402.4(5)
  
 3. PLEASE LABEL THE GAS APPLIANCE BEING FED BY THE 11/4
 BRANCH AT 2782 CFH. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE LABEL THE FOUR GAS APPLIANCE BEINGWIT A CFH
 LOAD OF 1060 I THINK THEY ARE THE BOILERS . PER WPB
 AMEND TO FBC 107.2.1
  
 5. THE 1" BRANCH AT .5 LBS TO POOL HEATER IS
 UNDERSIZED. FBC FG TABLE 402.4(1)
  
 6. PLEASE LABEL THE DUCT WORK ON SHT P-401 DETAILS
 #1+3. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By gjohnson Date 2018-01-31 Time 10:06 Rev Time 0.00
Received By gjohnson Date 2018-01-31 Time 10:06 Sent To  
Notes
2018-01-31 10:24:551ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. LABEL THE KITCHEN EQUIPMENT ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW THE LENGTH OF EACH CUT SECTION OF PIPE
 INCLUDING PIPING TO POOL EQUIPMENT. PER WPB AMEND TO
 FBC 107.2.1
  
 3. SHOW THE CFH LOAD FOR THE POOL EQUIPMENT. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE THE COMBUSTION AIR CALCULATIONS FOR
 THE KITCHENS AND POOL EQUIPMENT. PER FBC FG 304
  
 5. SHOW TABLE USED TO SIZE 2PSI SYSTEM PER FBC FG TABLE
 404.4(1) -(37)
  
 6. PLEASE SUBMIT THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND
 REGULATORS . PER NFPA 54, NFPA 58, AND FBC-2014 FUEL
 GAS SEC. 402.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-09-21 Cont ID  
Sent By shill Date 2018-09-21 Time 12:35 Rev Time 0.00
Received By shill Date 2018-09-21 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-09-19 Cont ID  
Sent By shill Date 2018-09-19 Time 12:57 Rev Time 0.00
Received By shill Date 2018-08-08 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 16:08 Rev Time 0.00
Received By shill Date 2018-06-11 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-05-18 Time   Rev Time 0.00
Received By shill Date 2018-03-13 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-18 Cont ID  
Sent By cpuell Date 2018-05-18 Time 16:33 Rev Time 0.00
Received By cpuell Date 2018-03-13 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-12 Cont ID  
Sent By lmarchan Date 2018-02-12 Time 07:54 Rev Time 0.00
Received By lmarchan Date 2018-01-10 Time 11:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-06-01 Cont ID  
Sent By shill Date 2018-06-01 Time 17:14 Rev Time 0.00
Received By shill Date 2018-06-01 Time 17:14 Sent To  
Notes
2018-06-01 17:14:35MU 2018-0601-268
 $459,049.76
  
 NUMBER ON PLAN:
 18-18822
 $459,049.76
  
2018-06-01 16:56:09GIVEN TO SHILL

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By aclange Date 2018-04-02 Time 08:06 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 08:06 Sent To  
Notes
2018-04-02 08:07:14****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-01-26 Cont ID  
Sent By aclange Date 2018-01-26 Time 08:52 Rev Time 0.00
Received By aclange Date 2018-01-26 Time 08:52 Sent To  
Notes
2018-01-26 08:53:11****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-09-19 Cont ID  
Sent By ccole Date 2018-09-19 Time 15:43 Rev Time 0.00
Received By ccole Date 2018-09-12 Time 12:14 Sent To  
Notes
2018-09-19 16:19:10MECHANICAL PROVISOS:
 9/19/2018
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS
 AND EXHAUST SYSTEMS, THE FIRE SUPPRESSION SYSTEMS, THE
 WALK-IN COOLER AND FREEZER, GENERATOR, FIRE ALARM, AND
 FIRE SPRINKLERS.
  
 CONCERNING THE KITCHEN HOODS AND EXHAUST SYSTEMS, THE
 CURRENT DESIGN AS SHOWN ON THE MAIN PLANS WILL BE
 ACCEPTED WITH THE CONTINGENCIES LISTED BELOW:
  
 A) THE LOCATIONS OF THE GOOSENECK EXHAUST TERMINATIONS
 ON THE LOW ROOF WILL NOT CAUSE EITHER A PUBLIC NUISANCE
 TO OCCUPANTS OF EITHER THE AUTOGRAPH HOTEL OR THE
 ADJACENT APARTMENT BUILDING, NOR WILL THEY CAUSE DAMAGE
 TO OR DEGRADATION OF THE ROOF SURFACE, OR POTENTIALLY
 IMPEDE ROOF DRAINAGE.
  
 B) THE IN-LINE GREASE EXHAUST FANS WILL BE EQUIPPED
 WITH ADEQUATE FILTERS TO MINIMIZE THE GREASE LADEN
 EXHAUST VAPOR AND ODORS FROM BEING DISPERSED INTO THE
 AIR WHERE THEY MAY BECOME A NUISANCE TO OCCUPANTS OF
 THE APARTMENT AND HOTEL BUILDINGS.
  
 C) A MAINTENANCE PROGRAM AND SCHEDULE FOR PERIODIC
 CLEANING AND INSPECTION OF THE EXHAUST FANS AND DUCTS
 WILL BE DEVELOPED BY THE OWNERSHIP OF THE AUTOGRAPH
 HOTEL, AND AN OUTLINE OF THE PROGRAM SHALL BE SUBMITTED
 TO THE BUILDING DEPARTMENT.
  
 2) THE 36"X82" CASEMENT WINDOW USED FOR ACCESS TO THE
 LOW ROOF FOR SERVICING AND REPLACEMENT OF EQUIPMENT IS
 NOT ACCEPTED. IN IT'S PLACE, A MINIMUM 36" WIDE
 EXTERIOR DOOR SHALLL BE INSTALLED, ALONG WITH ANY
 REQUIRED PERMANENT STEPS OR LADDER NEEDED TO ACCESS THE
 ROOF.
  
 3) THE FIRE PUMP ROOM SHALL BE VENTILATED PER SECTION
 4.13.6 NFPA-20.
  
 4) THE COMBUSTION AIR INTAKE AND EXHAUST SYSTEM FOR THE
 GAS-FIRED WATER HEATERS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS. SHOP DRAWINGS FOR THE PVC
 INTAKE AND EXHAUST DUCTS SHOWING TOTAL RUN DISTANCES
 AND CLEARANCE DISTANCES FOR THE AIR INTAKE AND EXHAUST
 TERMINATION LOCATIONS SHALL BE SUBMITTED WITH AN
 APPROVAL STAMP BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-07-13 Cont ID  
Sent By ccole Date 2018-07-13 Time 15:42 Rev Time 0.00
Received By ccole Date 2018-07-12 Time 17:33 Sent To  
Notes
2018-07-13 16:55:373RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 BUILDING
 PERMIT #17110874
 OLD CITY HALL/MARRIOTT HOTEL
 7/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-101, LS-101: FIRE DAMPERS MISSING AT THE
 16X14 DUCT PENETRATING THE EXIT CORRIDOR/VESTIBULE
 FIRE-RATED WALL, AND THE TWO14X14 DUCTS PENETRATING THE
 CONFERENCE/MECH FIRE-RATED WALL.
  
 2) M-101: PROVIDE VENTILATION FOR THE FIRE PUMP ROOM-
 SEE SECTION 11.3.2.1 NFPA 20.
  
 3) M-101: PROVIDE EXHAUST VENTILATION FOR THE
 LINEN/TRASH CHUTE ROOM- TABLE 6-4 ASHRAE 62.1-10.
  
 4) M-101 & M600: VENTILATION AND AIR BALANCE
 CALCULATIONS FOR THE FUTURE LAUNDRY HAVE NOT BEEN
 PROVIDED, AND NO MEANS OF PROVIDING THE REQUIRED O/A
 FOR OCCUPANTS IS SHOWN ON THE PLAN. PLEASE CLARIFY IF A
 REVISION TO THE PLAN WILL BE PROVIDED FOR THE LAUNDRY,
 AND IF SO, PLEASE ADD IT TO THE LIST OF DEFERRED
 SUBMITTALS ON SHEET M-001.
  
 5) M-102: THE KITCHEN EXHAUST FANS SHALL HAVE A MINIMUM
 CLEARANCE OF 10' TO THE ADJACENT BUILDING WALLS AND
 PROPERTY LINE- SECTION 506.3.13.3 FBC-14 MECHANICAL.
 THE PLAN SHOWS 5'9-13/32 AND 5'4" WHICH IS
 NON-COMPLIANT.
  
 6) M-102: CLARIFY HOW ACCESS TO THE KSF, KEF'S AND
 OTHER APPLIANCES AND EQUIPMENT ON THE ROOF WILL BE
 PROVIDED FOR SERVICE AND REPLACEMENT- SECTION 306.1
 FBC-14 MECH.
  
 7) M-101,M-105: WHERE REQUIRED BY 606.2.1 FBC-14
 MECHANICAL, THE DUCT SMOKE DETECTORS SHALL BE INSTALLED
 IN THE RETURN AIR SYSTEMS OF THE AIR HANDLERS.THE PLANS
 ARE SHOWING THEM IN THE SUPPLY SIDES.
  
 8) M-101, 102, 103, 104, 105, 705: THE FIRE/SMOKE
 DAMPERS AT SHAFT PENETRATIONS AND OTHER PENETRATION
 LOCATIONS WILL HAVE TO BE MOTORIZED AS PART OF THE
 SMOKE CONTROL SYSTEM. PLEASE PROVIDE THE MOTORIZED
 DAMPER SYMBOLS AT THE REQUIRED LOCATIONS.
  
 9) M-101, 102, 103, 104, 105, 705: PLEASE PLACE VERY
 APPARENT NOTES ON THE MEP PLANS TO INDICATE THE
 STAIRWELL VENTILATION CHASES ARE FOR STAIRWELL
 PRESSURIZATION ONLY AND NO OTHER PIPES, CONDUITS,
 RACEWAYS, WIRING, DUCTS ETC. SHALL BE PERMITTED IN
 THOSE CHASES.
  
 10) M-105: MORE INFORMATION ABOUT THE POOL ROOMS WILL
 BE REQUIRED EITHER UNDER THIS MAIN OR SEPARATE PERMIT.
 PLEASE PROVIDE A LIST OF CHEMICALS TO BE STORED IN THE
 ROOMS INCLUDING THEIR QUANTITIES AND SUBMIT MSDS
 SHEETS. A) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE POOL ROOM AND ADJACENT STORAGE ROOMS. PLEASE NOTE
 THAT HAZARDOUS EXHAUST DUCT SYSTEMS SHALL RUN
  
 INDEPENDENTLY OF OTHER EXHAUST DUCTS. THE CURRENT PLAN
 SHOWS INTERCONNECTION OF THE EXHAUST DUCTS FROM EACH
 STORAGE ROOM WHICH MAY BE PROHIBITED IF ONLY ONE OF THE
 ROOMS IS STORING CHEMICALS.
  
 11) M-105: PLEASE INCLUDE THE MAKEUP AND EXHAUST AIR
 CALCULATIONS FOR THE POOL ROOMS IN THE AIR BALANCE
 SCHEDULE.
  
 12) M-001: PLEASE ADD THE FOLLOWING ITEMS TO THE
 DEFERRED SUBMITTALS LIST: MANUFACTURER'S SPECIFICATIONS
 FOR THE GENERATOR, DUCT SMOKE DETECTORS, C02 SENSORS,
 DRYERS, AND FACTORY MADE ACCESS PANELS,
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-13 Cont ID  
Sent By ccole Date 2018-04-13 Time 09:23 Rev Time 0.00
Received By ccole Date 2018-04-12 Time 10:48 Sent To  
Notes
2018-04-13 09:33:512ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17110874
 OLD CITY HALL/MARRIOTT HOTEL
 4/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED
 PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE
 ENGINEER OF RECORD.
 ALL 1ST REVIEW COMMENTS NOT COMPLETELY RESOLVED ARE
 LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER.
  
 1) THE RESUBMITTED AC SUMMARY CALCULATIONS ARE NOT
 ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER.
 PLEASE NOTE THAT THE OUTDOOR DRYBULB TEMPERATURE SHOWN
 ON M-600 DOES NOT MATCH THE TEMPERATURE SHOWN IN THE
 CALCS.
  
 2) THE REVISED ENERGYGAUGE SUBMITTAL IS MISSING
 COMPLIANCE DATA FOR THE ODU-L5 SYSTEM.
  
 3) IF NOT PROVIDING A COMMISSIONING PLAN AT THIS TIME,
 PLEASE PROVIDE A NOTE ON THE PLANS TO INDICATE A PLAN
 WILL BE PROVIDED AS A DEFERRED SUBMITTAL.
  
 4) THE REQUESTED AIR BALANCE CALCULATIONS WERE NOT
 PROVIDED.
  
 5) THE ENGINEER'S RESPONSE TO THE COMMENT #5 REQUESTING
 THE SMOKE CONTROL RATIONAL ANALYSIS STATES "THE
 BUILDING DOES NOT INCLUDE A SMOKE CONTROL SYSTEM AS IT
 IS NOT REQUIRED BY FLORIDA BUILDING CODE". THAT IS
 ACKNOWLEDGED, HOWEVER THE PLANS ARE INDICATING A SMOKE
 CONTROL SYSTEM IS BEING INSTALLED. REFER TO SHEET M-704
 SMOKE CONTROL SEQUENCE AND REQUIREMENTS, M-705 SMOKE
 CONTROL RISERS, & M-706 SMOKE CONTROL PANEL GRAPHIC.
 EVIDENTLY THIS BUILDING CONTAINS A SMOKE CONTROL
 SYSTEM. PLEASE REFER TO SECTION 909.4 AND PROVIDE THE
 ANALYSIS. ADDITIONALLY PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING MECHANICAL CODE SECTIONS:
 513.10 EQUIPMENT.
 EQUIPMENT SUCH AS, BUT NOT LIMITED TO, FANS, DUCTS,
 AUTOMATIC DAMPERS AND BALANCE DAMPERS SHALL BE SUITABLE
 FOR THEIR INTENDED USE, SUITABLE FOR THE PROBABLE
 EXPOSURE TEMPERATURES THAT THE RATIONAL ANALYSIS
 INDICATES, AND AS APPROVED BY THE CODE OFFICIAL.
 513.10.1EXHAUSTFANS.
 COMPONENTS OF EXHAUST FANS SHALL BE RATED AND CERTIFIED
 BY THE MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE
 TO WHICH THE COMPONENTS WILL BE EXPOSED. THIS
 TEMPERATURE RISE SHALL BE COMPUTED BY:
 TS = (QC/MC)+ (TA) (EQUATION 5-4)
 WHERE:
 C = SPECIFIC HEAT OF SMOKE AT SMOKE-LAYER TEMPERATURE,
 BTU/LB F (KJ/KG ? K).
 M = EXHAUST RATE, POUNDS PER SECOND (KG/S).
 QC = CONVECTIVE HEAT OUTPUT OF FIRE, BTU/S (KW).
 TA = AMBIENT TEMPERATURE, F (K).
 TS = SMOKE TEMPERATURE, F (K).
 EXCEPTION: REDUCED TS AS CALCULATED BASED ON THE
 ASSURANCE OF ADEQUATE DILUTION
 513.10.2 DUCTS.
 DUCT MATERIALS AND JOINTS SHALL BE CAPABLE OF
 WITHSTANDING THE PROBABLE TEMPERATURES AND PRESSURES TO
 WHICH THEY ARE EXPOSED AS DETERMINED IN ACCORDANCE WITH
 SECTION 513.10.1. DUCTS SHALL BE CONSTRUCTED AND
 SUPPORTED IN ACCORDANCE WITH CHAPTER 6.
 DUCTS SHALL BE LEAK TESTED TO 1.5 TIMES THE MAXIMUM
 DESIGN PRESSURE IN ACCORDANCE WITH NATIONALLY ACCEPTED
 PRACTICES. MEASURED LEAKAGE SHALL NOT EXCEED 5 PERCENT
 OF DESIGN FLOW. RESULTS OF SUCH TESTING SHALL BE A PART
 OF THE DOCUMENTATION PROCEDURE. DUCTS SHALL BE
 SUPPORTED DIRECTLY FROM FIRE-RESISTANCE-RATED
 STRUCTURAL ELEMENTS OF THE BUILDING BY SUBSTANTIAL,
 NONCOMBUSTIBLE SUPPORTS.
 EXCEPTION: FLEXIBLE CONNECTIONS, FOR THE PURPOSE OF
 VIBRATION ISOLATION, THAT ARE CONSTRUCTED OF APPROVED
 FIRE-RESISTANCE-RATED MATERIALS.
 513.10.3 EQUIPMENT,INLETS AND OUTLETS.
 EQUIPMENT SHALL BE LOCATED SO AS TO NOT EXPOSE
 UNINVOLVED PORTIONS OF THE BUILDING TO AN ADDITIONAL
 FIRE HAZARD. OUTDOOR AIR INLETS SHALL BE LOCATED SO AS
 TO MINIMIZE THE POTENTIAL FOR INTRODUCING SMOKE OR
 FLAME INTO THE BUILDING. EXHAUST OUTLETS SHALL BE SO
 LOCATED AS TO MINIMIZE REINTRODUCTION OF SMOKE INTO THE
 BUILDING AND TO LIMIT EXPOSURE OF THE BUILDING OR
 ADJACENT BUILDINGS TO AN ADDITIONAL FIRE HAZARD.
 513.10.4 AUTOMATIC DAMPERS.
 AUTOMATIC DAMPERS, REGARDLESS OF THE PURPOSE FOR WHICH
 THEY ARE INSTALLED WITHIN THE SMOKE CONTROL SYSTEM,
 SHALL BE LISTED AND CONFORM TO THE REQUIREMENTS OF
 APPROVED RECOGNIZED STANDARDS.
 513.10.5 FANS.
 IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN FANS
 SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED FOR
 THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS BEING
 TWO. FANS SHALL BE SELECTED FOR STABLE PERFORMANCE
 BASED ON NORMAL TEMPERATURE AND, WHERE APPLICABLE,
 ELEVATED TEMPERATURE. CALCULATIONS AND MANUFACTURER'S
 FAN CURVES SHALL BE PART OF THE DOCUMENTATION
 PROCEDURES. FANS SHALL BE SUPPORTED AND RESTRAINED BY
 NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH THE
 STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT BE
 OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER (KILOWATTS)
 AS DETERMINED FROM MEASUREMENT OF ACTUAL CURRENT DRAW.
 MOTORS DRIVING FANS SHALL HAVE A MINIMUM SERVICE FACTOR
 OF 1.15.
 513.11 POWER SYSTEMS.
 THE SMOKE CONTROL SYSTEM SHALL BE SUPPLIED WITH TWO
 SOURCES OF POWER. PRIMARY POWER SHALL BE THE NORMAL
 BUILDING POWER SYSTEMS. SECONDARY POWER SHALL BE FROM
 AN APPROVED STANDBY SOURCE COMPLYING WITH CHAPTER 27 OF
 THE FLORIDA BUILDING CODE, BUILDING. THE STANDBY POWER
 SOURCE AND ITS TRANSFER SWITCHES SHALL BE IN A ROOM
 SEPARATE FROM THE NORMAL POWER TRANSFORMERS AND SWITCH
 GEAR AND VENTILATED DIRECTLY TO AND FROM THE EXTERIOR.
 THE ROOM SHALL BE ENCLOSED WITH NOT LESS THAN 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OF THE FLORIDA BUILDING
 CODE, BUILDING OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711 OF THE FLORIDA BUILDING
 CODE, BUILDING, OR BOTH. POWER DISTRIBUTION FROM THE
 TWO SOURCES SHALL BE BY INDEPENDENT ROUTES. TRANSFER TO
 FULL STANDBY POWER SHALL BE AUTOMATIC AND WITHIN 60
 SECONDS OF FAILURE OF THE PRIMARY POWER. THE SYSTEMS
 SHALL COMPLY WITH NFPA 70.
 513.11.1 POWER SOURCES AND POWERSURGES.
 ELEMENTS OF THE SMOKE MANAGEMENT SYSTEM RELYING ON
 VOLATILE MEMORIES OR THE LIKE SHALL BE SUPPLIED WITH
 UNINTERRUPTIBLE POWER SOURCES OF SUFFICIENT DURATION TO
 SPAN 15-MINUTE PRIMARY POWER INTERRUPTION. ELEMENTS OF
 THE SMOKE MANAGEMENT SYSTEM SUSCEPTIBLE TO POWER SURGES
 SHALL BE SUITABLY PROTECTED BY CONDITIONERS,
 SUPPRESSORS OR OTHER APPROVED MEANS.
 513.12 DETECTION AND CONTROL SYSTEMS.
 FIRE DETECTION SYSTEMS PROVIDING CONTROL INPUT OR
 OUTPUT SIGNALS TO MECHANICAL SMOKE CONTROL SYSTEMS OR
 ELEMENTS THEREOF SHALL COMPLY WITH NFPA 72 AND THE
 REQUIREMENTS OF CHAPTER 9 OF THE FLORIDA BUILDING CODE,
 BUILDING OR THE FLORIDA FIRE PREVENTION CODE. SUCH
 SYSTEMS SHALL BE EQUIPPED WITH A CONTROL UNIT COMPLYING
 WITH UL 864 AND LISTED AS SMOKE CONTROL EQUIPMENT.
 CONTROL SYSTEMS FOR MECHANICAL SMOKE CONTROL SYSTEMS
 SHALL INCLUDE PROVISIONS FOR VERIFICATION. VERIFICATION
 SHALL INCLUDE POSITIVE CONFIRMATION OF ACTUATION,
 TESTING, MANUAL OVERRIDE, THE PRESENCE OF POWER
 DOWNSTREAM OF ALL DISCONNECTS AND, THROUGH A
 PREPROGRAMMED WEEKLY TEST SEQUENCE REPORT, ABNORMAL
 CONDITIONS AUDIBLY, VISUALLY AND BY PRINTED REPORT.
 [513.12.1 WIRING.
 IN ADDITION TO MEETING THE REQUIREMENTS OF NFPA 70, ALL
 WIRING, REGARDLESS OF VOLTAGE, SHALL BE FULLY ENCLOSED
 WITHIN CONTINUOUS RACEWAYS.
 513.12.2 ACTIVATION.
 SMOKE CONTROL SYSTEMS SHALL BE ACTIVATED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, BUILDING OR THE FLORIDA
 FIRE PREVENTION CODE.
 513.12.3 AUTOMATIC CONTROL.
 WHERE COMPLETELY AUTOMATIC CONTROL IS REQUIRED OR USED,
 THE AUTOMATIC CONTROL SEQUENCES SHALL BE INITIATED FROM
 AN APPROPRIATELY ZONED AUTOMATIC SPRINKLER SYSTEM
 COMPLYING WITH THE FLORIDA FIRE PREVENTION CODE, FROM
 MANUAL CONTROLS THAT ARE READILY ACCESSIBLE TO THE FIRE
 DEPARTMENT, AND ANY SMOKE DETECTORS REQUIRED BY
 ENGINEERING ANALYSIS.
 [513.13 CONTROL-AIR TUBING.
 CONTROL-AIR TUBING SHALL BE OF SUFFICIENT SIZE TO MEET
 THE REQUIRED RESPONSE TIMES. TUBING SHALL BE FLUSHED
 CLEAN AND DRY PRIOR TO FINAL CONNECTIONS. TUBING SHALL
 BE ADEQUATELY SUPPORTED AND PROTECTED FROM DAMAGE.
 TUBING PASSING THROUGH CONCRETE OR MASONRY SHALL BE
 SLEEVED AND PROTECTED FROM ABRASION AND ELECTROLYTIC
 ACTION.
 513.13.1 MATERIALS.
 CONTROL-AIR TUBING SHALL BE HARD-DRAWN COPPER, TYPE L,
 ACR IN ACCORDANCE WITH ASTM B 42, ASTM B 43, ASTM B 68,
 ASTM B 88, ASTM B 251 AND ASTM B 280. FITTINGS SHALL BE
 WROUGHT COPPER OR BRASS, SOLDER TYPE IN ACCORDANCE WITH
 ASME B 16.18 OR ASME B 16.22. CHANGES IN DIRECTION
 SHALL BE MADE WITH APPROPRIATE TOOL BENDS. BRASS
 COMPRESSION-TYPE FITTINGS SHALL BE USED AT FINAL
 CONNECTION TO DEVICES; OTHER JOINTS SHALL BE BRAZED
 USING A BCUP5 BRAZING ALLOY WITH SOLIDUS ABOVE 1,100?F
 (593?C) AND LIQUIDS BELOW 1,500?F (816?C). BRAZING FLUX
 SHALL BE USED ON COPPER-TO-BRASS JOINTS ONLY.
 EXCEPTION: NONMETALLIC TUBING USED WITHIN CONTROL
 PANELS AND AT THE FINAL CONNECTION TO DEVICES PROVIDED
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 1. TUBING SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 602.2.1.3.
 2. TUBING AND CONNECTED DEVICE SHALL BE COMPLETELY
 ENCLOSED WITHIN A GALVANIZED OR PAINT-GRADE STEEL
 ENCLOSURE HAVING A MINIMUM THICKNESS OF 0.0296 INCH
 (0.7534 MM) (NO. 22 GAGE). ENTRY TO THE ENCLOSURE SHALL
 BE BY COPPER TUBING WITH A PROTECTIVE GROMMET OF
 NEOPRENE OR TEFLON OR BY SUITABLE BRASS COMPRESSION TO
 MALE BARBED ADAPTER.
 3. TUBING SHALL BE IDENTIFIED BY APPROPRIATELY
 DOCUMENTED CODING.
 4. TUBING SHALL BE NEATLY TIED AND SUPPORTED WITHIN THE
 ENCLOSURE. TUBING BRIDGING CABINETS AND DOORS OR
 MOVEABLE DEVICES SHALL BE OF SUFFICIENT LENGTH TO AVOID
 TENSION AND EXCESSIVE STRESS. TUBING SHALL BE PROTECTED
 AGAINST ABRASION. TUBING SERVING DEVICES ON DOORS SHALL
 BE FASTENED ALONG HINGES.
 513.13.2 ISOLATION FROM OTHER FUNCTIONS.
 CONTROL TUBING SERVING OTHER THAN SMOKE CONTROL
 FUNCTIONS SHALL BE ISOLATED BY AUTOMATIC ISOLATION
 VALVES OR SHALL BE AN INDEPENDENT SYSTEM.
 513.13.3 TESTING.
 TEST CONTROL-AIR TUBING AT THREE TIMES THE OPERATING
 PRESSURE FOR NOT LESS THAN 30 MINUTES WITHOUT ANY
 NOTICEABLE LOSS IN GAUGE PRESSURE PRIOR TO FINAL
 CONNECTION TO DEVICES.
 513.14 MARKING AND IDENTIFICATION.
 THE DETECTION AND CONTROL SYSTEMS SHALL BE CLEARLY
 MARKED AT ALL JUNCTIONS, ACCESSES AND TERMINATIONS.
 513.15 CONTROL DIAGRAMS.
 IDENTICAL CONTROL DIAGRAMS SHALL BE PROVIDED AND
 MAINTAINED AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE.
 513.16 FIRE FIGHTER'S SMOKE CONTROL PANEL.
 A FIRE FIGHTER'S SMOKE CONTROL PANEL FOR FIRE
 DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
 513.17 SYSTEM RESPONSE TIME.
 SMOKE CONTROL SYSTEM ACTIVATION SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE.
 513.18 ACCEPTANCE TESTING.
 DEVICES, EQUIPMENT, COMPONENTS AND SEQUENCES SHALL BE
 TESTED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
 513.19 SYSTEM ACCEPTANCE.
 ACCEPTANCE OF THE SMOKE CONTROL SYSTEM SHALL BE IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 5) CONTINUED. IN REFERENCE TO SECTION 513.10.5 LISTED
 ABOVE, INDICATE THE MAKES OF THE PRESSURIZATION AND
 SMOKE EXHAUST FANS, AND VERIFY THAT THEY ARE UL LISTED
 AS POWER VENTILATORS FOR SMOKE CONTROL SYSTEMS.
  
 6) ACKNOWLEDGED: SMOKE CONTROL FANS, DUCTS, MOTORIZED
 DAMPERS, FIRE/SMOKE DAMPERS ARE TO BE DEFERRED
 SUBMITTALS.
  
 7, 8, 9) ACKNOWLEDGED THAT THE GENERATOR IS LOCATED
 OUTSIDE OF THE BUILDING. PLEASE PROVIDE AN ENLARGED
 DRAWING SHOWING THE EXHAUST PIPING RUN AND DISCHARGE
 LOCATION, REQUIRED EXHAUST OUTLET CLEARANCES TO
 BUILDING OPENINGS, AND WIND LOAD ENGINEERING FOR TIE
 DOWN OF THE UIOT AND ALL ASSOCIATED EXTERIOR
 COMPONENTS. SUBMIT MANUFACTURER'S SPECIFICATIONS
 APPROVED BY THE EOR.
  
 ADVISORY: IT IS IMPORTANT TO NOT THAT SOUND MAY BE AN
 ISSUE WITH THE GENERATOR LOCATED IN CLOSE PROXIMITY OF
 THE GARAGE. PLEASE PROVIDE THE DBA OF THE GENERATOR
  
 12) ACKNOWLEDGED. DUCT SMOKE DETECTOR NOTE ADDED TO AC
 EQUIPMENT SCHEDULE. PLEASE PROVIDE SYMBOLS ON THE
 MECHANICAL LAYOUT PLANS TO SHOW THE LOCATIONS.
  
 16) ACKNOWLEDGED THAT THE FABRIC DUCT WILL BE A
 DEFERRED SUBMITTAL, AND THE PRODUCT SHALL MEET THE
 REQUIREMENTS OF UL 181.
  
 17) AS PREVIOUSLY REQUESTED PLEASE SHOW THE LOCATIONS
 OF ACCESS PANELS FOR ABOVE CEILING AC UNITS.
  
 19) 2ND REQUEST FOR DUCT SIZES OR DUCT SCHEDULE TO BE
 PLACED ON SHEET M-101.
  
 20) PLEASE REMOVE THE 6070 CFMS OF EA FOR OAU-3 SHOWN
 IN THE SCHEDULE ON M-600.
  
 21) THE MAKEUP AIR FOR THE KITCHEN EXHAUST HOOD IS INTO
 COMBUSTION AIR FOR THE APPLIANCES. MAKEUP AIR IS
 INTRODUCED DIRECTLY INTO THE HOOD CANOPY FOR THE
 EXHAUST SYSTEM. PLEASE PROVIDE ANOTHER MEANS OF
 PROVIDING COMBUSTION AIR EITHER FROM THE SPACE OR
 PROVIDED MECHANICALLY- SECTION 304 FBC-14 FUEL GAS.
  
 22) THE REQUESTED AIR BALANCE CALCULATION WAS NOT
 PROVIDED.
  
 23, 29, 39) 2ND REQUEST FOR LOCATIONS OF REFRIGERANT
 CHASES FOR THE VRF SYSTEMS. PLEASE NOTE THAT CONTRACTOR
 SHOP DRAWINGS SHALL BE APPROVED BY THE EOR AND
 SUBMITTED PRIOR TO 1ST INSPECTION.
  
 24) 2ND REQUEST FOR CLEARANCE DISTANCE MEASUREMENTS FOR
 THE EXHAUST FANS TO THE BUILDING WALLS- SECTION
 506.3.13.
  
 25) COMMENT NOT COMPLETELY ADDRESS. O/A FOR ELEVATOR
 LOBBY NOT PROVIDED.
  
 31) THE REVISED LIFE SAFETY SHEETS LS101 & LS102 HAVE
 NOT BEEN CORRECTED TO SHOW THE REQUIRED FIRE RATED
 SEPARATION BETWEEN THE SMOKE PURGE DUCT AND THE
 STAIRWELL ENCLOSURE- SECTION 1022.5 FBC-14 BUILDING.
  
 32) ACKNOWLEDGED THAT THE EA IS SUB-DUCTED INTO THE
 FIRE-RATED SHAFTS BUT FIRE DAMPERS STILL MISSING AT THE
 O/A DUCT PENETRATIONS INTO THE SHAFTS.
  
 33) PROVIDE THE SEQUENCE OF OPERATION FOR POOL
 EQUIPMENT EF-8, AND PROVIDE MAKEUP AIR FOR THE STORAGE
 ROOM EXHAUST SYSTEMS.
  
 35) ACKNOWLEDGED THAT THE POOL HEATER WILL BE A
 DEFERRED SUBMITTAL.
  
 36) THE REVISED LIFE SAFETY SHEETS LS101 & LS102 HAVE
 NOT BEEN CORRECTED TO SHOW THE REQUIRED FIRE RATED
 SEPARATION BETWEEN THE SMOKE PURGE DUCT AND THE
 STAIRWELL ENCLOSURE- SECTION 1022.5 FBC-14 BUILDING.
  
 38) 2ND REQUEST FOR DUCT SIZES OR DUCT SCHEDULE TO BE
 PLACED ON SHEET M-105.
  
 40) ACKNOWLEDGED. DUCT SMOKE DETECTOR NOTE ADDED TO AC
 EQUIPMENT SCHEDULE. PLEASE PROVIDE SYMBOLS ON THE
 MECHANICAL LAYOUT PLANS TO SHOW THE LOCATIONS.
  
 42) AS PREVIOUSLY REQUESTED PLEASE SHOW THE LOCATIONS
 OF ACCESS PANELS FOR ABOVE CEILING AC UNITS.
  
 43) REQUESTED AIR BALANCE CALCULATION NOT PROVIDED.
  
 44) ACKNOWLEDGED THAT MANUFACTURER'S SPECIFICATIONS FOR
 THE OAU SYSTEMS WILL BE DEFERRED SUBMITTAL.
  
 45) ACKNOWLEDGED THAT WIND LOAD ENGINEERING FOR ALL
 EXTERIOR MOUNTED MECHANICAL EQUIPMENT AND APPLIANCES
 WILL BE DEFERRED SUBMITTALS.
  
 46) ACKNOWLEDGED THAT REFRIGERANT PIPING RISER DRAWINGS
 WILL BE A DEFERRED SUBMITTAL.
  
 48) ACKNOWLEDGED THAT MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS WATER HEATERS AND COMBUSTION AIR INTAKE DUCT
 AND EXHAUST VENTS WILL BE A DEFERRED SUBMITTAL.
  
 49) PLEASE PROVIDE ON THE PLAN, OR AS A SUBMITTAL
 DOCUMENT, A MASTER LIST OF ALL DEFERRED SUBMITTALS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By ccole Date 2018-02-02 Time 10:17 Rev Time 0.00
Received By ccole Date 2018-01-31 Time 15:10 Sent To  
Notes
2018-02-02 10:18:251ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17110874
 OLD CITY HALL/MARRIOTT HOTEL
 2/1/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUMMARY AC CALCULATIONS ARE INCOMPLETE. PLEASE
 REVIEW SECTION C403.2.1 (EXCEPTION) FBC-14 ENERGY
 CONSERVATION:
  
 EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A
 REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF
 SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE
 BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING
 CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE
 FOLLOWING (BY ZONE):
 1. PROJECT NAME/OWNER
 2. PROJECT ADDRESS
 3. AREA IN SQUARE FEET
 4. SIZING METHOD USED
 5. OUTDOOR DRY BULB USE
 6. INDOOR DRY BULB
 7. OUTDOOR WET BULB USED
 8. GRAINS WATER (DIFFERENCE)
 9. TOTAL SENSIBLE GAIN
 10. TOTAL LATENT GAIN
 11. RELATIVE HUMIDITY
 12. TOTAL COOLING REQUIRED WITH OUTSIDE AIR
 13. TOTAL HEATING REQUIRED WITH OUTSIDE AIR
 PLEASE RESUBMIT REVISED, ELECTRONICALLY SIGNED AND
 SEALED CALCULATIONS.
 2) THE SUBMITTED FLORIDA ENERGYGAUGE COMPLIANCE REPORT
 IS THE 2017 VERSION, HOWEVER THE PROPOSED PROJECT WAS
 SUBMITTED UNDER THE 2014 CODE. PLEASE PROVIDE A REPORT
 USING THE FIFTH EDITION 2014 SOFTWARE. PLEASE NOTE THE
 FOLLOWING: A) THE REPORT IS MISSING COMPLIANCE DATA FOR
 OAU-1, 2, 3, & 4. B) THE DESIGN EFFICIENCIES FOR THE
 SYSTEMS APPEAR TO BE LISTED AS SEER INSTEAD OF EER.
 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE
 THAT A COPY OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED FOR REVIEW AT FINAL INSPECTION.
  
 4) IN ACCORDANCE WITH TABLE 403.3 MINIMUM VENTILATION
 CALCULATIONS FOR OUTDOOR AIR AND EXHAUST AIR ARE
 REQUIRED FOR ALL ROOMS AND SPACES. PLEASE PROVIDE A
 SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AND EXHAUST AIR FOR ALL ROOMS
 AND SPACES. PLEASE INCLUDE AIR BALANCE CALCULATIONS
 5) SMOKE CONTROL SYSTEMS: REFER TO SECTION 513 AND
 SUBMIT ALL RELATIVE DOCUMENTS INCLUDING:
 A) SECTION 513.3. SPECIAL INSPECTION AND TEST
 REQUIREMENTS.
 B) SECTION 513.4- 513.4.6. RATIONAL ANALYSIS
 C) SECTION 513.5. SMOKE BARRIER CONSTRUCTION.
 D) SECTION 513.6. PRESSURIZATION METHOD.
 6) SMOKE CONTROL EQUIPMENT SUBMITTALS SHALL BE REVIEWED
 AND APPROVED BY THE ENGINEER(S) OF RECORD AND SHALL
 INCLUDE:
 A) SECTION 513.10.2 & 513.10.5: PRESSURIZATION AND
 EXHAUST FANS.
 B) SECTION 513.10.2: DUCTS.
 C) SECTION 513.10.4: AUTOMATIC DAMPERS- FSD'S, FD'S,
 MOTORIZED O/A.
 7) REFER TO SECTION 513.11 POWER SYSTEMS: THE STANDBY
 POWER SOURCE AND IT'S TRANSFER SWITCHES DO NOT APPEAR
 TO BE VENTILATED TO AND FROM THE EXTERIOR, AND THE
 GENERATOR ROOM DOES NOT APPEAR TO BE FULLY ENCLOSED IN
 1-HOUR FIRE RATED BARRIERS- SEE SHEETS AS-101, LS-101,
 A-101, M-101, E-201, E-301. THESE PLANS APPEAR TO
 INDICATE THE GENERATOR ROOM OPEN INTO THE ADJACENT
 APARTMENT BUILDING ENCLOSED GARAGE. PLEASE NOTE THAT
 THE 1ST FLOOR AND SITE PLANS FOR THE ADJACENT APARTMENT
 BUILDING (PERMIT #17110075) DO NOT SHOW THE GENERATOR
 ROOM AT THE COMMON WALL BETWEEN THE BUILDINGS.
 8) M-101: LABEL THE GENERATOR ROOM AND MATCH THE ROOM
 SIZE AND CONFIGURATION WITH THE FLOOR PLAN DRAWING
 A-101. PROVIDE COMPLETE DRAWINGS THAT DEPICT THE
 GENERATOR IN THE ROOM WITH ALL WORKING CLEARANCES PER
 MANUFACTURER'S SPECIFICATIONS. SHOW THE LOCATIONS OF
 THE RADIATOR EXHAUST, THE MAKEUP AIR OPENING, AND THE
 ENGINE EXHAUST PIPE. PROVIDE EXHAUST PIPE DETAILS
 INCLUDING TYPE AND SIZE OF PIPE, LENGTH OF RUN AND
 TERMINATION LOCATION WITH REQUIRED CLEARANCES. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 REVIEWED AND APPROVED BY THE EOR.
 9) M-101: THE EXHAUST FROM THE EF-2 AND EF-3 CANNOT
 DISCHARGE INTO THE GENERATOR ROOM AND THE ENCLOSED
 GARAGE. PLEASE RELOCATE BOTH TERMINATIONS TO THE
 OUTDOORS- SECTION 501.3.
 10) M-101: NO TEXT PROVIDED FOR REFERENCE NOTES #6, 7,
 8, 9, & 10.
 11) M-101: IDU-L1-3 APPEARS TO BE RETURNING AIR FROM
 THE KITCHEN AND RECIRCULATING IT INTO THE DINING ROOM
 WHICH IS PROHIBITED PER SECTION 403.3.2.1(3).
 12) M-101: DUCT SMOKE DETECTORS SHALL BE INSTALLED IN
 THE RETURN AIR SYSTEMS OF IDU'S- L1-1, L1-2, L1-3,
 L2-3, L2-4, L3-2, & L3-3- SECTION 606.2.1.
 13) M-101: MULTIPLE FIRE DAMPERS MISSING FOR DUCTS
 PENETRATING THE FIRE-RATED WALLS AT THE FIRE COMMAND
 ROOM, FUTURE LAUNDRY, AND LINEN CHUTE ROOM- SECTION
 607.5.2.
 14) M-101: IT DOESN'T APPEAR ADEQUATE O/A IS BEING
 PROVIDED TO THE BRANDING/FLEX-SPACE. THE PLAN IS
 INDICATING ONLY 490 CFMS FOR THIS LARGE AREA. PLEASE
 SEE COMMENT #4 ABOVE AND PROVIDE O/A CALCULATIONS.
 15) M-101: IT APPEARS THAT THE TRANSFER DUCTS AT THE
 MENS AND WOMENS RESTROOMS ARE NOT POSITIONED PROPERLY
 ON THE PLAN.
 16) M-101: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE FOR THE FABRIC DUCT.
 PLEASE NOTE THAT NON-METALLIC DUCTS SHALL COMPLY WITH
 UL 181- SECTION 603.5.
 17) M-101: CLARIFY HOW AIR IS BEING RETURNED TO
 IDU-L2-5 SUPPLYING THE GUEST REGISTRATION AREA.
 17) M-101 & A-101.1: THERE ARE MANY IDU'S AND EF'S
 LOCATED ABOVE GYPSUM CEILINGS. SHOW LOCATIONS OF
 DIMENSIONED ACCESS PANELS ON THE PLAN AND PROVIDE
 CONSTRUCTION DETAILS. PLEASE NOTE THAT NON-COMBUSTIBLE
 MATERIALS ARE REQUIRED FOR PANELS LOCATED ABOVE CEILING
 PLENUM SPACES.
 18) M-101 & A-101.1: COMBUSTIBLE WOOD CEILINGS ARE
 SHOWN ON THE PLAN IN THE GUEST/LOBBY AREA . PLEASE
 VERIFY THAT THESE CEILINGS ARE NOT FORMING PART OF AN
 ABOVE CEILING PLENUM SPACE- SECTION 602.2.1.
 19) M-101: MANY OF THE RIGID AND FLEXIBLE BRANCH DUCT
 SIZES ARE NOT SHOWN. IF USING THE SCHEDULE ON M-600,
 PLEASE CUT AND PASTE IT ON THIS AN ALL OTHER LAYOUT
 PLANS.
 20) M-101: PLEASE LABEL THE OAU-3 INLET ON THE PLAN AND
 CLARIFY HOW THE 6070 CFMS OF AIR IS BEING EXHAUSTED PER
 THE SCHEDULE ON M-600. SHOW THE LOCATION OF THE EXHAUST
 INLET OR OUTLET ON THE PLAN. PLEASE NOTE THAT AN ERV IS
 REQUIRED FOR EXHAUST SIZED AT 100 % OF THE AMOUNT OF
 SUPPLY AIR- TABLE C403.2.6 FBC-14 ENERGY CONSERVATION.
 21) M-101: COMBUSTION AIR IS REQUIRED FOR THE GAS-FIRED
 COOKING APPLIANCES IN THE KITCHEN. PLEASE SHOW HOW THE
 AIR WILL BE SUPPLIED AND PROVIDE CALCULATIONS IN
 COMPLIANCE WITH SECTION 304 FBC-14 FUEL GAS.
 ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 HOODS AND EXHAUST SYSTEMS, FIRE SUPPRESSION SYSTEMS,
 AND WALK-IN COOLERS AND FREEZERS. COMPLETE ENGINEERED
 DRAWINGS AND SUBMITTALS ARE REQUIRED FOR EACH PERMIT.
 PLEASE NOTE: A)WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE ROOF TOP FANS WILL BE REQUIRED. B) THE MAKEUP
 AIR TEMPERATURE SHALL BE IN COMPLIANCE WITH SECTION
 508.1.1
 22) M-101: PROVIDE AIR BALANCE CALCULATIONS.
 23) M-101: CHASES FOR REFRIGERANT LINES NOT SHOWN.
 24) M-102: KEF-1-1, 1-2, & 1-3 APPEAR TO BE WITHIN 10'
 OF THE BUILDING EXTERIOR WALLS, AND ALSO THE ADJACENT
 PARKING GARAGE WALL. REFER TO SECTION 506.3.13 AND
 PROVIDE CLEARANCE DISTANCE MEASUREMENTS ON THE PLANS.
 25) M-102: OUTDOOR VENTILATION AIR IS REQUIRED FOR THE
 ELEVATOR LOBBY, THE EMPLOYEE BREAKROOM, AND THE
 ENGINEER'S SHOP- TABLE 403.3.
 26) M-102: ROOF LADDER CONTINUATION OR TERMINATION FROM
 GENERATOR ROOM ON THE 1ST FLOOR IS NOT SHOWN.
 27) M-102: SHOW THE LOCATION OF NOTE #12 ON THE PLAN-
 16X8 O/A DUCT UP IN SHAFT.
 28) M-102 & M-103: DAMPERS MISSING AT THE EXHAUST DUCT
 PENETRATIONS AT THE GUEST-BATHS/SHAFTS.
 29) M-102 & M-103: CHASES FOR REFRIGERANT LINES NOT
 SHOWN.
 30) M-103: SHOW THE LOCATION OF NOTE #12 ON THE PLAN-
 16X8 O/A DUCT UP IN SHAFT.
 31) M-104: THE SMOKE PURGE MAKEUP AIR DUCT IN THE
 INTERIOR STAIRWELL ENCLOSURE IS PROHIBITED PER SECTION
 1022.5 FBC-14 BUILDING.
 32) M-104: MULTIPLE MISSING FIRE/SMOKE DAMPERS AT O/A
 AND EXHAUST DUCTS PENETRATING THE FIRE-RATED SHAFTS.
 33) M-105: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE POOL EQUIPMENT AND STORAGE ROOMS, AND INDICATE HOW
 MAKEUP AIR IS BEING PROVIDED FOR THE EXHAUST SYSTEMS.
 PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE STORED
 IN THE ROOMS, PROVIDE THEIR HAZARD CLASSIFICATIONS AND
 THE STORAGE QUANTITIES. SUBMIT MSDS SHEETS FOR ALL
 CHEMICALS AND MATERIALS.
 34) M-105: IN ACCORDANCE WITH SECTION 510.4 THE EXHAUST
 FROM THE POOL EQUIPMENT ROOM AND ASSOCIATED STORAGE
 ROOMS SHALL RUN INDEPENDENTLY AND DIRECTLY TO THE
 EXTERIOR OF THE BUILDING.
 35) M-105: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED POOL HEATERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304 FBC-14 FUEL GAS. SUBMIT SPECS FOR
 ALL EQUIPMENT.
 36) M-105: THE 14X14 DUCT IN THE INTERIOR STAIRWELL
 ENCLOSURE IS PROHIBITED PER SECTION 1022.5 FBC-14
 BUILDING.
 37) M-105: REFERENCE NOTES #2, 3, & 4 ARE MISLABELED ON
 THE PLANS.
 38) M-105: MANY OF THE RIGID AND FLEXIBLE BRANCH DUCT
 SIZES ARE NOT SHOWN. IF USING THE SCHEDULE ON M-600,
 PLEASE CUT AND PASTE IT ON THIS AN ALL OTHER LAYOUT
 PLANS.
 39) M-105: CHASES FOR REFRIGERANT LINES NOT SHOWN.
 40) M-105: DUCT SMOKE DETECTORS SHALL BE INSTALLED IN
 THE RETURN AIR SYSTEMS OF IDU?S 8B3-1, 8B3-2, 8B3-3, &
 8B4-7- SECTION 606.2.1.
 41) M-105: PROVIDE A CALCULATION TO VERIFY THE 240 CFMS
 OF O/A PROVIDED TO THE LOBBY IS ADEQUATE FOR THAT AREA
 AND TO ALSO PROVIDE MAKEUP AIR FOR THE RESTROOMS-
 SECTION 601.2
 42) M-105 & A-104.1: THERE ARE MANY IDU'S AND EF'S
 LOCATED ABOVE GYPSUM CEILINGS. SHOW LOCATIONS OF
 DIMENSIONED ACCESS PANELS ON THE PLAN AND PROVIDE
 CONSTRUCTION DETAILS. PLEASE NOTE THAT NON-COMBUSTIBLE
 MATERIALS ARE REQUIRED FOR PANELS LOCATED ABOVE CEILING
 PLENUM SPACES.
 43) M-105: PROVIDE AIR BALANCE CALCULATIONS.
 44) M-600: THE O/A AND EXHAUST CFMS SHOWN IN SCHEDULE
 FOR THE OAU'S INDICATES THAT ERV'S ARE REQUIRED PER
 TABLE C403.2.6. PLEASE INDICATE IF THE OAU'S ARE
 EQUIPPED WITH THEM.
 45) M-701 & M-702: SITE SPECIFIC WIND LOAD ENGINEERING
 IS REQUIRED FOR INSTALLATION OF ALL THE ROOFTOP
 MECHANICAL EQUIPMENT. PLEASE PROVIDE THE WIND LOAD
 DESIGN CRITERIA ON THE PLAN, AND COMPLETE DETAILS FOR
 ATTACHING THE EQUIPMENT AND CURBS TO THE ROOF
 STRUCTURE- SEE SECTION 1609 FBC-14 BUILDING. REFER TO
 TABLE 1509.6.5 FOR REQUIRED CLEARANCES FOR CONDENSERS
 TO BE MOUNTED ON STANDS, AND SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE STAND.
 46) M-703: PLEASE PROVIDE A REFRIGERANT RISER DRAWING
 THAT IS AN ACTUAL DEPICTION OF THE PIPING RUNS AND
 LENGTHS. VERIFY THE RUNS ARE IN COMPLIANCE WITH
 MANUFACTURER'S SPECIFICATIONS.
 47) M-704: PLEASE INCLUDE THE SMOKE PURGE SYSTEM IN THE
 SEQUENCE OF OPERATION.
 48) P-401: SHOW THE LOCATIONS OF THE GAS WATER HEATER
 EXHAUST VENTS OUTLETS, AND THE COMBUSTION AIR INTAKES,
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 COMPONENTS. IT APPEARS BY THE LOCATION OF THE APPLIANCE
 THAT THE EXHAUST VENT WILL HAVE TO RUN THROUGH ALL THE
 FLOORS OF THE BUILDING TO THE ROOF VIA A CHASE OR
 SHAFT. PLEASE PROVIDE DETAILS.
 49) REQUIRED SUBMITTALS: SMOKE CONTROL FANS, AC STANDS
 AND RTU CURBS, FAN CURBS, EXHAUST AND AIR INTAKE
 LOUVERS, FIRE DAMPERS AND FIRE/SMOKE DAMPERS, DUCT
 SMOKE DETECTORS, GENERATOR, FIRE WRAPPING, CO2 SENSORS,
 FABRIC DUCTWORK, GAS DRYERS, AND GAS-FIRED WATER
 HEATERS AND FLUE VENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status N Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 15:21 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 14:32 Sent To  
Notes
2019-04-10 15:21:54BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 ADVISORY: MARRIOTT HOTEL 251 NARCISSUS
  
 THIS ELEVATION CERTIFICATE SUBMITTAL IS REVOKED FOR THE
 FOLLOWING:
  
 DUE TO THE DATE OF APPLICATION FOR THE HOTEL ON
 SEPTEMBER 7, 2017, THE BUILDING COMPLIES WITH THE
 STANDARD AT THE TIME OF PERMIT APPLICATION. THE
 BUILDING IS NOT REQUIRED TO PARTICIPATE IN THE NATIONAL
 FLOOD INSURANCE PROGRAM AND DOES NOT REQUIRE AN
 ELEVATION CERTIFICATE.
  
 HISTORY:
  
 PERMIT APPLICATION FOR THE MARRIOTT HOTEL WAS SEPTEMBER
 7, 2017. THE STRUCTURE IS LOCATED JUST OUTSIDE A
 SPECIAL FLOOD HAZARD AREA (SFHA) ON THE COMMUNITY FLOOD
 MAP, PANEL NUMBER 120229 0015B, EFFECTIVE DATE OF MARCH
 1, 1979, UTILIZING BASE FLOOD ELEVATION (BFE) DATUM
 NGVD 1929. ANOTHER STRUCTURE (THE RESTERAUNT) LOCATED
 WITHIN THIS PROJECT IS IN FLOOD ZONE A5, WITH A MINIMUM
 (BFE) OF 7 FEET NGVD 29. THE CITIES LOCAL FREEBOARD
 REQUIREMENT, AT TIME OF PERMIT APPLICATION, WAS 1 FOOT,
 MAKING THE ADJACENT BUILDING (THE RESTAURANT) MINIMUM
 FINISHED FLOOR ELEVATION ALSO REFERRED TO AS DESIGN
 FLOOD ELEVATION (DFE), 8 FEET NGVD 29. THE DESIGNER
 PLACED BOTH RESTAURANT AND HOTEL BUILDINGS FINISHED
 FLOOR ELEVATION (DFE) AT 9 FEET NGVD 29.
  
 THE NEW COMMUNITY FLOOD MAPS, EFFECTIVE DATE OF OCTOBER
 5, 2017, PANEL NUMBER 12099C 0583F, UTILIZES BASE FLOOD
 ELEVATION DATUM NAVD 1988, THIS NEW MAP PLACES THE
 HOTEL IN A SPECIAL FLOOD HAZARD AREA (SFHA) WITH A BASE
 FLOOD ELEVATION (BFE) OF 6 FEET NAVD 88. WITH THE
 CITY'S NEW 2 FOOT FREE BOARD, A BUILDING PERMITTED
 AFTER OCTOBER 5, 2017 WOULD REQUIRE A MINMUM FINISHED
 FLOOR ELEVATION (DFE) OF 8 FEET NAVD 88.
  
 THE AS-BUILT FINISHED FLOOR ELEVATION (DFE) OF THE
 HOTEL IS 9 FEET NGVD 29. IF THE HOTEL WERE PERMITTED
 TODAY (POST OCT. 5, 2017) THE FINISHED FLOOR ELEVATION
 (DFE) WOULD BE RECORDED AS 7.48 FEET NAVD 88, USING THE
 NEW 1988 DATUM. THIS WOULD PLACE THE HOTEL .52 FEET
 BELOW THE MINIMUM FINISHED FLOOR ELEVATION (DFE) OF 8
 FEET NAVD 88.
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 15:39 Rev Time 0.00
Received By shill Date 2018-07-14 Time 15:39 Sent To  
Notes
2018-07-14 15:39:32THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE
 REQUIRED PRIOR TO FINISHED FLOOR CONCRETE POUR
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE REQUIRED
 PRIOR TO CO OR TCO
  
 THE FOUNDATION PERMIT, WAS SUBMITTED UNDER THE 1979
 FIRMS. THEREFORE, THE MINIMUM DFE IS 8' NGVD29 (7' BFE
 + 1' FREEBOARD). APPLICANT COMPLIES WITH THE 2017 FIRMS
 + 2' FREEBOARD (APPROX 5.5' NAVD88 PER FIS + 2'
 FREEBOARD=7.5' NAVD88)
  
 THE DFE FOR THIS STRUCTURE IS 9' NGVD29
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By aclange Date 2018-04-02 Time 08:07 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 08:07 Sent To  
Notes
2018-07-14 13:23:37THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE
 REQUIRED PRIOR TO FINISHED FLOOR CONCRETE POUR
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE REQUIRED
 PRIOR TO CO OR TCO
  
 THE FOUNDATION PERMIT, WAS SUBMITTED UNDER THE 1979
 FIRMS. THEREFORE, THE MINIMUM DFE IS 8' NGVD29 (7' BFE
 + 1' FREEBOARD). APPLICANT COMPLIES WITH THE 2017 FIRMS
 + 2' FREEBOARD (APPROX 5.5' NAVD88 PER FIS + 2'
 FREEBOARD=7.5' NAVD88)
  
 THE DFE FOR THIS STRUCTURE IS 9' NGVD29
  
  
  
2018-04-02 08:08:06PROVISOS:
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By aclange Date 2018-01-31 Time 14:19 Rev Time 0.00
Received By aclange Date 2018-01-31 Time 14:19 Sent To  
Notes
2018-01-31 14:19:48SEE BUILDING REVIEW FOR NOTES.

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-09-21 Cont ID  
Sent By shill Date 2018-09-21 Time 12:17 Rev Time 0.00
Received By gjohnson Date 2018-09-21 Time 12:17 Sent To  
Notes
2018-09-21 12:21:41***PROVISO***
  
 GEORGE JOHNSON, PLUMBING PLANS EXAMINER II
 [email protected]
 561-805-6711
  
 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION
 GUIDE FOR FLUID APPLIED WATER PROOFING SHOWER PAN
 LINER. SHALL BE ON JOBSITE FOR INSPECTIONS.

Review Stop P PLUMBING
Rev No 4 Status F Date 2018-08-29 Cont ID  
Sent By gjohnson Date 2018-08-29 Time 12:19 Rev Time 0.00
Received By gjohnson Date 2018-08-29 Time 12:19 Sent To  
Notes
2018-08-29 12:19:44 
 4TH REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: IT APPEARS THAT THE PLUMBING COMMENT
 WERE NOT ADDRESSED I COULD NOT FIND A RESPONSE LETTER
 AND PREVIOUS COMMENT NOT COMPLIED WITH.
  
 1. SHT. P-902 + P-904 THE SANITARY STACKS ARE NOT
 LABELED THE SAME SHT. P902 IS LABELED WITH AN S THE
 STACKS ON P-904 ARE LABELED WITH AN X PLEASE LABEL THE
 STACKS ON EACH SHT. TO MATCH THE COINCIDING STACKS ON
 ALL SHTS. PER WPB AMEND TO FBC 107.2.1
 2. PREVIOUS COMMENT #3 SHT. A -512 DETAIL # 8 STILL
 SHOWS THE WATERPROOFING MEMBRANE STOPPING AT THE CURB
 AT THE SLIDING BOOKCASE GLASS PLEASE SHOW THE MEMBRANE
 RUNNING UP AND OVER THE CURB. PER FBC PL 417.5.2
 3. SHT. P-905 PLEASE SHOW THE PIPE SIZING ON THE
 PRESSURE RISER LOBBY DETAIL #1. PER WPB AMEND TO FBC
 107.2.1
 5. SHTS P-901 P-905 THE RISER LABELING DOES NOT MATCH
 SHT. 901 THE STACKS ARE LABELED WITH AN W THE STACKS ON
 SHT. 905 ARE LABELED WITH AN X PLEASE LABEL THEM ALL
 WITH COINCIDING LABELS WITH THE STACK NUMBER. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. 902 RISER S1 THE BATHROOM GROUP AT THE BOTTOM
 OF THE RISER IS NOT VENTED PROPERLY THE LAVATORY SHALL
 CONNECT UPSTREAM OF THE SOIL STACK IT CANNOT CONNECT TO
 THE SOIL STACK WITHOUT A SEPARATE VENT AND THERE SHALL
 BE A VENT BETWEEN THE SHOWER AND TOILET. PER FBC PL
 901.2.1, 912.1
 7. SHT. P-102 THE OVERFLOW STORM DRAINS THAT ARE
 TERMINATING ON THE WEST SIDE OF THE BUILDING WILL NEED
 TO BE RELOCATED, AS YOU KNOW THIS SIDE OF THE BUILDING
 IS NOT OPEN IT IS CONNECTED TO THE PARKING GARAGE
 APARTMENT BUILDING THE OVER FLOW ON THE NORTH END IS
 DUMPING INTO THE PARKING GARAGE AND THE OVER FLOW ON
 THE SOUTH END IS DUMPING INTO THE GENERATOR AREA AND
 WILL FLOOD THE GENERATOR IF THE OVERFLOW IS BEING USED.
 PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-07-30 Cont ID  
Sent By gjohnson Date 2018-07-30 Time 13:31 Rev Time 0.00
Received By gjohnson Date 2018-07-25 Time 14:19 Sent To  
Notes
2018-07-30 13:31:29 
 3RD REVIEW: FBC 2014 5TH EDITION
 PLUMBING COMMENTS:
 1. SHT. P-902 + P-904 THE SANITARY STACKS ARE NOT
 LABELED THE SAME SHT. P902 IS LABELED WITH AN S THE
 STACKS ON P-904 ARE LABELED WITH AN X PLEASE LABEL THE
 STACKS ON EACH SHT. TO MATCH THE COINCIDING STACKS ON
 ALL SHTS. PER WPB AMEND TO FBC 107.2.1
 2. PREVIOUS COMMENT #3 SHT. A -512 DETAIL # 8 STILL
 SHOWS THE WATERPROOFING MEMBRANE STOPPING AT THE CURB
 AT THE SLIDING BOOKCASE GLASS PLEASE SHOW THE MEMBRANE
 RUNNING UP AND OVER THE CURB. PER FBC PL 417.5.2
 3. SHT. P-905 PLEASE SHOW THE PIPE SIZING ON THE
 PRESSURE RISER LOBBY DETAIL #1. PER WPB AMEND TO FBC
 107.2.1
 4. ON ALL ISOMETRIC DRAWINGS PLEASE LABEL ON THE
 DIAGRAM WHEN A PIPE ENDS WHERE IT CONTINUES AND WITH
 COINCIDING LABEL. PER WPB AMEND TO FBC 107.2.1
 5. SHTS P-901 P-905 THE RISER LABELING DOES NOT MATCH
 SHT. 901 THE STACKS ARE LABELED WITH AN W THE STACKS ON
 SHT. 905 ARE LABELED WITH AN X PLEASE LABEL THEM ALL
 WITH COINCIDING LABELS WITH THE STACK NUMBER. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. 902 RISER S1 THE BATHROOM GROUP AT THE BOTTOM
 OF THE RISER IS NOT VENTED PROPERLY THE LAVATORY SHALL
 CONNECT UPSTREAM OF THE SOIL STACK IT CANNOT CONNECT TO
 THE SOIL STACK WITHOUT A SEPARATE VENT AND THERE SHALL
 BE A VENT BETWEEN THE SHOWER AND TOILET. PER FBC PL
 901.2.1, 912.1
 7. SHT. P-102 THE OVERFLOW STORM DRAINS THAT ARE
 TERMINATING ON THE WEST SIDE OF THE BUILDING WILL NEED
 TO BE RELOCATED, AS YOU KNOW THIS SIDE OF THE BUILDING
 IS NOT OPEN IT IS CONNECTED TO THE PARKING GARAGE
 APARTMENT BUILDING THE OVER FLOW ON THE NORTH END IS
 DUMPING INTO THE PARKING GARAGE AND THE OVER FLOW ON
 THE SOUTH END IS DUMPING INTO THE GENERATOR AREA AND
 WILL FLOOD THE GENERATOR IF THE OVERFLOW IS BEING USED.
 PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By gjohnson Date 2018-04-12 Time 14:56 Rev Time 0.00
Received By gjohnson Date 2018-04-11 Time 16:36 Sent To  
Notes
2018-04-12 14:57:031ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
 1. SHT. A512 DETAIL #5 THE FLUID APPLIED WATER PROOFING
 SHALL BE PITCHED TOWARD THE DRAIN AT A MIN OF 1/4" FT.
 AND SEALED AT THE DRAIN PLEASE SHOW THIS OR MAKE A NOTE
 ON THE PLAN. PER FBC PL 417.5.2
 2. THE WATER PROOFING MEMBRANE SHALL BE INSTALLED PER
 MANUFACTURE SPECIFICATIONS PLEASE PROVIDE MANUFACTURE
 SPECIFICATION AND INSTALLATION GUIDE. PER WPB AMEND TO
 FBC 107.2.1
 3. SHT. A512 DETAIL #4 THE WATER PROOFING MEMBRANE
 SHALL TURN UP ON ALL SIDES A MIN OF 2" ABOVE THE
 FINISHED THRESHOLD LEVEL IT APPEARS THAT THE DETAIL IS
 SHOWING IT STOPPING AT THE BOTTOM OF THE GLASS FOR THE
 BOOK SHELF WINDOW. PER FBC PL 417.5.2
 4. SHT. P- 904 PLEASE LABEL THE SOIL STACKS TO MATCH
 THE LABELING ON THE STACKS ON SHEET P-902. PER WPB
 AMEND TO FBC 107.2.1
 5. SHT. P-902 + 903 PLEASE SEPARATE THE WATER AND
 SANITARY ISOMETRICS AND REMOVE ANYTHING FROM THE
 DRAWING THAT IS NOT THE REQUIRED PIPING SUCH AS THE
 CARRIERS FOR THE TOILETS AS THE DRAWING ARE SHOWN NOW
 IT IS TO DIFFICULT TO DETERMINE CODE COMPLIANCE. PER
 WPB AMEND TO FBC 107.2.1
 6. PLEASE SHOW THE REQUIRED VALVE ON THE DROPS FOR THE
 GANG BATHS ON THE LOBBY LEVEL AND ROOF. PER FBC PL
 606.1(5)
 7. SHT. P-904,102, 104, 106 LABEL SANITARY RISER TO
 MATCH THE RISERS TAGS ON SHT. P902. PER WPB AMEND TO
 FBC 107.2.1
 8. SHT. P-905,101,103,105,107 PLEASE LABEL THE WATER
 RISER TO MATCH THE TAGS ON THE RISERS ON SHT. P-902.
 PER WPB AMEND TO FBC 107.2.1
 9. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE ROOF TOP
 BAR AND LOUNGE ALSO THE PLUMBING IN THE SERVICE AREA.
 PER WPB AMEND TO FBC 107.2.1
 10. WHAT IS ROOM 800D SERVICE AREA USED FOR IS THIS THE
 LAUNDRY? PLEASE CLARIFY AND SHOW ALL PLUMBING ON THE
 PLAN. PER WPB AMEND TO FBC 107.2.1
 11. PLEASE INDICATE ON THE PLAN WHAT SLOPE THE STORM
 PIPING IS BEING INSTALLED IF IT IS 1/8" FT. THERE IS
 PIPING THAT IS UNDERSIZED. PER FBC PL TABLE 1106.3
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By gjohnson Date 2018-01-31 Time 09:42 Rev Time 0.00
Received By gjohnson Date 2018-01-31 Time 09:42 Sent To  
Notes
2018-01-31 09:44:491ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. COULD YOU CLARIFY THE DIFFERENCE BETWEEN A MOBILITY
 ROLL IN TYPE SHOWER AND A MOBILITY NON ROLL IN WHAT
 TYPE OF SHOWER OR TUB WILL IT HAVE? PER WPB AMEND TO
 FBC 107.2.1
  
 2. SHT. A-102 RM 216 APPEARS TO BE AN ACCESSIBLE
 BATHROOM IT?S NOT LABELED AS ACCESSIBLE ALSO THE MATRIX
 ON SHT. A002 DOES NOT LIST 216 AS AN ACCESSIBLE PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. A-102 RM 243 IS LABELED AS M, R IT HAS A TUB IN
 IT ACCESSIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. A-103 SHOWS 2 ACCESSIBLE UNITS 316 AND 336 THE
 MATRIX ON SHT. A002 RMS. 336 AND 736 ARE NOT LISTED AS
 ACCESSIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2
 AND 606.3 PLEASE SHOW ON PLAN.
  
 6. SHT. A230 EMPLOYEE BATHROOM S 2.3 AND 2.4 PLEASE
 SHOW DIMENSIONS ON THE REQUIRED CLEAR FLOOR FOR THE
 TOILET AND LAVATORY AND THE TOILET COMPARTMENT DOORS
 SHALL NOT SWING INTO THE MINIMUM REQUIRED COMPARTMENT
 AREA. PER FBC ACC 606.2 AND 604.8.1.2
  
 7. SHT. A230 IN THE MEN?S AND WOMEN?S BATHROOMS 809
 +810 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE FOR THE
 TOILETS AND LAVATORY?S , THE CLEAR FLOOR SPACE FOR THE
 TOILET SHALL START AT THE REAR WALL AND SIDE WALL OF
 THE TOILET. ALSO IN THE MEN?S THE URINAL SHALL NOT BE
 LOCATED WITHIN THE CLEAR FLOOR SPACE OF THE TOILET. PER
 FBC PL 604.3.1 AND 604.3.2 AND 606.2
  
 8. SHT. A230 DETAIL #4 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S THE DOOR
 SHALL NOT SWING INTO THE REQUIRED CLEAR FLOOR SPACE,
 THE TOILET IN 817 IS SHOWN AT 19? THE CENTERLINE OF ALL
 ACCESSIBLE TOILETS SHALL BE 16? MIN 18? MAX OFF THE
 SIDE WALL. PER FBC ACC 604.3.1, 606.2, 604.8.1.2 AND
 604.2
  
 9. SHT. 230 DETAIL #1 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S, SHOW
 LOCATION OF THE LAVATORY LOCATED OUTSIDE OF THE
 ACCESSIBLE STALL. PER FBC ACC 604.3.1, 606.2
  
 10. SHT. A230 DETAIL #2 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S , THE CLEAR
 FLOOR SPACE FOR THE TOILET SHALL START AT THE REAR WALL
 AND SIDE WALL OF THE TOILET. PER FBC ACC 604.3.1, 606.2
  
 11. SHT. 230 DETAIL #3 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S, ? THE
 CENTERLINE OF ALL ACCESSIBLE TOILETS SHALL BE 16? MIN
 18? MAX OFF THE SIDE WALL. PER FBC ACC 604.3.1, 606.2,
 AND 604.2
  
 12. SHT. 231 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE
 FOR THE TOILETS AND LAVATORY?S , THE CLEAR FLOOR SPACE
 FOR THE TOILET SHALL START AT THE REAR WALL AND SIDE
 WALL OF THE TOILET, THE CENTERLINE OF ALL ACCESSIBLE
 TOILETS SHALL BE 16? MIN 18? MAX OFF THE SIDE WALL AND
 SHOW THE GRAB BARS IN THE AMBULATORY STALL. PER FBC ACC
 604.3.1, 606.2, AND 604.2
  
 13. SHT. A250 DETAIL #3 FOR K6 DOES NOT MATCH THE
 LAYOUT OF ROOM 216 ON THE FLOOR PLAN SHT A102 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 14. SHT. A243 DETAIL #7 IF THE BATHROOM IS ACCESSIBLE
 PLEASE SHOW CLEAR FLOOR SPACE FOR FIXTURES AND GRAB
 BARS. PER FBC ACC 604.3.1, 606.2, AND 604.2
  
 15. PLEASE PROVIDE DETAILS FOR THE MOUNTING HEIGHTS OF
 THE ACCESSIBLE FIXTURES, GRAB BARS, MIRRORS, TOILET
 PAPER DISPENSERS. PER FBC ACC CHAPTER 6
  
 16. PLEASE PROVIDE A SHOWER PAN DETAIL SHALL COMPLY
 WITH FBC PL 417
  
 17. PLEASE EXPAND THE ISOMETRICS FOR THE GANG BATH ON
 8TH FLOOR, POOL BATHE AND COMMON BATHROOMS ON GROUND
 FLOOR THEY ARE EXTREMELY HARD TO READ AS THEY ARE AND
 WHEN SAVED FOR OUR RECORD WILL NOT TRANSFER WELL. PER
 WPB AMEND TO FBC 107.2.1.4
  
 18. PLEASE PROVIDE A SANITARY COLLECTION ISOMETRIC
 SHOWING ALL THE RISERS LABELED TO MATCH THE FLOOR
 PLANS. WPB AMEND TO FBC 107.2.1
  
 19. PLEASE PROVIDE A COMPLETE WATER ISOMETRIC SHOWING
 THE MAIN, RISERS LABELED TO MATCH FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 20. PLEASE SHOW THE RISER NUMBERS FOR THE SANITARY,
 WATER AND STORM ON FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 21. PLEASE PROVIDE A STORM ISOMETRIC WITH THE SQFT AND
 SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2018-09-24 Cont ID  
Sent By gjohnson Date 2018-09-24 Time 12:04 Rev Time 0.00
Received By gjohnson Date 2018-09-24 Time 12:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-09-21 Cont ID  
Sent By shill Date 2018-09-21 Time 12:39 Rev Time 0.00
Received By shill Date 2018-09-21 Time 12:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 11:53 Rev Time 0.00
Received By shill Date 2018-09-02 Time 11:21 Sent To  
Notes
2018-09-02 11:53:52SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) ARE IN
 ACCORDANCE WITH FS 471, FS 481 AS (A,S,M,E,P). NEW
 SHEETS SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE
 REVIEW.
  
 2. ENERGY CALC SIGNATURE/SEAL OK
  
 3. COOLING CALCS SIGNATURE/SEAL OK
  
 4. SMOKE CONTROL SIGNATURE/SEAL OK
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 13:53 Rev Time 0.00
Received By shill Date 2018-07-14 Time 13:53 Sent To  
Notes
2018-07-14 13:53:30SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) ARE IN
 ACCORDANCE WITH FS 471, FS 481 AS (A,S,M,E,P). NEW
 SHEETS SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE
 REVIEW.
  
 2. ENERGY CALC SIGNATURE/SEAL OK
  
 3. COOLING CALCS SIGNATURE/SEAL OK
  
 4. SMOKE CONTROL SIGNATURE/SEAL OK
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-01-31 Cont ID  
Sent By aclange Date 2018-01-31 Time 11:42 Rev Time 0.00
Received By aclange Date 2018-01-31 Time 11:42 Sent To  
Notes
2018-01-31 11:43:47ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
  
 A AND S PAGES OK. ID PAGES DO NOT HAVE A SEAL.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By aclange Date 2018-04-02 Time 08:10 Rev Time 0.00
Received By aclange Date 2018-04-02 Time 08:10 Sent To  
Notes
2018-12-26 08:53:11PROVISO: ORIGINALS REQUIRED PRIOR TO COMMENCEMENT
  
  
 MIGUEL SANTIAGO, PE
 ECS
 BRANDON LEADLEY BN 6127
 REMOVE - JOSEAN A DUPREY, BN 7330 (NO LONGER WITH ECS)
 JAMES PEARSALL, BN 2477
  
2018-04-02 08:15:28PROVIDED WITH FOUNDATION PERMIT.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 09:53 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 09:25 Sent To  
Notes
2018-03-19 09:52:27 
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT AND RESUMES
 RECEIVED ARE NOT COMPLETE. ORIGINAL DOCUMENTS REQUIRED.
 EMAILED ERIC HANDLEY 3/19/18

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-17 Cont ID  
Sent By aaponte Date 2018-07-17 Time 16:36 Rev Time 0.00
Received By aaponte Date 2018-07-16 Time 17:01 Sent To  
Notes
2018-07-17 16:38:52PROVISO: 1. TRANSFORMER ENCLOSURE ALONG BANYAN BLVD
 SHALL BE DESIGNED AS A DECORATIVE ELEMENT ACCORDING TO
 THE FACADE DESIGN.
 2. STEPS ON NARCISSUS AVENUE NEED TO ALLOW FOR A
 MINIMUM 6 FEET WIDE CLEAR SIDEWALK, AND FINAL
 CONFIGURATION SHALL BE APPROVED WITH THE LANDSCAPE AND
 HARDSCAPE PERMITS.
 3. A LANDSCAPE AND HARDSCAPE PERMIT SHALL BE SUBMITTED
 FOR APPROVAL MAXIMUM TWO MONTHS AFTER BUILDING PERMIT
 IS ISSUED.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-18 Cont ID  
Sent By AA Date 2018-05-18 Time 16:10 Rev Time 0.00
Received By aaponte Date 2018-05-18 Time 15:06 Sent To  
Notes
2018-05-18 16:09:11OK, AGREEMENT SHALL BE APPROVED BEFORE CO.1. ENTRANCE
 CANOPY GOES OVER THE PROPERTY LINE. AN AGREEMENT WILL
 BE NECESSARY.
 SATISFIED 2. CANOPY COLUMNS ARE CREATING A NARROW PATH
 FOR PEDESTRIAN IN FRONT OF HOTEL ENTRANCE, 3.5' ONLY OF
 CLEAR SPACE. CAN THE COLUMNS BE REMOVED?
 NOT SATISFIED. TRANSFORMER ROOM IS ENCROACHING INTO THE
 MINIMUM 16 FEET SETBACK. PLEASE PROVIDE A SKETCH WITH
 DIMENSION TO INDICATE THE STATED 84% ACTIVE USE ALONG
 BANYAN. THE PROPOSED MECHANICAL ENCLOSURE PROJECTING
 OUT FROM FACADE HAS A BIG IMPACT ON BANYAN FRONTAGE.
 CAN IT BE RECESSESED FURTHER? 3. A NEW TRANSFORMER ROOM
 IS INDICATED ALONG THE BANYAN BOULEAVARD FRONTAGE.
 PLEASE SUBMIT A REVISED CALCULATION OF ACTIVE USES
 ALONG BANYAN TO CONFIRM COMPLIANCE WITH REQUIRED 80%.
 THE CALCULATION SHALL INCLUDE THE RESIDENTIAL BUILDING.
 WHAT IS THE ENCLOSUDE OF THAT TRANSFORMER ROOM?
 PARTIALLY SATISFIED, BANYAN SETBACK LINE NOT INDICATED
 ON SHEET A101. - 4. PLEASE INDICATE THE LOCATION OF THE
 PROPERTY LINE AND SETBACK LINE ON ALL FLOOR PLANS AND
 ELEVATIONS TO DETERMINE ANY ENCROACHMENTS.
 NOT SATISFIED, PLEASE INCLUDE INFORMATION INTHIS PERMIT
 SET. - 5. PLEASE PROVIDE A COMPLETE GROSS SQUARE
 FOOTAGE TABLE INCLUDING ALL THE BUILDINGS IN THE
 PROJECT.
 NOT SATISFIED, IF INFORMATION WILL BE APPROVED THROUGH
 OTHER PERMITS, A BASIC LAYOUT SHALL BE CONTAINED IN
 THIS PERMIT AS A REFERENCE ONLY WITH A NOTE STATING THE
 APPROVED PERMIT NUMBER - 6.PLEASE SUBMIT LANDSCAPE AND
 HARDSCAPE DRAWINGS, INCLUDING PHOTOMETRICS FOR
 STREETSCAPE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By AA Date 2018-02-09 Time 15:24 Rev Time 0.00
Received By aaponte Date 2018-02-09 Time 15:24 Sent To  
Notes
2018-02-09 15:29:321. ENTRANCE CANOPY GOES OVER THE PROPERTY LINE. AN
 AGREEMENT WILL BE NECESSARY.
 2. CANOPY COLUMNS ARE CREATING A NARROW PATH FOR
 PEDESTRIAN IN FRONT OF HOTEL ENTRANCE, 3.5' ONLY OF
 CLEAR SPACE. CAN THE COLUMNS BE REMOVED?
 3. A NEW TRANSFORMER ROOM IS INDICATED ALONG THE BANYAN
 BOULEAVARD FRONTAGE. PLEASE SUBMIT A REVISED
 CALCULATION OF ACTIVE USES ALONG BANYAN TO CONFIRM
 COMPLIANCE WITH REQUIRED 80%. THE CALCULATION SHALL
 INCLUDE THE RESIDENTIAL BUILDING. WHAT IS THE ENCLOSUDE
 OF THAT TRANSFORMER ROOM?
 4. PLEASE INDICATE THE LOCATION OF THE PROPERTY LINE
 AND SETBACK LINE ON ALL FLOOR PLANS AND ELEVATIONS TO
 DETERMINE ANY ENCROACHMENTS.
 5. PLEASE PROVIDE A COMPLETE GROSS SQUARE FOOTAGE TABLE
 INCLUDING ALL THE BUILDINGS IN THE PROJECT.
 6.PLEASE SUBMIT LANDSCAPE AND HARDSCAPE DRAWINGS,
 INCLUDING PHOTOMETRICS FOR STREETSCAPE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved